Photograph of an office wall convector air conditioner system Wisconsin Protocol for Cleaning Air Conditioners & Heat Pumps & Legionella Bacteria

  • POST a QUESTION or COMMENT about cleaning air conditioners, heat pumps, dehumidifiers, humidifiers & Legionella bacterial hazards

How to clean HVAC systems to avoid Legionnaire's disease hazards:

This article explains how to use the Wisconsin Protocol for cleaning air conditioners & heat pumps to avoid Legionella bacteria in air conditioners, how to clean air conditioning systems, Legionnaire's disease prevention & cleaning suggestions for air conditioning equipment and condensate trays, including condensate piping, traps, drains, condensate pumps, and concerns for mold, Legionella bacteria, and other hazards associated with air conditioning systems, cooling towers, and evaporative coolers.

This is a page in our article series escribing the inspection, maintenance, and repair of residential air conditioning systems (A/C systems) to inform home buyers, owners, and home inspectors of common cooling system defects.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?





ADVERTISEMENT





Comments and Advice on use of the Wisconsin Protocol for Cleaning A/C Equipment

The Wisconsin protocol for cleaning air conditioning condensate trays includes "This procedure calls for an initial shock treatment with 50 ppm free residual (total) chlorine, addition of detergent to disperse bio-fouling, maintenance of 10 ppm chlorine for 24 hours, and a repeat of the cycle until there is no visual evidence of biofilms.

To prevent exposure during cleaning and maintenance, wear proper personal protective equipment: a Tyvek-type suit with a hood, protective gloves, and a properly fitted respirator with a high-efficiency particulate (HEPA) filter or a filter effective at removing one-micron particles."

There is some suggestion that using chlorine products is more likely to damage the equipment by corrosion. For example simply pouring bleach will produce chlorine gas and will corrode nearby aluminum fins on an evaporator or condenser coil.

This is a well known problem and there must be a collection of standard products offered to the HVAC industry.

http://www.osha.gov/dts/osta/otm/otm_iii/otm_iii_7.html is OSHA's technical manual re Legionnaire's disease and has some (incomplete) details "disinfecting the cooling tower system according to the Wisconsin Division of Health protocol for "Control of Legionella in Cooling Towers" or a similar process for cleaning heat rejection systems that follows sound practices to minimize potential for Legionella growth."

A section in this document discusses the use of commercial biocides (looks questionable), traditional oxidizing agents (chlorine), or bromine (effective and less corrosive). In the case of Legionella, other measures like temperature control and cleaning frequency are cited as also important.

I would look for a disinfectant that would be broad spectrum but which also is assured not to damage the equipment, maybe a bromine product.

Some history behind the "Wisconsin protocol" for cleaning air conditioning condensate trays may be in order.

By coincidence my associate Craig Balchunas (Poughkeepsie, NY) returned from a one day class on Legionella where he spoke with one of the original contributors to the "Wisconsin Protocol".

He informs me that the protocol was an "off the cuff" exercise by a group of professionals in response to an urgent protocol request from the Wisconsin DOH, that the protocol has not been tested scientifically, and that there may be problems with corrosion damage to equipment when the protocol is followed.

Therefore we add that for any disinfection using corrosives (as I anticipated in my comment below) since there is risk of damage to the equipment, you'll need to wash the disinfectant off thoroughly at the end of the procedure.

We also discussed UV lights as a disinfection method - a method I view with skepticism for several reasons including questions about adequacy of exposure time in air systems and similarly, because some pathogens find intermediate hosts (such as Legionella bacteria hiding in an amoeba) which protect them as they pass through the UV system.

At the end of the day, regular inspection and cleaning and control of blow-by of unwanted condensate droplets are what make the most sense to me.

...





ADVERTISEMENT





...

Continue reading at Legionella BACTERIA & HVAC EQUIPMENT or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.

Or see these

Recommended Articles

Suggested citation for this web page

WISCONSIN PROTOCOL for CLEANING HVAC at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

Or see this

INDEX to RELATED ARTICLES: ARTICLE INDEX to AIR CONDITIONING & HEAT PUMPS

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Ask a Question or Search InspectApedia

Share this article:

Search the InspectApedia website

Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.

Citations & Reviewers

In addition to any citations in the article above, a full list is available on request.

  • Thanks to Mark Cramer, Tampa Florida, for assistance in technical review of the "Critical Defects" section and for the photograph of the deteriorating gray Owens Corning flex duct in a hot attic. Mr. Cramer is a Florida home inspector and home inspection educator.
  • http://www.osha.gov/dts/osta/otm/otm_iii/otm_iii_7.html is OSHA"s technical manual re Legionnaire's disease
  • US EPA Safe Drinking Water Hotline: 800-426-4791
  • "Legionella in NY - How to Conduct a Legionella Risk Assessment", Mark Hodgson, LSC, Naperville IL & Diane Miskowski, MPH, EMSL Analytical, Inc., Westmont NY, Crown Plaza, White Plains, 8 May 2007.

    Course description: "Guidelines for the control of Legionella in critical care hospitals in New York have been in place for two years. In October 2006, these guidelines were extended to include nursing homes and long term care facilities. Join us for this 8 hour seminar to learn all you need to know to conduct a Legionella health risk assessment, control it in your facility, and remediate it.

    This course will describe the ecology of the [Legionella] organism, the epidemiology of the disease [Legionnaire's disease], a discussion of some recent outbreaks, and the proper sampling methods and analysis of the bacteria.

    A significant amount of time will be spent discussing how to actually perform a Legionella risk assessment, and an overview of cooling towers and potable water system design and how that contributes to growth of the [Legionella] organism.

    Discussion will include where Legionella can be found in the engineered environment, and the use of biocides and other controls." -- Thanks to Craig Balchunas, AHI Accurate, LLC., a home inspection firm in Hyde Park, NY. - (800) 360-3998
  • "Legionella", a public information poster provided free by LA Testing, an California environmental testing lab - www.LATesting.com.
  • In addition to citations & references found in this article, see the research citations given at the end of the related articles found at our suggested

    CONTINUE READING or RECOMMENDED ARTICLES.