Celotex & Dow polyisocyanurate foam board insulation:
Here we describe the history & asbestos content of certain Celotex® & Dow polyisocyanurate foam board insulation products and we clarify the asbestos content in contemporary polyisocyanurate foam board insulation.
This article gives the history and properties of Celotex® Thermax and other foam board insulating products. Celotex® foam board insulation was later purchased by Dow Chemical who continues to market polyisocyanurate foam insulating board. Page top photo: Celotex® Tuff-R polyisocyanurate foam board insulation.
This article series assists building buyers, owners or inspectors who need to identify foam board insulation and to address possible presence of asbestos in buildings.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
Polyisocyanurate insulation products have an R-value of about R 7.04 to R 7.20 per inch. Shown in the photo, Celotex Thermax solid foam insulating board with aluminum foil facing.
With a stabilized 3/4" air space on one side of this insulating board its R-value at 1" increases to R10.
1/2" Celotex Thermax was rated at R 3.8, increasing to R 6.4 with the air space we specified above.
4" Celotex Thermax was rated at R 28.8, increasing to R 31.6 with the air space we specified above.
According to product markings we show below, modern Celotex or more recently Dow polyisocyanurate insulation complies with requirements of ICBO, BOCA, SBCCI, CABO, ICC, HUD/FHA, Federal Specification HH-I-1972/1, Class 2, ASTM C 1289, Type 1, Class 2. The product is described in ICBO Report #3223, SBCCI #9574A, and BOCA #89-45.
In Canada see CCMC Evaluation Report #08433-L. The product shown below also is stamped with logos of NAHB, ETL, Good Housekeeping, and Energy Star.
Readers may also want to review IAQ and health questions discussed at POLYISOCYANURATE FOAM and IAQ.
Watch out: for safety also see FIRE PROTECTION FOR FOAM BOARD INSULATION
Hi, can you tell me if this ceiling foam contains asbestos? I think it is from 1981. Thank you!
Photo: Celotex® Thermax foam core insulating board, courtesy of reader Jaclyn.
2017/05/05 Jason Wojnowiak said:
I have a picture of some Celotex. [Shown above - Ed. ] [Click to enlarge any image]
Would you know if this has asbestos?
This question was posted originally at CELOTEX ASBESTOS PRODUCTS
Jason and Jaclyn,
Celotex Thermax™ as illustrated by your first photo above was (and is currently as a Dow Thermax™ product) a foil-faced insulating board comprised chiefly of foam insulation, laminated with aluminum foil or possibly kraft paper.
Asbestos appeared in some, probably not all, foam insulating boards made up to the early to mid 1980's, particularly or more likely in fire-resistant products that incorporated a layer of asbestos paper.
In the photos just above and below, provided by Jason [above], the Celotex Thermax board has been cut-open.
Enlarging the photo (enlarged view above) I don't see any sign of an asbestos paper, though of course a closer look in the field would be in order.
[Click to enlarge any image]
Above and then below we show your images of the labeling and text on this Celotex Thermax insulating board. Readers will want to click to enlarge each image to read the details of the Celotex insulation specifications.
This insulation meets several standards and specifications including Energy Star ratings - a rating that well post-dates asbestos-based insulation for in-home use. The company's stamping describes this product as a "Glass fiber reinforced polyisocyanurate foam board with reflective aluminum foil facers."
Is it possible this product contains asbestos? It’s an insulation board in my pull behind camper.
Exact year unknown but between 1975 & 1985. Manufactured by the Dow Chemical Co. some other legible words include: STURDY-R, Dow, nominal board
[Click to enlarge any image]
This Q&A were posted originally at ASBESTOS LIST of PRODUCTS
From the text, that's a polyisocyanurate foam product. You can see details about that product
at POLYISOCYANURATE FOAM BOARD
Some of those products included asbestos.
If you can attach a photo of the rest of the text on your board and of any patent numbers that would be most helpful.
Also, what are the brand and model of your camper and where is it located (Country, city)?
Photo: Celotex Sturdy-R installed in a U.S. home in Gloucester County Virginia between 1996 and 1998, courtesy of reader Sirrena.
Foil faced and structural laminate type insulating boards using foam and aluminum or other facings have patents that help identify the product contents.
Watch out: you are absolutely right to ask if asbestos ever was used in insulating foam boards. Indeed the patent I cite above as well as at least one other patent describe possible use of asbestos in these insulating board products.
Excerpt from Hipchen: The structural laminate of the present invention has at least one but preferably has two facing sheets, one on either side of the foam core. These facing sheets can be constructed of a wide variety of non-flammable materials such as asbestos, glass fibers, or metals.
In the broadest aspects of the invention, any metal can be employed such as copper, brass, iron, steel, or aluminum. Aluminum is the preferred metal because of its ductility and ease with which it can be manufactured into a material of suitable thickness.
Celotex is the original assignee of this patent. That does NOT tell us what Celotex products actually contain when marketed.
Here is a later patent citing asbestos in foam insulating boards:
Notice that where fireproof or fire resistant products were being marketed asbestos was more likely to appear.
Excerpt from Ohashi:
This invention relates to novel fireproof laminates using a urethane modified polyisocyanurate foam as a core material.
More particularly, it relates to fireproof laminates having excellent fireproof property and low-smoke development, which are obtained by using the above core material having a defined density and an asbestos paper lined with a metal foil as a surface material for at least one side of the core material and piling them one upon another at a total thickness of a defined range through self-adhesion of the urethane modified polyisocyanurate foam.
In the U.S. in the 1980's Celotex Thermax insulating board was described by the Celotex Company (Jim Walters corporation, Tampa) as an insulating sheathing board with an R-value of 5.4 for a 3/4" thick board: higher R than its competitors at the time as it was compared with foam insulating board sold by Dow, WR Grade and Simplex. (Popular Mechanics, October 1984, advertisement p. 139)
In July 2001 Celotex's rigid foam insulation business was purchased by Dow Chemical which explains why most web searches for Celotex Thermax insulating board will turn up Dow Chemical company listings for Thermax products.
I have not found reports of use of asbestos in foam currently-marketed (2016) insulating foam board products. But laminated foam insulating board products sold in North America up to about the mid 1980's might indeed contain asbestos, particularly in special fire-resistant applications.
At FOAM BOARD INSULATION TYPES you can see more photos of Celotex-branded foam insulating board, principally a polyisocyanurate foam product.
[Click to enlarge any image]
We are replacing our siding on a home, built in 1990. It is Celotex Tuff-R. We are concerned with the possibility of Asbestos, but are coming up blank with searching online. Here are pictures of the information we did see on it
. Any information would be really appreciated. - Anonymous by private email 2018/03/22
A home built in the U.S. (where is yours?) in 1990 would not be expected to have used asbestos-containing materials.
Celotex Tuff-R sold in the 1990's is a polyisocyanurate foam insulation product. That's not asbestos.
Review also this EPA ASBESTOS MATERIALS BAN: CLARIFICATION 1999 [PDF]
Foil-faced or water-resistant-faced polyiso foam sheathing board approved for use without a weather resistive barrier (WRB) or housewrap will generally be named as having that advantage by its manufacturer - after all it's a selling point. The insulating sheathing board seams, particularly horizontal seams, must be properly taped - sealed to avoid leakage.
But some other polyiso sheathing and insulating board products are NOT listed as approved for use without a WRB.
The home was built between 1996 and 1998 in Gloucester County, Virginia.
2018/07/23 Sirrena said:
Found this under my siding, is this suppose to be directly under siding an no wrapping?
[Click to enlarge any image]
Thank you for asking about the need for a housewrap over Celotex Sturdy-R insulating sheathing.
Bottom line: We could find NO company statement from Celotex nor an independent statement that a housewrap or weather barrier can be omitted under Celotex Sturdy-R.
Therefore unless you can find such a statement from Celotex about their Sturdy-R sheathing permitting its use without a housewrap it would make sense to install a housewrap over the walls before installing siding.
From what I can read on the imprint on your U.S.-sold Celotex Sturdy-R
1. The insulation can not be left exposed - (that would be a fire and smoke hazard) - used indoors it would be covered by drywall. Outdoors by siding - leaving some fire rating questions a bit unclear.
2. The certifications, such as ICBO Chapter 17 STRUCTURAL TESTS and SPECIAL INSPECTIONS - Section 1713 [PDF] marked on this PIB have to do with approving use of the board as structural sheathing (not requiring cross-bracing, for example) and say nothing about the omission of a housewrap weather resistive barrier.
3. The facing looks like a synthetic fabric, but we don't have more of its properties.
4. However I am not arguing that existing siding on the home must be stripped just to add a WRB.
IF all siding was removed for another reason (like re-siding) you should install housewrap.
IF there is evidence of leaks into the building walls those areas deserve further exploration for hidden damage and we'd decide based on diagnosis of the leak if what was needed was a spot-repair or something more extensive.
Product labeling details about this Celotex Sturdy-R U.S. product are provided in photographs from Sirrena.
Some brands and types of foam-based insulating wall sheathing are code-approved for use without a weather resistive barrier (WRB), typically closed-cell waterproof styrofoam but also some polyisocyanurate foam sheathings as well as other types of foam-based wall sheathing boards.
But other foam based insulating sheathing products are not approved for use without a WRB or housewrap. When companies are not explicit on the requirement for a WRB you may find an answer implied in the fine print in product publications - as I’ll show below.
Otherwise we’re left guessing and having to assume that if a company is silent on the WRB requirement there’s a reason for that that might leave us at, at best, nervous.
Even where an insulating sheathing is rated for use without housewrap, the sheathing seams should be sealed or taped the same way they were to pass (in the U.S.) the AC71 tests. Otherwise your wall may leak, inviting rot and insect damage.
Dow’s polyisocyanurate sheathing (Thermax and Tuff-R) as well as their extruded polystyrene products such as Styrofoam can be used as wall sheathing without requiring a housewrap or WRB.
Celotex, a U.K. company under Saint-Gobain, website www.celotex.co.uk/- has this to say about Celotex Sturdy-R insulating sheathing:
“…”
That’s right. Nothing.
At least a search of the company’s website and a Google search for Celotex Sturdy-R produces not a shred of information. In 2017 Celotex suspended the supply of some other Celotex “PIR” insulation board products due to compliance issues and pending further testing. I can’t say if Celotex Sturdy-R met a similar fate but I can tell you that the suspended products were all polyisocyanurate or PIR foam products. The company is (in July 2018) silent on the Tuff-R product in your photo.
It seems likely that Celotex Sturdy-R, an inorganic-covered polyisocyanurate foam insulating sheathing board, is not supported and not marketed currently.
So if your building is sheathed in this material it would make sense and seem safer to me to install a water-shedding housewrap on the walls before adding siding.
Modern foam insulating board products like the Dow Chemical SuperTuf and Thermax may use fiberglass or other reinforcing fibers however. Shown above: Dow Super Tuff R foil faced insulating foam board at a Home Depot store in Poughkeepsie, NY. This product is rated by the Dow Chemical company as R 3.3 in 1/2" board and R 6.5 in 1" thickness board.
Shown in our second photo above in which some shopper (not me) peeled back part of the foam board facing, you may see that some insulating board products use aluminum foil only on one side, facing the other side with paper or plastic.
The Dow Chemical company notes that the installer can obtain an additional R 2.8 if the insulation is installed with an air space on the reflective side - the side without printing.
Contemporary Thermax branded insulating board or sheathing board, a Dow Chemicals product, is described by DOW as follows:
THERMAX™ Heavy Duty Insulation consists of a glass-fiber-reinforced polyisocyanurate foam core faced with nominal 4 mil embossed white thermoset-coated aluminum on one side and 1.25 mil embossed aluminum on the other. It can be installed exposed to the interior without a thermal barrier.
Dow Chemical currently markets several versions of Thermax™ to meet different needs such as building insulating sheathing, heavier duty insulating sheathing or insulating board for metal buildings, etc.
Here is a copy of one of the current Thermax™ Sheathing products now produced and sold by the Dow Chemical Company and an example Dow Chemical MSDS for a typical Thermax insulating sheathing product.
Below you will find questions and answers previously posted on this page at its page bottom reader comment box.
On 2020-05-26 - by (mod) - how to dispose of waste foam-core Polyurethane & EPS insulating board waste
Kevin,
Regulations for disposal of waste insulation products including foam board will vary depending on where you live (country, city, province, state etc). But in general, a very small amount, a few scraps can usually be bagged as household waste while a larger amount such as from a demolition are disposed-of as construction debris.
Some foam products are recyclable according to many sources I reviewed for this response, but those offering that comment may not have run into the practical difficulty of actually recycling foam insulation. For example in some Minnesota communities the recycling contractors will accept only a very limited number of types of foam, often only #1 and #2.
Polyurethane is recycled in two primary ways: mechanical recycling, in which the material is reused in its polymer form, and chemical recycling that takes the material back to its various chemical constituents. - American Chemistry
Regulations for disposal of foam insulation board may also vary by the type or kind of foam. Some states have banned all use of some common foam products such as EPS, Expanded Polystyrene. Examples of foam waste disposal or recycling regulations and methods are below,
On 2020-05-26 by Kevin
I have a bunch of this from a jacuzzi dismantle. How do I get rid of it?
On 2020-02-15 by Bucky
thanks for your help
On 2020-02-15 - by (mod) -
Stapling to the stud face, overlapping adjacent facings is standard and is what I usually do. Stapling to the inside edge is much more work, risks tearing the kraft with the stapler, but adds an air space and might slightly improve overall R-value.
We do not normally staple the bat at the top and bottom of the stud Bay. Stapling at the sides is the proper way to support the insulation batt and it will certainly prevent any sagging if you staple up and down both sides. I've never found sagging fiberglass Staples in place be a problem.
On 2020-02-15 by bucky
Thanks for the quick reply. Yes I will be installing drywall over the DOW TUFF- R. So just to confirm you suggest leaving the Kraft Facing in place?
As far as stapling goes, is it better to staple the tabs on the face of the studs creating a somewhat tighter barrier or as I think your suggesting to staple the tabs on the inside edge?
Or might it be better to only staple the tabs on the inside edge only at the very top of the wall to prevent the batt from potentially sagging over time but leave the rest unstapled /unfolded to prevent air space. Or is that slight air space created on the edges by stapling the tabs inside a potential benefit by increasing R-value against the foam board? ??
On 2020-02-14 - by (mod) - avoid trapping moisture in walls
I appreciate the concern for trapping moisture in walls where we inadvertently install multiple moisture barriers.
At inspectapedia.com/interiors/Perm-Ratings-for-Materials.php PERM RATINGS of BUILDING MATERIALS we give perm ratings of various building materials.
There you'll see that Insulation, Kraft-Faced has a perm of about 1.0 and foil faced Kraft of about 0.5
1-inch polyisocyanurate foam board has about the same permeability or about 1.0 while thicker foam boards will have less permeability. (2-inch polyisocyanurate foam board has a perm of about 0.5)
If your polyisocyanurate foam board is a product like Dow Tuff-R, that has a permeability of much less, about 0.03. That's because it's a foil-faced foam board.
I would leave the lower-perm kraft faced insulation - (not to mention that as edges are only stapled the permeability of the whole wall surface is far greater than just that of the kraft paper)
Taping the Tuff-R boards is always a nice additional measure to keep moist warm air from pushing moisture into the wall cavity.
For fire safety you're not going to leave foam board exposed anyway; you're going to install drywall over it, right?
But the critical step in avoiding sending moisture into any wall is to
- minimize the penetratrations into the wall
- to seal any penetrations you cannot avoid
since most of the source of moisture that gets into wall cavities is not by penetrating the field of the wall materials but rather air leaks at penetrations.
On 2020-02-14 by bucky
I have a walk out basement 2x4 wall at my home in central N.E. ,so a heating climate, that I want to reinsulate and finish with sheet rock.
The current insulation is old /damaged kraft faced R-11. I was planning on using R-15 fiberglass batts to reinsulate. On the exterior is 1/2 plywood sheathing and cedar clapboards which is in good shape and not in need of replacement.
I was considering adding polyisocyanurate foam board, probably 1/2" , to add additional R value and to reduce thermal bridging through the studs. A few questions. The R-15 fiberglass that I have has a kraft facing on it.
Is it ok to install the DOW SUPER TUFF-R over the kraft facing or does the TUFF-R provide an adequate vapor retarder itself? I would prefer not to remove the kraft facing but don't want to cause a double vapor barrier.
The foam board would be in direct contact with the kraft paper [any less of double vapor barrier issue?] Finally do the seams /penetrations in the foam board need to be taped or sealed ? Suggestions? Thanks
On 2018-07-24 - by (mod) -
Sirrena
I'd add that the holes cut into the sheathing, if it was immediately behind siding without a housewrap, invite leaks into the wall.
'
Also I note what looks like felt or building paper around the window in the bottom (or left if the photo is upright) of your image shows that detailing around the windows is incomplete - adding risks of leaks into the wall in such locations. Where such spots are revealed by siding removal it's worth a close inspection for water entry, leaks, rot, insect attack - that might need further steps - before adding housewrap and restoring siding.
On 2018-07-24 by Sirrena
I also want to clarify that the two square holes were pre-exsisting when we removed the siding. I also want to thank you for your help, it was greatly appreciated.
IMAGE LOST by older version of Clark Van Oyen’s useful Comments code - now fixed. Please re-post the image if you can. Sorry. Mod.
On 2018-07-23 - by (mod) -
From what I can read on the imprint on your U.S.-sold Celotex Sturdy-R
1. The insulation can not be left exposed - (that would be a fire and smoke hazard) - used indoors it's covered by drywall, outdoors by exterior siding.
2. The certifications, such as ICBO Section 1713 have to do with approving use of the board as structural sheathing (not requiring cross-bracing, for example) and say nothing about the omission of a housewrap weather resistive barrier.
3. The facing looks like a synthetic fabric, but we don't have more of its properties.
4. However I am not arguing that existing siding on the home must be stripped just to add a WRB.
IF all siding was removed for another reason (like re-siding) you should install housewrap.
IF there is evidence of leaks into the building walls those areas deserve further exploration for hidden damage and we'd decide based on diagnosis of the leak if what was needed was a spot-repair or something more extensive.
The detailed photos are helpful, I have added them to the article to invite further comment from other readers.
On 2018-07-23 by Anonymous
the home was built between 1996 and 1998 in Gloucester County, Virginia.
IMAGE LOST by older version of Clark Van Oyen’s useful Comments code - now fixed. Please re-post the image if you can. Sorry. Mod.
On 2018-07-23 - by (mod) -
Sirrena
To have space to provide a detailed answer including research I have repeated your question and our reply in the article above.
Please take a look, and send along additional photos and information I ask for there - if you can.
Editor
On 2018-07-23 by Sirrena
Found this under my siding, is this suppose to be directly under siding an no wrapping?
IMAGE LOST by older version of Clark Van Oyen’s useful Comments code - now fixed. Please re-post the image if you can. Sorry. Mod.
We bought a house that was built in the 50's - it has what I THINK is a Celotex ceiling (or some copy of Celotex) - it's in horrible shape and needs to be taken down - what are your thoughts on it containing asbestos, considering the age? - Saundra
Saundra,
Keep in mind that Celotex and other insulating board panel and ceiling tile and panel manufacturers produced a range of products, many of which may contain asbestos, but others made of organic fibers, wood fibers, cane fibers may not contain asbestos.
The Celotex ceiling products division was sold to Certainteed Saint-Gobain beginning in 1999. Certainteed continues to produce and sell both fiberglass and mineral-fiber ceiling products, as well as gypsum based ceiling materials. You may find look-alike products by searching that company's product catalogs.
Modern ceiling products do not contain asbestos.
Using Certainteed as an example, [www.certainteed.com] you can obtain an MSDS (Material Data Safety Sheet) for each of the company's products. Common modern ceiling product ingredients include fibrous glass wool, urea formaldehyde resin, and fiberboard products contain slag wool, starch, cellulose [wood fibers], perlite, crystalline silica, and clay. It's worth noting that even modern building products can present health hazards if they are not handled properly.
For example crystalline silica can cause nose, throat, and lung irritation. [6]
If you are not sure of the product brand and age of the ceiling covering, and are not sure whether or not the product contains asbestos, and if we accept as a "given" that your ceiling covering needs to be removed, there are two reasonable ways to proceed:
or
To elaborate your question about asbestos-containing products made by Celotex, the company produced a wide range of fiber-based insulation products such as insulating boards and panels and the company continues to produce modern (non-asbestos-containing) versions of those products today.
At FIBERBOARD SHEATHING, Celotex Homasote & Other we include identifying photographs of some Celotex products.
Is it safe to clean the ceiling of our Church which has celotex boards and believed to have been installed in 1935? - Len Taylor 10/25/12
"Safe" depends - the greatest hazard of cleaning a church ceiling is falling off of a ladder. I don't know what kind of cleaning you are talking about, nor what the concern was; But if you avoid aggressive cleaning that damages the material and creates fibers and dust, you should be ok. Celotex fiberboard insulating panels are not an asbestos product - as you can read at SHEATHING, FIBERBOARD
(May 24, 2015) Anonymous said:
What kind of asbestos was used in paper duct wrap in 1908? Was it chrysotile or another form?
Please see ASBESTOS PAPER DUCT INSULATION and also see ASBESTOS DUCTS, HVAC - where we cite research on these materials as well as advice on action plans when they're present in a building.
(Aug 5, 2015) Melanie said:
I need to find out if our ceiling tile contains asbestos. They were manufactured in Marrero, LA in 1971. Numbers found on the box are: 32286 and 270. Can you help? Thank you.
Check with Louisiana Acoustical & Drywall Materials is a subsidiary of GMS, 2601 Samford Ave Shreveport, LA 71103 318-459-2944 louisianamaterials.com
See details at ASBESTOS CEILING TILES
Or see DO THESE CEILING TILES CONTAIN ASBESTOS?
(Nov 9, 2015) homeowner said:
I need to know if Celotex mineral wool contains asbestos.
This is loose fiber insulation in walls and attic found in home that was renovated with this product in 1959. There is a package that says "Celotex Mineral Wool,fire retardant" in the home.
Mineral wool is not an asbestos product. Only if yours was cross-contaminated might we expect to find asbestos in it.
See inspectapedia.com/insulation/Rock_Wool_Insulation.php for details.
(Jan 30, 2016) jane said:
We are rehabbing a house that has Celotex tile board as the ceiling in the upstairs. I'm guessing it was put up in the early 1940's. I have a box with a label and wondered if you could tell me if they contain asbestos. Type No.91 Joint Es Size 1/2x16"x16" sq. Ft.88.89 No.Pieces 50
Jane, please use the page bottom CONTACT link to send some pictures of the box labeling on all sides and the tile bith sides and we can comment further as well as researching further.
See DO THESE CEILING TILES CONTAIN ASBESTOS?
(May 28, 2016) tclark said:
I'm looking at purchasing a home built in 1929. All of the walls and ceilings are finished with panels that our realtor is calling Celotex panels.
She states that they are a by product of sugar cane which would not be surprising as the town in which it is located produces sugar cane. I see on this site that this product does not contain asbestos.
How can I be sure that this is actually the product that was used vs one of the others that do contain asbestos? Also, how is this material repaired when needed? I can post photos if it will help
TClark
Your realtor may or may not be correct as cellulose-based (wood-based) insulating board panels were made from a variety of products, not just sugar cane.
But as you may read in the article above, she is right that some Celotex was made of that material. Or perhaps she was sugar coating the sale for you. Did you ask the realtor how she knew for sure what the material was, who made it and what were its constituents and how she knew that it was made at a plant that was not at risk of asbestos cross-contamination.
To know for certain if a product contains no asbestos, with no more data than your question, you'd have to have a sample tested by a certified asbestos test lab (about $50.) though it may not be justified in this case.
You can use our page top or page bottom CONTACT link to send me photos. The Comment Box software does not yet let readers post photos, though many of us have asked for that feature.
...
Continue reading at POLYISOCYANURATE FOAM and IAQ possible health hazards?, or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see these
POLYISOCYANURATE FOAM BOARD at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.
Search the InspectApedia website
Note: appearance of your Comment below may be delayed: if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.
Only one image can be added per comment but you can post as many comments, and therefore images, as you like.
You will not receive a notification when a response to your question has been posted.
Please bookmark this page to make it easy for you to check back for our response.
Our Comment Box is provided by Countable Web Productions countable.ca
In addition to any citations in the article above, a full list is available on request.