Thermostat Heat Anticipator Explanation
Simplified instructions for setting the heat anticipator in a Honeywell T87 and similar thermostats.
This article series explains what a heat anticipator is on a wall thermostat, where to find it, what it looks like, why we adjust the heat anticipator, how we do so.
We list the recommended heat anticipator settings.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?
Honeywell's Instructions for Setting the Heat AnticipatorUsing the Honeywell T87 Thermostat instructions (see [3a] inReferences or Citations ] as an example, and quoting:
If the T87F is used for 3-wire, spdt, heating-only (Series 20) control (Fig. 6), set the heat anticipator for 1.2 (far left end of scale).
A fixed resistor-type heater is provided in the 137421A or 198170A Wallplate for this application.
For other control applications, proceed as follows.
Adjust anticipator to match current rating (Amps) of primary control. Rating is usually stamped on the control name- plate.
Move the heat anticipator pointer or indicator to the marking that matches this rating.
The pointer may be moved with fingers or pencil point through the hole shown in in the figure below.
If the current rating is not given, proceed as follows before mounting the thermostat:
1. Connect an ac ammeter of appropriate range (0 to 2.0A, for example) between the R and W terminals on the wallplate or subbase
2. Let the system operate for one minute before read ing the ammeter.
3. Move the anticipator indicator to match the ammeter reading.
A slightly higher setting to obtain longer burner-on times (fewer cycles per hour) may be desirable for some systems. [3a]
According to Honeywell, set the heat anticipator to a lower number to let the heat run shorter
or make the room a bit cooler in relation to the set point on the thermostat by avoiding room temperature "overshoot" as additional heat arrives in the room by radiation from heating baseboards or furnace run-on time after the burner on the boiler or furnace has been stopped by the thermostat.
According to Honeywell, set the heat anticipator to a higher number to cause the burner to run longer
- with a longer on-cycle.
When we adjust the heat anticipator on a thermostat that has one, we are fine-tuning the amount of heat anticipation that the device is allowing.
Watch out: Some modern DMMs that include a clamp-on ammeter might measure accurately down into the very few milliamp range that is needed, but most do not. In its instructions for using a mini milli-amp meter (described in detail
at HEAT ANTICIPATOR SET & TEST by AMMETER)
the company makes clear that a precise adjustment of a heat anticipator to a specific individual heating system installation needs to make a precise measurement of the current in the entire thermostat circuit.
Using the Honeywell CT87A,B,J Round® Thermostat instructions (see [3b] inReferences or Citations ] as an example, and quoting:
NOTE: If the furnace stays on beyond the thermostat set temperature, move the anticipator pointer down by .1 ampere.
If the furnace shuts off before the set temperature is reached, move the anticipator pointer up by .1 ampere.
Watch out: Never adjust the anticipator below .3 ampere. [b]
You'll notice that the word "Longer" and the arrow shown in the earlier T87 Thermostat heat anticipator sketch [drawing above on this page] are not shown in Honeywell's line-drawing illustration but the word "LONGER" with or without a clarifying arrow appears in some of our photos of the actual heat anticipator.
As we discuss below, an arrow below the word "LONGER" is hard to see, but it's there.
Above: from Honeywell's T87 thermostat instructions we see that for steam heat, whose cast iron radiators have a lot of thermal mass and so tend to keep generating heat after the thermostat is satisfied, there is the greatest risk of heat "overrun" or "too much heat" so Honeywell says set the heat anticipoator to 1.2A - the highest number on the left of the heat anticipator scale.
Since more current (Amps) in the heat anticipator = more heat = heat off sooner, we can infer that the numbers on this heat anticipator scale must be Amps (not resistace or Ohms).
The explanation of which way to move the heat anticipator indicator for a longer burner on-time remains the same as for the T87:
For longer burner on time we want the heat anticipator to heat up less so that it warms the thermostat less, so we move move the heat anticipator indicator to a LOWER Amps number on the scale - less current (or more resistance from the longer wire length in the heat anticiaptor) means less heat will be generated by the "heat anticipator" winding.
So the thermostat is "pre-warmed" less, so the actual heating boiler or furnace will stay on longer.
Photo above: I've marked Honeywell's recommended heat anticipator settings in yellow along the scale: Steam heat, which tends to overshoot the room temperature, gets shut off sooner at the higher Amps number;
Electric heat, which has the least tendency to "overshoot" the room temperature and warm air heat which also has that property, have much lower heat anticipator scale numbers (Amps) of 0.4 for warm air heat and 0.3 for electric heat.
In our enlargement below, notice that below the word LONGER is an arrow pointing to the left! It points towards the higher Amps numbers. That's been the source of confustion among thermostat users for many decades.
Just remember higher Amps = more current = more heat = heat anticipator warms the thermostat more = heat turns off sooner.
Really? Honeywell was confusing as all getout in labeling of the heat anticipator on some thermostats.
In our photo above, notice that the word "LONGER" (we want the heater to stay on longer) is embossed at the low-end of the resistance scale, under the .10 and .12 numbers.
Lower resistance means more heat will be generated, so the little coil in the heat anticipator will heat up the thermostat more, telling it to turn off sooner.
An arrow under "LONGER" is there, but very hard to see, even on the actual thermostat. So I drew over it in yellow to make clear.
The arrow points to the left, towards higher current numbers = more pre-heating in the thermostat = shorter heat-on cycles. I've outlined the hard-to-see arrow in yellow.
I think Honeywell put the word "LONGER" and the left-pointing arrow on the "wrong" end of the scale simply because the mechanical design of the device gave enough space there for that text and arrow.
Heating System Type |
for the CT87 Thermostat |
|---|---|
Steam Heat |
|
Hot Water Heat |
|
High-Efficiency Warm Air Heat |
|
Standard Warm Air Heat |
|
Electric Heat |
|
Adapted, expaned and illustrated from Honeywell CT87A,B,J Round® Thermostat Low Voltage (15 to 30 VAC) Thermostat and Mounting Hardware Installation Instructions Honeywell Corporation, cited in detail
If the furnace stays on beyond the thermostat set temperature, move the anticipator pointer down by .1 ampere. That is, to a lower number.
If the furnace shuts off before the set temperature is reached, move the anticipator pointer up by .1 ampere. That is, to a higher number on the heat anticipator scale.
Watch out: Never adjust the anticipator below .3 amperes.
Below we've moved the pointer back over to 0.3 amperes on the heat anticipator scale.
This nice summary was provided by reader in a comment originally posted as a comment to the
article HEAT ANTICIPATOR ADJUSTMENT.
For a detailed explanation of how the thermostat heat anticipator actually works
see HEAT ANTICIPATOR OPERATION.
The main reason for the anticipator adjustment is to match the thermostat with different furnaces.
From the factory the anticipator resistor is adjusted so that its warming effect (power dissipation) is nearly the same for different furnaces. That way the thermostat will behave the same way, no matter what furnace it is used with. But sometimes fine-tuning is needed as we explained above.
The heat anticipator is connected in series with the coil that energizes the gas valve [or turns on the hot water circulator if heat is by hot water].
The anticipator resistance is much lower than the resistance of the gas valve coil [or the circulator relay coil]. That means that no matter where the anticipator is adjusted, it does not appreciably affect the current in the circuit.
In other words, the current through the anticipator is constant for your furnace [or hot water boiler or steam boiler], no matter where the anticipator is adjusted.
The warming effect of the heat anticipator is
P = R x I**2
where
“P” is the power dissipated by the anticipator
“I” is the gas valve current rating in amperes, and
“R” is the anticipator resistor.
“I” is relatively constant for your furnace. “R” is adjusted to so that “P” is the nearly the same for different furnaces.
That is why the anticipator is calibrated in amperes, for easy matching to your furnace. It is also why some manufacturers refer to the adjustment as “fixed”.
Tweaking:
OPINION of QP: You can tweak the anticipator if you want to, but that is not the main reason for the adjustment.
Note: as we discuss
at HEAT ANTICIPATOR OPERATION there is some confustion between power and heat and current and watts.
That article gives a clear explanation of the relationship between electrical resistance and heat - the theory that explains why and how a thermostat heat anticipator works.
More details are at ELECTRICAL RESISTANCE vs HEAT GENERATED.
...
Below you will find questions and answers previously posted on this page at its page bottom reader comment box.
Can you explain to me why some thermostats include a heat anticipator control? qprew7u - 12 April 2015
Answer by Moderator: to fine tune the heating system on-cycle to account for room temperature "Overshoot"
Especially with hot water type heating systems, when the heater itself shuts off the residual hot water in the heating radiator (and less in baseboards) continues to send heat into the occupied space. So if the room thermostat turns off the heater exactly when the room temperature is sensed to be right at the thermostat setting, the room may become a bit warmer than occupants want (and heating fuel will be wasted as well).
The heat anticipator, by "anticipating" the effect of this residual heat, warms up the interior of the room thermostat so that it will shut off the building heating system slightly early, avoiding this room temperature overshoot.
Because different types of heating system (hot water, steam, air, and radiation devices varying among baseboards or radiators) have different propensity to over-deliver heat after the thermostat has shut down, thermostat manufacturers like Honewell add, on some (not all) thermostats, a heat anticipator device to prevent that problem.
A furnace has two principal heat controls:
- The thermostat controls the gas valve on a gas fueled heater, or the oil burner's primary control / aquastat on an oil fired heating system.
- On a forced warm air furnace, the blower temperature switch controls the blower.
The furnace blower continues to run after the thermostat opens, for efficient heat exchange
On a furnace the blower is scavenging the remaining heat in the heat exchanger and it's avoiding heat exchanger damage that could occur if that component overheats and cracks.
QP's remarks describe forced warm air furnace heat but keep in mind that heat anticipators are used on hot water heating systems (baseboards and radiators) as well.
Any heating system: forced warm air, gravity warm air, hot water heat through radiators or baseboards, or steam heat, can "over-shoot" and continue to deliver more heat to the occupied space after the thermostat is satisfied.
A hot water heating system has different controls:
- The oil or gas burner on a hot water heating boiler is turned on or off by the temperature of the boiler water (via the boiler's Aquastast control)
- In U.S. installations the thermostat is turning the circulator on or off to send hot water to the spaces to be heated.
In Canada typically the circulator runs continuously and the thermostat is turning the boiler on and off directly. - Ed.Only if the amount and duration that over-shoot is really a problem should you think about adjusting the heat anticipator. - Ed.
The heat anticipator “anticipates” that extra heat delivery by warming the thermostat to shut it off early.
The anticipator also creates hysteresis, so the furnace or boiler does not cycle too often.
QP means by hysterisis that we introduce a lag or delay between the change in room temperature and the response of the thermostat.
However the heat anticipator is only operating to turn the thermostat OFF a little "early". It does not introduce any delay when turning the thermostat back ON. - Ed.
Lower heat anticipator settings:
According to Honeywell, setting the heat anticipator to a lower number (lower Amps number) setting will result in shorter burner on-cycles, ie less room-temperature overshoot.
A typical heat anticipator scale runs beetween a low of 0.10 Amps and a high of about 1.2 Amps.
Higher heat anticipator settings:
According to the manufacturer, a higher heat anticipator setting will result in less self heating of the thermostat, longer burner on-cycles, and possible overshoot of the room temperature. -
For an explanation of the relationship between electrical resistance and heat that thus explains how a heat anticipator adjustment works,
see ELECTRICAL RESISTANCE vs HEAT GENERATED. Chubby541 10/31/2012
Moderator Reply: heat anticipator setting numbers versus heat-on cycles
Thanks Chubby for prompting us to make sure that our explanation of the thermostat heat exchanger is precisely accurate and more clear.
As you can see in our closeup photo of the heat anticipator adjustment scale, the word "Longer" and an arrow are stamped into the end of the scale with the lowest number. The arrow points away from the low end towards the high end of the scale.
Honeywell is saying for a longer heat-on cycle (less heat anticipation) move the heat anticipator adjustment in the direction of the arrow - towards the higher amps end of the scale.
[Click to enlarge any image]
The heat anticipator is an electrical resistance heater that provides a tiny source of extra heat right inside the wall thermostat of some older room thermostats like the Honeywell T87 bimetallic spring mercury bulb model.
Heat anticipators are found in the T87® and the CT97A,T,J Round® room thermostats by Honeywell as well as in some other thermostat brands discussed here.
Making a little extra heat inside the thermostat means that the thermostat thinks the room is a little warmer than it actually is - which leads the thermostat to stop calling for heat a little early - hence the name "heat anticipator". The thermostat is anticipating that some additional heat will arrive into the room after it turns off the boiler.
More heat inside the thermostat means sooner burner off time (shorter burner on-cycles) and less room heat overshoot.
By Ohms Law, I = E / R or
- Current (Amps) x Resistance (Ohms) = Voltage = E
- Voltage / Resistance (Ohms) = Current (Amps) = I
- Voltage / Current (Amps) = Resistance (Ohms) = R
We can also write
- Volts x Amps = Watts
The relationship of electrical resistance to temperature is also derived from Ohms law and is written as follows, where (a) is the temperature coefficient of resistance: [23]
- a = 1 / Ro dRo / dT Ohms/Ohms/oC
Where for example watts can be giving us energy in the form of light, heat, or most likely a mix of the two.
This is true in general or simplified terms. A true "power" equation that relates power dissipation and current through electrical resistance P = IE ; P = I2R; is a little more complicated thanks to James P. Joule but we'll skip that more technically correct approach for this discussion.
Details are at DEFINITION OF AMPS, ELECTRICAL CURRENT
Reader Follow-Up: moving the heat anticipator to lower numbers gave shorter burner on-time
The Honeywell documentation is correct. Moving the anticipator to the RIGHT, i.e. LOWER current numbers, results in SHORTER cycle time. Why am I so sure?
1. Just tried it with my forced hot air system; moved from 0.8 to 0.4. It turns on/off twice as often now.
2. The current numbers on the anticipator aren't how much current it's generating (really, how would it do that?), it's how much current it's EXPECTING.
At lower settings, it is EXPECTING less current; since the amount of current the BOILER produces is constant, this results in more Joule heating of the anticipator and a faster cycle.
3. That "LONGER" text? Yeah, look more closely. It's got an arrow POINTING TO THE LEFT. It's too fuzzy to see in your picture; look on a real device. - C.K. 11/30/2013
The arrow does not point toward higher resistance, it points toward higher EXPECTED CURRENT (those are measurements in Amperes, as you correctly note!) and hence LOWER RESISTANCE: if the current coming from the boiler is HIGHER, the anticipator needs LESS resistance to produce the same amount of heat. (This is simply keeping I²R, i.e. the total heat output, constant.)
Example: boiler sends 0.4 A through the anticipator. If the anticipator is set to 0.8 A, it will heat up LESS (because it is expecting MORE current) and hence the cycle time will be LONGER than if the anticipator were set to 0.4 A.
I think the confusion in earlier versions of this article ("I can't explain this [yet] because at lowest resistance you'd think that we are not using the heat anticipator's resistor") stems from the assumption that moving the anticipator toward lower values uses less of the heating element, when in fact it is the other way around (to keep I²R constant).It's not obvious from looking at a T87 which end of the resistance coil is connected (I would assume the small end, but you seem to assume the large end.)
Have you tested this with a multimeter?
Moderator Reply: exactly right: shorter wire, less resistance, more current flow, more heat anticipator heat output, earlier thermostat shutoff, shorter heat-on cycle
Thanks C.K. I'm not sure about your interpretation of "expecting" and anticipation, but Honeywell agrees with you about which way to move the heat anticipator setting for longer or shorter burner on-cycles.
Please click on any InspectApedia image to see a larger, more detailed image, including showing the arrow on the heat anticipator.
And in theReferences or Citations section of this article you can find a link to the installation instructions for the Honeywell T87F from which we quote above. I agree with you about the direction of the arrow you cite.
Lowering the heat anticipator to a lower number gives shorter heat-on times
Honeywell Corporation agrees that lowering the heat anticipator from 0.8 to 0.4 will give shorter heat on-times which, in turn, would typically result in more frequent burner on-off cycling - which is on an oil fired system and on some gas fired systems a less efficient way to run a heater.
\That's because lowering the Amps number from 0.8 to 0.4 cuts the current flow (Amps) in half, cutting the heat anticipator output accordingly.
By cooling the heat anticipator we stop pre-heating the thermostat's room temperature sensor as much.
By stopping the temperature sensor pre-heat we stop turning off the heat early.
We turn it off sooner.
That gives shorter on-imes and thus more frequent heat operation.
Raising the heat anticipator to a higher number gives longer heat-on times
In their T87 Honeywell states that a higher number on their heat anticipator scale gives a longer burner on-time.
That's because the heat anticipator pre-heats the thermostat less at higher Amps numbers, so the thermostat doesn't turn off "early" - it turns off "later" so the heating system will remain on longer.
A slightly higher setting to obtain longer burner-on times (fewer cycles per hour) may be desirable for some systems.
And again in their CT87A,B,J Round Thermostat instructions Honeywell also states that moving the heat anticipator up will give the burner a longer on time.
If the furnace shuts off before the set temperature is reached, move the anticipator pointer up by .1 ampere.
In preparing the original article and again in 2017 for confirmation of our understanding of heat and electrical resistance and thus of how the heat anticipator actually works, I checked with Dr. Jess Aronstein, an electrical engineer specializing in forensic work.
Here is his comment:
The anticipator heater operates with a constant voltage applied to it. When you decrease its resistance, at constant applied voltage, the current increases (E=IR).
The heat generated is proportional to the current squared times the resistance (heat = I-squared x R).
So if you set to half the resistance, the current in the active portion of the heating element is double the original, and the heat generated is the current squared times the resistance which calculates to double the heat relative to the original setting. - J. Aronstein to D Friedman, private email 2017/11/01
This is not a case of increasing the heat output by increasing electrical resistance in the circuit. It's the opposite.
On a thermostat that uses a heat anticipator, moving the anticipator's heating device sliding adustment to a higher Amps number (more current) will be seen to actually be using a shorter segment of the nichrome wire that comprises the heating element. That's actually lowering the resistance, permitting more current to flow, and generating more heat.
The numbers and resistance and heat effects in the original manufacturer's instructions can be a bit confusing.
In answer to your question of how the heat anticipator would know how much current it is generating, the anticipator is not generating current.
The heat anticipator is a variable resistor that varies by changing wire length. It is resisting current flow and generating heat. When we shorten the anticipator's wire length by moving the adjuster we are sending the same voltage through a lower-resistant shorter wire - the current flow increases and more heat is genearted.
The heat from the variable resistor warms the thermostat sensing bimetallic spring, thus fooling the thermostat into thinking the room is warmer than it actually is.
The heat anticipator is anticipating that additional heat is going to arrive in the room from water (or less-so by air flow).
We can measure resistance or current flow in Amps at different points along a wound resistance coil. The scale on the heat anticipator corresponds roughly to the position along the coil at which the moving contact touches the coil.
Moving the point of contact to a place where electricity has run through more wire means more resistance (less heat from the heat anticipator to warm up the thermostat), while less wire length means less resistance (so more heat is generated, the heat anticipator gets hotter so turns off the heater sooner) - Jaffee (1997).
Bottom line: by anticipating additional heat arrival
(hence the device name "heat anticipator") and by shutting off the burner a bit sooner than otherwise, the heat anticipator is reducing room temperature overshoot - warming the room higher than the thermostat requested.
When you raise the current value on your heat anticipator setting, according to Ohms law the resistance goes down as the amperage is inversely proportional to the voltage R=E/I which gives off less heat in the anticipator coil which allows the furnace or boiler to run longer - (Feb 26, 2014) Bill Martino
Reply by mod:
Thank you for the clarification, Bill. This topic has generated many comments, which underscores how confusing it can be for some readers.
Longer burner on time has to be due to less heat coming off of the heat anticipator (less add-on warming of the thermostat's temperature sensor).
More heat is generated when the resistance is lowered, as you'll read in the article we cite below.
Reader finds it funny that the heater will cycle on and off
What I find amusing about a thermostat with a heat anticipator is that a thermostat that is NOT controlling any sort of furnace or heat source, but which is adjusted to near the current temperature of the room, can cycle on and off despite the room temperature not changing. (Nov 17, 2014) RH in CT
Reply by mod:
RH the thermostat should not be making you laugh - nor cycling on and off as you describe. I'd check further. Check for shorted thermostat wires.
Details are at ELECTRICAL RESISTANCE vs HEAT GENERATED
by (mod) - which way is the heat anticipator current flowing?
Thanks so much Fab.
You are quite correct. Sitting on my lab desk is a Honeywell T87 mercury bulb type TT with a heat anticipator, dis-assembled for inspection. I'll post more of those photos ...
butRemember that this is a 24VAC current - alternating current, so its flow doesn't have a "direction". But it does have a path, that I've indicated on my photo above. So you can see that moving the slider to the right gives a shorter amount of wound wire, less resistance, more heat anticipator heat, so the system will shut off a bit sooner.
In photos of these thermostats don't just "look" at the apparent position of the mercury bulb and the position of the nichrome wire-wound variable resistor heat anticipator device.
One has also to follow the actual circuit, often a tiny brown wire that's mostly hidden under other components. When I'm back in the lab I'll expose those details in future photos to go along with your comment.
What adds to the confusion is that the company varied the direction of the scale, the shape of the variable resistor winding, which end was wide and which was narrow, etc. in various versions of the T87 over the years.
Both of your factoids are helpful.
Thank you. Daniel Friedman
Source of confusion stems from lack of a clear depiction of which end of the anticipator resistor is connected to the mercury switch.
I could find that info nowhere! But it can be deduced from two factoids:
1) The anticipator resistor has virtually no influence on the controller current through the circuit.
2) Honeywell literature indicates the anticipator resistor delivers approximately the same amount of heat to the bi-metal strip when the current setting corresponds to the control circuit amperage, in order for the thermostat to be useful for the widest variety of control systems.
Therefore the highest current position (small end of the resistor) must connect to the mercury switch so it doesn't over-heat the bimetal temp sensor.
Therefore, current flows from the contact point on the resistor to the small end of the resistor to the switch.
The other large end is not connected. On 2020-01-22 by fabrice002 -
Reply by Moderator
Right, Fabrice. See our heat anticipator illustrations here and at ELECTRICAL RESISTANCE vs HEAT GENERATED - Daniel Friedman
Does the heat anticipator affect air conditioning ?
How does anticipater affect air conditioner? On 2019-05-19 by IkeE -
Answer by (mod) - no
No Ike a heat anticipator ought to be off when there is no call for heat.
...
Continue reading at HEAT ANTICIPATOR OPERATION or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see these
HEAT ANTICIPATOR ADJUSTMENT - T87 at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Search the InspectApedia website
Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.
In addition to any citations in the article above, a full list is available on request.