Electric Heating Baseboard Requirements Electric baseboard heat linear feet needed: how to determine how many feet of electric baseboard are needed to heat a building, space, or area.
Electric baseboard heat installation, calculations, wiring: in this article series we explain how to install and wire electric heating baseboards.
Here we also compare the features of a portable or permanently installed electric fan heater with electric baseboard heat.
This article series answers most questions about all types of heating systems and gives important inspection, safety, and repair advice.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?
Here are some electric heat rules of thumb that will help you see if the electric baseboard already installed in your building will be sufficient. These guesstimates presume your building is located in a climate where there are real winters, not in southern states.
A larger room or a poorly-insulated building will need more watts of electric heat (and pay higher electrical bills).
[Click to enlarge any image]
As Carson Dunlop Associates' sketch shows, you can figure that your electric baseboard is providing about 250 watts of electric heat per foot of baseboard length.
If you don't know what kind of heat your building uses, we explain how to figure out the answer
at HEATING SYSTEM TYPES.
Below is a table of typical electrical heater wattage requirements or heater size based on room area in square feet.
Electrical Baseboard Watts, Length, Circuit Size Chart1 |
||||
| Room Area | Electric Heat Needed | Baseboard Length | Baseboard Watts | Circuit Size |
| 8 x 8 = 64 sq.ft. | 320 - 512 Watts | 2 ft. | 500 W | 15 A / 120V or 240V |
| 8 x 10 = 80 sq.ft. | 400 - 640 Watts | 2.5 ft. | 640 W | 15 A / 120 V or 240V |
| 10 x 10 = 100 sq.ft. | 500 - 800 Watts | 3 ft. | 800 W | 15 A / 120 V or 240V |
| 10 x 12 = 120 sq.ft. | 600 - 960 Watts | 4 ft. | 1000 W | 15 A / 120 V or 240V |
| 15 x 20 = 300 sq.ft. | 1,500 - 2,400 Watts | 6 - 10 ft. | 2,500 W | 15 A 240V |
| 20 x 24 = 480 sq.ft. | 2,400 - 3,840 Watts | 10 - 16 ft. | 2,500 - 4,000 W | 20 A 240V - 30 A 240V |
| 20 x 30 = 600 sq.ft. | 3,000 - 4,800 Watts | 12 - 20 ft. | 3,000 - 5000 W | 30 A 240V |
| 20 x 30 = 600 sq.ft. | 5,000 - 7,600 Watts | 20 - 30 ft. | 5,000 - 7,600 W | 30 A 240V - 40 A 240V |
1. Watch out: These room sizes and heater sizes are approximate; important additional factors such as the temperature difference between indoors and outdoors, the building air leakage rate, and building insulation will of course affect the amount of heat needed to keep occupants comfortable in cold weather. 2. Watch out: when selecting the electrical circuit size you must consider the total wattage of all of the electric heaters that will be used on the circuit. Do not exceed the total wattage permitted for the wire and circuit breaker size. If you need more heat in an area than a single circuit can provide in watts, run additional circuits to the area to permit dividing the electric heater load among circuits. Separately at ELECTRIC BASEBOARD HEAT INSTALL we give details of electric heat circuit requirements such as wire and circuit breaker size based on electric heater size in total watts. |
||||
Electric Baseboard Heat vs. Electric Fan Heaters |
||
| Feature | Electric Baseboard Heat | Electric Fan Heat |
| Heat Use Type | Suitable for primary heat source Permanently installed |
Use steel element heater if primary heat source Also may be permanently installed Open coil elements suitable for supplemental or occasional use |
| Room Heat Speed | 30-40 minutes | Less than 10 minutes |
| Room Temperature Variation | Heat is concentrated at baseboards | Fan circulates room air, heats more evenly |
| Heater Efficiency | ||
| Heater Operating Cost1 | Slower room heating increases operating cost. | Circulating air may speeds room heating and reduces operating cost. |
| Heater Noise | Nearly silent; some thermal expansion noises | Varies by fan type2 & speed, very quiet to audible blower fan noise. |
| Heater Space Needed | Consumes wall space, don't block by anything | Smaller space occupied by heater; don't block by anything |
| Heater Life Expectancy | 20+ years3 | 8-12 Years3 |
1. Electric baseboard heat is the least expensive to install but is the most-expensive (per BTUh of heat output) for most areas in North America.
Electric heat is 100% efficient in that virtually all of the energy consumed is being delivered as heat.
Electrical circuit voltage (120 vs. 240 VAC) choice will not change the operating cost of the electric heater, but electrical circuit installation costs may be less with a 240 VAC circuit where multiple heaters are required, because more heaters can be installed on the circuit.
For example a 20A 120V electrical circuit can support a baseboard heater with maximum heat output of 1920 Watts while a 20A 240V circuit can support a total electric baseboard heat output of twice that amount, or 3840 Watts.
2. For the same CFM output, propeller type heater fans are noisier than squirrel cage type heater fans. Two small fan heaters in a room will produce less total noise than a large heater specified to heat the same area.
Above: our photo shows a propeller-type fan heater being installed in the exterior wall of a bathroom in a New York study.
3. Source: Suarez, Paul, "Which is right for your room, a baseboard or wall heater?" Cadet Heat, 2500 West 4th Plain Blvd. Vancouver, WA 98660 USA, Website: cadetheat.com, Email: customerservice@cadetheat.com Tel: 855-223-3878 / International: 1-360-693-2505, retrieved 2018/09/09, original source: http://cadetheat.com/blog/baseboard-or-wall-heater/
Adapted from King Electric, ELECTRIC HEAT WIRING CIRCUIT SIZING CHART [PDF] King Electrical Manufacturing Co., cited in detail below, retrieved 2018/09/10, original source: https://www.king-electric.com/pdfs/helpful-hints-sizing-chart.pdf
At ELECTRIC BASEBOARD HEAT INSTALL we give electric heat circuit requirements based on electric heater size in total watts.
Example of Cord-and-Plug Electric Fan Heater Sizes & Circuits
See details at ELECTRIC BASEBOARD HEAT INSTALL
Portions of this article are adapted from KING ELECTRIC CB-SERIES ELECTRIC BASEBOARD HEAT INSTALLATION [PDF] King Electrical Mfg. Co., 9131 10th Avenue South, Seattle, WA 98108 USA Tel: 206.762.0400 Website www.king-electric.com
NEC 210.21 (B) Receptacles.
(1) Single Receptacle on an Individual Branch Circuit.
A single receptacle installed on an individual branch circuit shall have an ampere rating of not less than that of the branch circuit.
Exception No. 1: A receptacle installed in accordance with 430.81(B)/
Exception No. 2: A receptacle installed exclusively for the use of a cord-and-plug-connected arc welder shall be permitted to have an ampere rating of not less than the minimum branch-circuit conductor ampacity determined by 630.11(A) for arc welders.
NEC 210.21 (B) Receptacles. (continued)
(2) Total Cord-and-Plug-Connected Load.
Where connected to a branch circuit supplying two or more receptacles or outlets, a receptacle shall not supply a total cord-and-plug-connected load in excess of the maximum specified in Table 210.21(B)(2).
That table specifies the following:
Circuit Rating (Amperes) 15 or 20, Receptacle Rating (Amperes) 15, Maximum Load (Amperes) 12
Circuit Rating (Amperes) 20, Receptacle Rating (Amperes) 20, Maximum Load (Amperes) 16
Circuit Rating (Amperes) 30, Receptacle Rating (Amperes) 30, Maximum Load (Amperes) 24
See ELECTRICAL CODES to download copies of various electrical codes and standards.
Also see ELECTRICAL RECEPTACLE HEIGHT & CLEARANCES for a discussion of avoiding fire hazards of electrical receptacles installed above electric baseboard heaters.
This discussion has been promoted! It has its own page now found at ELECTRIC HEATER LOCATIONS.
(Nov 14, 2012) Louis Bernardini said: I need a wiring diagram for a Singer model 7165B electric baseboard unit.
...
Continue reading at ELECTRIC BASEBOARD HEAT INSTALL or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see these
ELECTRIC BASEBOARD FEET NEEDED at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Questions & answers about proper electrical wiring for electric baseboard heat
Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.
Search the InspectApedia website
Note: appearance of your Comment below may be delayed: if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.
Only one image can be added per comment but you can post as many comments, and therefore images, as you like.
You will not receive a notification when a response to your question has been posted.
Please bookmark this page to make it easy for you to check back for our response.
IF above you see "Comment Form is loading comments..." then COMMENT BOX - countable.ca / bawkbox.com IS NOT WORKING.
In any case you are welcome to send an email directly to us at InspectApedia.com at editor@inspectApedia.com
We'll reply to you directly. Please help us help you by noting, in your email, the URL of the InspectApedia page where you wanted to comment.
In addition to any citations in the article above, a full list is available on request.