Supply Air Heating & Cooling Register & Duct System HVAC supply air ducts, registers, & controls:
This article describes the inspection of heating and air conditioning (HVAC) duct air supply and return registers & duct zones for defects such as missing air conditioning cool air supply or return air registers, undersized air conditioning duct openings, improper cooling duct routing, cooling (or heating) air duct corrosion, leaky air duct connections, defective heating or cooling ductwork materials. We include a discussion of how to increase the supply of cool air or air conditioner output in a building.
The photograph at the top of this page shows my hanb in front of a 1930's heating and cooling air supply register still in active use, but with leakage around the register which transmitted odors and mold from the building basement.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?
Article Contents...
The ceiling air supply register shown in the photo at left is typical of modern residential installations except for those leak stains around the register.
Leaks around a ceiling air supply register may point to a hidden mold contamination problem, uninsulated duct work, ductwork leaks or other problems.
Further investigation was needed to discover whether the stains were due to a roof leak above this point or an air conditioning leak into and around the supply duct or as we've seen in some northern climates, accumulation of condensation and even ice in ceiling air conditioning ducts caused by movement of moist air backwards through the duct system by natural convection when the HVAC system was turned off.
The ceiling register in the second photo (above) has blown soot and debris onto the ceiling itself.
Further investigation was needed to determine if this soiling was from failure to maintain filters in the duct system, mold or debris in the duct system, a failed (and dangerous) oil-fired or gas-fired furnace heat exchanger, or other causes.
The minimum air conditioning system inspection standard (or heating inspection standard) includes the observation of the presence of a cooling source in each habitable room in the building.
Ductwork to each room (at least connected to visible supply registers) & supply registers themselves should be observed in every room, delivering conditioned air to each habitable room (we can exclude closets and utility rooms and in some locales, baths).
Beware of "dummy" supply registers that are not connected to anything.
Beware of supply registers that are connected to ductwork but have no air flow due to duct routing errors, pinched, or disconnected duct work, or similar faults. This defect can only be observed if conditions permit operating the system.
...
In a home inspection report, cooling system duct work defects may be reported under "Heating System" for cases where same ductwork is used for both heating and cooling. However, optimal supply and return placement for cooling is different from the optimum placement for cooling supply and return air.
A heating system may deliver warm air low on walls or at floor level (warm air rises).
A cooling system may prefer to deliver cool air from a supply diffuser high on the wall or in ceilings (cool air falls) and draw cool air to the system return duct from a separate high-location in a ceiling (warm air rises to the high return duct for air conditioning). This topic is discussed in more detail at LOCATION OF DUCTS below.
Zone control for air handling systems can be provided by:
See ZONE DAMPER CONTROLS for details about how to achieve individual zone control for warm air heating for for air conditioning systems.
...
The air flow rate supplied by an HVAC duct and air handler system is a function of several variables that can explain why you may not measure an air flow in cubic feet per minute or CFM that matches neither your expectations nor the equipment's CFM rating. These include at least the problems (and solutions) that we list below:
Technical note: The D'Arcy-Weisbach equation for pressure and head loss can be used to calculate the actual pressure loss due to friction in a building piping or air duct system.
The Engineering Toolbox provides the D'Arcy-Weisbach formula:
Δp = λ (l / dh) (ρ v2 / 2)
where Δp = pressure loss (Pa, N/m2), and
l = length of duct or pipe (m) and
dh = hydraulic diameter (m) and finally,
ρ = density (kg/m3).
Watch out: But keep in mind that even this apparently accurate calculation of the effect of piping on air pressure and airflow loss will not include the effects of leaks or obstructions in the building return air or supply air duct system such as those listed below.
...
Older Florida home with air handler under house in crawl space. Air is ducted to floor registers. Not very efficient as cold air doesn't rise much. House has a flat roof no attic space to get up into. Any thoughts on how to improve? - D. (Anon).
A competent onsite inspection by an expert usually finds additional clues that help accurately diagnose a problem. That said, here are some things to consider in improving cool air flow in your home:
We agree completely that cool air works better delivered from ceilings than from floors
since cool air tends naturally to fall through the occupied space. It takes more energy to blow cool air "up" than to drop it into a room from supply registers mounted high on walls or in the ceilings. We discuss this further
at LOCATION OF REGISTERS & DUCTS
But the cost of changing ductwork is rather high and the work disruptive so that's not your first choice.
Please see COOL AIR SUPPLY IMPROVEMENT
Please see WARM AIR SUPPLY IMPROVEMENTS
...
The following tables are adapted from "How to Evaluate Furnace Duct Work & Cure Short Cycling or Inadequate Ductwork Problems" published by the Vermont Department for Children and Families [1]; similar tables are widespread through HVAC literature and resources cited atReferences or Citations
| Gas Furnace Heating Duct Requirements | |
|---|---|
| Furnace Input BTUs | Square Inch Duct Size Needed for both supply & Return Duct |
| 40,000 | |
| 60,000 | |
| 80,000 | |
| 100,000 | |
| 120,000 | |
| Oil-fired Warm Air Furnace Duct Sizing Requirements | ||
|---|---|---|
| Output BTU’s | Square Inch Duct Size Needed for both supply & Return Duct |
Min. CFM Airflow |
| 45,000 to 55,000 | ||
| 60,000 to 70,000 | ||
| 75,000 to 85,000 | ||
| 95,000 to 106,000 | ||
| 106,000 to 115,000 | ||
| 125,000 to 150,000 | ||
| Relationship of Round Duct to Square Inches to CFM Air Flow to Heating BTU’s |
|||
|---|---|---|---|
| Duct Diameter | Duct Square Inches | CFM Airflow Supported | Heating BTUs Capacity |
| 6-inch | |||
| 7 | |||
| 8 | |||
| 9 | |||
| 10 | |||
| 12 | |||
...
We had a new 100,000btu furnace installed. Our heating system is controlled by our original Carrier Comfort zone thermostat and control board (5zones) with electric 3 wire dampers.
After installation of new furnace heat is pushing through closed dampers - tabs indicate in closed position but air is being forced through. Some whistle. Basement set at 65, but is 69 degrees.
Can the new furnace be too powerful for the 22 year old dampers? Does the furnace have settings to adjust? Never had this issue prior to new furnace install, zone temps always maintained, never more than 1 degree warmer than setting.
Afraid service company will try to tell me i need to spend 1,000s in new equipment when in fact they did not match my existing components with furnace. Thank you for the help! On 2022-11-13 by Susana
by InspectApedia (Editor) - Carrier Comfort zone thermostat and control board - adjust blower fan speed
@Susana,
Heating and air conditioning Air Supply registers are never absolutely airtight. It's normal for there to be some air leakage through them when the fan and the air handler is running.
However if you think that the airflow is stronger than you like and noticeably stronger than it was with the previous air handler there are two explanations that should be understood:
First, it's possible that the squirrel cage fan in the blower of your old air handler was dirty.
Dirt on those fan blades can cut the air flow output by 60 or more percent. So a new blower with a clean fan will definitely move much more air.
Second, many air handlers have a fan speed setting that can be adjusted. It may be on a control board.
Often the air handler uses a different speed when cooling then when heating.
So you want to review those settings with your installer to be sure they are correct.More detailed diagnostics start
Also see SUPPLY DUCTS & REGISTERS
by Susana
@InspectApedia, Thank you for the suggestions. Is there any reason to believe the damper vane's failing - can it show closed but be letting a lot of air through? We could swap the damper inserts to see if the added heat shows up in corresponding zone.
by InspectApedia (Editor) - duct damper failure causes abnormal air flow at some air supply registers?
@Susana,
Thanks that's an interesting question - duct damper failure causes abnormal air flow at some air supply registers?
Duct damper vanes never close off a duct completely since making them that air-tight would either jam the moving baffle in the duct or would make the product more expensive than the manufacturers think they can sell.
Let's try a simple test: for an HVAC system air supply register that is downstream from the duct damper, try the duct damper in it's OPEN position and then in its CLOSED position with, of course, the air handler blower running. You should feel a significant drop in airflow when the damper closes.
See details at ZONE DAMPER CONTROLS https://inspectapedia.com/heat/Ductwork_Zone_Dampers.php
And let us know what you find.by Susana
@InspectApedia (Editor), thank you - service co adjusted the dip switches to lower air flow settings. Dampers are working properly per tech, and they suggested adjusting lower level zone damper's closed position to let some pressure off of system if the adjustment didn't do enough.
Our 23 year old furnace was propabably bogged down, too. Thank you again for the help and web link!
by InspectApedia (Editor) - AIr handler blower speed too high - air flow "too strong" at supply registers?
@Susana,
Thanks back to you for following-up with what worked. That will help other readers:
AIr handler blower speed too high - air flow "too strong" at supply registers?
Check fan speed settings on dip switches or jumpers on the air handler control board
Check/adjust position of duct dampers to be sure you've got the right balance of air flow among different duct zones.
...
Continue reading at SUPPLY DUCT AIR LEAKS or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see these
SUPPLY DUCTS & REGISTERS at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.
Search the InspectApedia website
Note: appearance of your Comment below may be delayed: if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.
Only one image can be added per comment but you can post as many comments, and therefore images, as you like.
You will not receive a notification when a response to your question has been posted.
Please bookmark this page to make it easy for you to check back for our response.
IF above you see "Comment Form is loading comments..." then COMMENT BOX - countable.ca / bawkbox.com IS NOT WORKING.
In any case you are welcome to send an email directly to us at InspectApedia.com at editor@inspectApedia.com
We'll reply to you directly. Please help us help you by noting, in your email, the URL of the InspectApedia page where you wanted to comment.
In addition to any citations in the article above, a full list is available on request.