Oil Heat Furnace Defects List & Home Inspection Education
This article lists significant oil-fired heating furnace (warm air system) defects, definitions, and home inspection education topics.
The building defects and inspection points listed in these articles also guide homeowners and home buyers to building areas that merit careful attention and often point areas of safety concern or important maintenance and repair tasks.
Page top illustration of an oil fired furnace courtesy of Carson Dunlop Associates, a Toronto home inspection, education & report writing tool company [ carsondunlop.com ].
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?
1. List the materials, function and location of the components of a typical oil fired forced air furnace including ? the fuel storage and supply system, burner, heat exchanger, draft regulator(barometric damper), vent connector, combustion air supply, cabinet, controls, ducts, registers, and grills.
2. Describe the features of adequate installation and repair technique for oil fired furnaces.
3. Define the following terms: oil safety valve, fire safety valve, atomizing oil burner (gun type burner), electrode, flame retention head, refractory (fire pot), blast tube (draft tube), transformer, fuel pump, ignition transformer, primary control (primary controller, stack relay, primary relay), flame sensor (Fire-eye, photo cell, cad cell), barometric damper (draft regulator), vent connector, side wall venting, automatic vent damper.
4. Describe the normal operating cycle of an oil fired forced air furnace from call for heat to shut down.
5. Outline the typical life expectancies of oil fired warm air furnaces.
6. Identify the codes or standards which apply to oil fired appliances and warm air furnaces in your area.
1. Describe the inspection procedure for oil fired warm air furnaces.
2. Identify the following common defects listed on the next page.
3. Describe the implication of each defect.
4. Identify the safety issues for the inspector and occupant of the home(fire, oil spill, combustion product, pollution, injury due to moving parts).
5. Communicate findings to client verbally and in writing, recommending corrective action where needed.
• Empty
• Leakage
• Located outside, not suitable for outdoor use
• Rusting
• Underground (warnings)
• Unsafe location (clearance distances, unprotected)
• Abandoned
• Damaged or corroded
• Tripped
Watch out: the combustion chamber and chamber liner must be intact both for proper combustion and also to help prevent a building fire.
See OIL BURNER COMBUSTION CHAMBER LINER INSPECTION
Also see COMBUSTION CHAMBER or CHAMBER LINER DAMAGE FAQs
• Leak
• Missing caps
• Undersized vent
• Plastic
• None installed (missing)
• Shared
• Improper location
• Inadequate draft air
• Inoperative
• Misadjusted maladjusted JDG
• Rusting
• Spillage
• Missing
• Corrosion, damage, crimped
• Leak
• Undersized
• Unprotected
• Improper material
• Inadequate combustible clearance
• Poor support
• Poor slope
• Poor connections
• Poor manifolding
• Poor insertion into chimney
• Rust, dirty, obstructed
• Vent connector too big, too small
• Vent connector too long
Dead end Flues
• Dirty
• Leak
• Missing
• Inadequate combustion air
• Dirty
• Incomplete combustion – soot
• Inoperative
• Leaking
• Short cycling
• Too close to combustibles
• Vibrating, noisy
• Corroded vents
• Excess temperature rise
• Poor vent location, arrangement
• Reliability
• Damaged cells
• Dirty
• Improper orientation
• Inoperative
• Mis-wired
• Missing components
• Combustible clearances
• Mechanical damage
• Missing components
• Obstructed air intake
• Rust
• Scorching
• Anticipator problems
• Damaged
• Dirty
• Loose
• Not level
• Poor adjustment or calibration
• Poor location
• Clogged pad, mesh or nozzle
• Dirty
• Inoperative motor or solenoid valve
• Leaks
• No duct damper
• Poor location
• Dirty
• Fan belt loose, worn, damaged
• Inoperative
• Noisy
• Overheating
• Poorly secured
• Running continuously
• Rust
• Too small
• Unbalanced or vibration
• Balancing damper adjustment
• Dirty, obstructed collapsed
• Disconnected or breached JDG or damaged ducts
• Excessively long runs, excessive elbows
• Wire or pipes in ducts
• Registers or grilles (for return air) in garage
• Rusting or dirty
• In-slab ducts
• Mechanical damage
• Leaky joints
• Insulation missing, damaged
• Filter problems
• Undersized
• Weak airflow
• Improperly wired
• Missing cover
• Scorching
• Set wrong or defective
• Fan problems
• Cabinet problems
• Control problems
• Domestic water too hot
• Inadequate heat for house
• Inoperative, inefficient pumps
• Inoperative water heater
• Leaking, clogged coils
• Water control problems
Readers should see HEATING SYSTEMS for our complete list of articles on this topic. Also see HOME & BUILDING INSPECTORS & INSPECTION METHODS.This article series, beginning at BUILDING DEFECTS LISTS, provides lists of common building defects and basic defect knowledge that also outline recommended curriculum content for home inspector education.
Watch out: these inspection lists do not list all possible defects for the systems discussed, and not all home or building inspectors will examine all of the items listed here. CONTACT us to suggest corrections or additions to articles at this website.
Also see FURNACES, HEATING and DUCT SYSTEM DESIGN SIZE & DEFECTS.
These curriculae and building defect lists are based on smilar curriculum documents first prepared by Joe Scaduto, an ASHI member who prepared course material for Northeastern University's Building Inspection Certificate program in 1988, subsequently by DF, InspectApedia's editor, for New York University ca 1988 and later, with others, recommended to ASHI, the American Society of Home Inspectors.
ASHI did not adopt this material though currently that association as well as others offer extensive HOME INSPECTOR EDUCATION material. The curriculum and lists of defects are informed by additional analysis of the process of home inspection that was developed beginning Calgary, AB for Canadian and U.S. home inspector education and certification examinations in 1997. Other early contributors to home inspection education in the U.S. and Canada include Dr. Jess Aronstein, Alan Carson, Mike Casey, Mark Cramer, John Cox, Dwight Barnett, Douglas Hansen, Rick Heyl, Larry Hoytt, Bill Merrill, Kevin O'Malley, Dennis Robitalille, Keith Peddie, Pat Porzio, Roger Robinson.
...
Continue reading at FURNACES, HEATING or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see these
DEFECTS LIST - HEAT FURNACE OIL at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.
Search the InspectApedia website
Note: appearance of your Comment below may be delayed: if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.
Only one image can be added per comment but you can post as many comments, and therefore images, as you like.
You will not receive a notification when a response to your question has been posted.
Please bookmark this page to make it easy for you to check back for our response.
IF above you see "Comment Form is loading comments..." then COMMENT BOX - countable.ca / bawkbox.com IS NOT WORKING.
In any case you are welcome to send an email directly to us at InspectApedia.com at editor@inspectApedia.com
We'll reply to you directly. Please help us help you by noting, in your email, the URL of the InspectApedia page where you wanted to comment.
In addition to any citations in the article above, a full list is available on request.