Plumbing Vent Definitions & Code FAQs
Plumbing vent and vent code questions and answers.
This article series defines plumbing vent system terms, distances, and functions, and other specifications and code requirements.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?
These questions and answers about plumbing vent codes and definitions were posted originally
at PLUMBING VENT CODES, DEFINITIONS, TYPES - home - be sure to check that ARTICLE INDEX and advice.
The basic plumbing vent terms are shown in this sketch, provided courtesy of Carson Dunlop Associates, a Toronto home inspection, education & report writing tool company [ carsondunlop.com ].
...
What's the clearance distance between a plumbing vent and a clothes dryer vent
I am planning to install a Dryer Jack on my roof with 41" sheet aluminum vent pipe going from it to dryer.
There is a 1 1/2" plumbing vent pipe exiting the roof about a foot from where I need the Dryer Jack installed.
Is this within code? On 2020-09-21 by Anonymous
Reply by- plumbing vent clearance to dryer vent
Anon:
Both of these are exhaust devices;
We provide the major plumbing codes at PLUMBING VENT CODES - code sources
where you are welcome to download any of those PDF files to take a closer look for yourself.
You won't find an explicit building code statement about clearance between a plumbing vent and a clothes dryer vent on a roof.
I would consider that I don't want lint clogging the plumbing vent outlet.
Please see details at CLOTHES DRYER VENT CLEARANCES & TERMINATION
Here are example dryer vent specifications
An exhaust hood should cap the vent to keep rodents and insects from entering the home.
Do not use an exhaust hood with a magnetic latch.
Locate the vent such that there is no less than 12" (305mm) between the bottom of the exhaust vent hood and the ground surface
Locate the vent such that there is no less than 12" (305mm) between the nearest side of a dryer exhaust vent hood and an adjoining wall or building inside corner
No obstructions by snow, flowers, rocks, plants, fences, walls, air conditioner condenser/compressor units, etc.
For other readers, a "Dryer Jack" is a roof exhaust vent such as the model shown below, from DryerJack = https://dryerjack.com/
In Louisiana is there a distance minimum code requirement between a stove vent and a plumbing vent on the roof exterior? - On 2020-11-12 by Aaron Hebert -
Reply by (mod) - code requirement between a stove vent and a plumbing vent on the roof exterior?
Aaron
Are we discussing a woodstove chimney?
If so, CHIMNEY HEIGHT & CLEARANCE CODES
...
What type of material is prohibited for a vent stack? Its on my Plumbing Inspector exam, and I cannot find the answer. I have been choosing Cast Iron pipe. - On 2019-12-16 by Anon -
Reply by (mod): lead pipe
Cast iron was permitted and often installed for plumbing vent piping in older buildings.
Also permitted: PVC, ABS, copper, and galvanized iron.
The ONLY plumbing vent material presently prohibited in most jurisdictions is lead pipe.
...
Intermittent plumbing vent dripping sounds keep me from sleeping
I have been unable to sleep in bedroom For 1 year due to intermittent drip noises (sounds sometimes like it’s hitting water but no leak) but especially loud waterfall noise in wall where stack is. You can hear the same noise in both bathrooms also which are side to side and there is a stack there also .
I am On first floor in 9 story building built in 1969. Cast iron in the vertical stacks. Plumbers are clueless and say the noise is not normal. Louder than it should be. I don’t know where to turn. - On 2020-10-15 by Pt
Reply by (mod) -
PT
I agree that a dripping water sound can be very disturbing.
Take a look at
DRIPPING WATER SOUND SOURCES
for some suggestions. Let me know what you think by posting follow-up remarks there;
As it may prompt help from another reader I'll also copy your question to that page.
Toilet won't flush, just swirls. Could someone working on our chimney have caused the problem?
I have a lower level half bath where the toilet suddenly will not flush (water just swirls around). There is no blockage.
We just had some chimney work done - is there ANY chance that the chimney worker screwed up something with the vent pipe that could be causing this?
If so, what are we looking for when we get up on the roof? I am grasping at straws here - I cannot for the life of me see what could suddenly be causing this issue. Thanks in advance for any help! On 2019-05-09 by Marcia
Reply by (mod) -
Marcia
Absence of venting on the drain line can interfere with good drainage, but more-likely, when flushing a toilet, if the vent were blocked the toilet would flush but you'd hear a glub-glub sound at smaller nearby sink, shower, or tub traps.
I'd start by checking the water level in the toilet bowl and the water level in the tank at the end of a toilet tank re-fill cycle after flushing.
More detailed help is at TOILET FLUSHES POORLY
...
New home construction, what is the code for venting all of the sewer pipes?
Is is legal to vent only to the attic or does it has to vent through the roof of other means to the outside?
Email address is "larrymiller@email.com" On 2020-08-02 by Larry Miller
Reply by (mod) - NO
Larry you NEVER vent just into the attic, never ever. The vent must go outside. The risks are odor, moisture, and even a methane gas explosion hazard.
@Anonymous,
how come I smell the sewer first thing in the morning when I brush my teeth
it hasn't always been like that maybe just the last couple of months
this is a 1969 mobile home unit. On 2018-05-21 by Anonymous
by (mod) - how come I smell the sewer first thing in the morning when I brush my teeth
I'd look for
- sulphur in the water supply first
then- check for blocked or slow drains or a blocked vent pipe that is causing siphonage out of the sink trap
DIAGNOSTICS: before you brush your teeth lean down and sniff the sink trap / does it smell particularly bad?
Then when you first turn on water in the sink, lean down (don't bang your teeth into the faucet) and sniff the water stream - does it smell bad?
...
In this condo some idiot cut the stack at the roof so he could take out a wall and just capped it off. We need to hook it back up by code so we can sell the condo. It runs right through the kitchen. He wanted an open kitchen I guess.
Is it just a matter of connecting ABS from ceiling to floor? I can’t find a sketch of this issue. Any help would be great On 2020-06-18 by Shad sellers -
Reply by (mod) -
Shad
I would cut off the cap and - as this is probably plastic piping - glue on a plastic ABS coupling that's the right diameter for your vent pipe, and then a sufficient extension of ABS upwards above the roof.See PLUMBING VENT REPAIR where I made a similar repair to a broken-off ABS plumbing vent stack pipe.
My photo above shows how we used a plastic soda bottle for a temporary, emergency "repair" until I could make the proper one described in the article I just cited.
OR: Ask your plumber if a vacuum breaker vent can be installed and will be approved by local code officials. If so it'd save a lot of trouble and expense caused by the idiot .
Daniel
I’m in Minnesota. I tied a lav vent into a main stack vent and realized I put the tee so the sweep is facing downward. I know I should of put it the other way.
But just wondering if it’s legal so I don’t have to cut everything out. On 2020-02-11 by loven -
Reply by (mod) -
Final authority to answer that question is your local plumbing inspector.
But there's a reason for respecting the direction of plumbing vent elbows or tees: proper functioning of the system.
You should cut out the improper tee and replace it with one in the proper orientation.
...
OK to conceal plumbing vent inside a concrete wall?
Vent can conceal concrete wall? what is the side effects if its conceal in concrete wall? which type of buildings i can install expose vent? is there any code requirements for expose or conceal? On 2017-05-19 by canerakcay
Reply by (mod) -
Can.,
My opinion is that a plumbing vent could be concealed inside of a concrete wall just as it could be concealed inside of a framed wall.However there are some differences.
How high above a planned new basement kitchen sink, below a window, does the 1 1/2" pvc vent pipe have to be...before running horizontally?
Currently this basement room is a laundry. Plan to move wash tub and washer and remodeling room to a small kitchen. Currently the wash or laundry tub was "T"ed into a vent pipe 66" from floor....is that HIGH enough? On 2017-12-26 by Roger
by (mod) - proper height for a basement and washer sink vent? - Above the flood rim
It should be above the flood rim of the sink
The vent stack in the photo at the top of this page appears to be more or less perpendicular to the slope of the roof rather than vertical.
Is there a reason for this? On 2017-09-16 by Caper
by (mod) - Risk of roof leaks at plumbing vent flashing
Caper:
Thanks for the astute question.No there is no valid reason for the angle shown in our photo, and worse, using a pre-fab stack vent boot flashing with the vent pipe at an angle as shown means that leaks are likely.
That simply was how the plumber cut the hole and routed the vent stack out through the roof.
She should have routed the vent vertically straight up through the sloped roof surface, not at the angle in this picture.
Plumbing vent boot flashing kits are designed to handle the sloped roof surface, as you'll notice in the photo: there's more metal on the "down slope" side of the boot flashing.
Watch out: a plumbing vent that is at too much of an angle with respect to the plumbing vent boot flashing may find leaks around the vent in conditions of heavy rain or melting snow or ice.
Do you need to run the vent line at an angle or not? On 2018-05-01 by Anonymous
Reply by (mod) -
If you mean does the vent pipe have to be at 90 degrees to the roof surface, NO. Straight up is fine.
I'm creating an upstairs apartment. I'll be tying in to the downstairs building drain. It's distant, so I'm wondering if I should vent the upstairs separately. In other words, is it ok to have 2 roof vents? Thanks! On 2017-12-19 by Steve
Reply by (mod) -
Yes I'd add a second roof vent, that's perfectly permissible.
How about running from sink to tub and toilet then out roof?
Can you tie them in this way?
If so would I need to run pipe flat on the rafters or angel it just a little up to where it's going to vent out roof? On 2018-05-01 by Anonymous
Reply by (mod) -
You generally don't want a line to be dead flat as condensate could accumulate and in a cold area, freeze.
Use the InspectApedia.com search box found above and find our article on DRAIN FIXTURE UNITS and you'll see how to calculate how many fixtures can go onto a single vent line depending on size and the amount of water each fixture uses.
My question is does the vent have to come off the end of the header line or can it be placed in between any of the fixtures and just cap the end. Having issues with accessibility on the end of the line.
I have a sink with a 2” vent tying in at the bottom of the riser already as shown in the picture.
This main vent acts as a vent for
2 toilets
2 showers
3 sinks
1 tub
Let me know what you think. On 2019-12-16 by Tyler
Reply by (mod) - use "wet vent" code - link is here
Tyler
You can run a vent from other than one end of the drain but that will change fixture drain operation into "wet vents" for some fixtures
details are at DEFINITION of WET VENTED PLUMBING FIXTURES
I’ve recently installed a basement shower where there used to be a bathtub.
We moved the drain approx 2 feet to accommodate this.
The drainage is now very poor on occasions but perfect at other times.
I’ve been told this may be a venting issue but the previous bathtub drain did not have this issue.
I put new tiles over this and can’t rip them up to access this. Is there any other possible fix?
Thanks 2018-03-25 by Jimmy Doyle -
by (mod) - moving a shower drain two feet - can still be vented OK
Moving a drain 2 ft ought not itself to cause a problem IF you maintained 1/8" to 1/4" per foot slope. If your drain slopes properly then I suspect the problem is a partial blockage or inadequate venting.
In my back yard i have a vent pipe that runs straight down to the pipe that runs out to my alley. If i move this pipe does it have to straight up and down or can I elbow it to move it say 5 feet. - On 2019-08-04 by dave
Reply by (mod) -
If it's truly only a plumbing vent then you can probably move it over a bit. Look at the total vent line distance to be sure you're within code.
However if it's a sewer line clean-out access you may make cleaning the line more difficult in the future.
What do I do with the plumbing vent piping connections when I move the bathroom sink?
I'm moving a bathroom sink to opposite wall across the bathroom.
The current location is tied in with toilet to 3" sewer drain line and 2" vent pipe.
What do I do about venting the sink 1.5" pipe once I move the sink across the bathroom to opposite wall and tie into the 3" drain/sewer line. Also this project is upstairs - On 2020-07-04 by Joemomma
Reply by (mod) -
You would either route a vent line around in the wall / ceiling from the new location or you might be permitted to use an AAV or air admittance valve or Studor vent.
There is a commercial job that requires air vents no direct draining i need to put a hand sink and doublewash tub in can I connect those two drains into the 1 1/2 drain pipe from another wash tub already going into the air vent or do i have to bring a new 3 inch drain and air gap vent over to the new tubs? On 2018-05-02 by UNKNOWN CODE
Reply by (mod) -
See if your local inspector will approve
An air admittance valvesee AIR ADMITTANCE VALVES AAVs - Studor Vents Explained
Can you plumb a drain vent under the sink on a outdoor grill island? On 2020-06-28 by tracymayo57@gmail.com
Reply by (mod) -
Sure, Tracy, but you may need to use an AAV or air admittance valve .
see DEFINITION of AIR ADMITTANCE VALVES / STUDOR VENTS
...
How many fixtures can a 3-inch vent support?
How many Fixtures can you put on a 3" vent. What is the furthest distant you can be away from the vent? On 2017-05-04 by Tim
by (mod) - consider fixture type not just number, and look at this DFU table
Tim in the article PLUMBING VENT CODES, DEFINITIONS, TYPES see the
Tables of Plumbing Drain Pipe & Vent Pipe Sizes & Critical Distances to Plumbing Fixtures
Also see the calculations at PLUMBING DRAIN FIXTURE UNITS DFUs -
Can I rough in a double vanity with a 1 1/2 pipe On 2017-05-03 by Richie
Reply by (mod) -
Richie,
See https://inspectapedia.com/plumbing/Plumbing-Vent-Distance-Codes.php#Sizes where we discuss the size of vent pipe needed.
What was the waste line size plumbing code in 1992 in a residential home in Alabama? On 2020-01-04 by Mickey
Reply by (mod) -
Mickey
I am so sorry that I cannot answer your question: there is no one "right answer"as the necessary waste pipe diameter depends on the particular drain line being installed and what kind of plumbing fixtures it serves and the number of them.
The plumbing code has the installer calculate DFUs - drain waste vent fixture units DFUs = a number that then, combined with the length of run, determines the drain diameter needed.
Details are at PLUMBING DRAIN FIXTURE UNITS DFUs
You might check with your local building department to see if they have copies of the 1992 Alabama residential plumbing code on file;
I also found some older Alabama codes at the Internet Archive by searching for "History of Alabama Plumbing Code"
...
...
Continue reading at PLUMBING VENT CODES, DEFINITIONS, TYPES - topic home, or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see these
PLUMBING VENT CODES & DEFINITIONS FAQs at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Search the InspectApedia website
Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.
In addition to any citations in the article above, a full list is available on request.