InspectAPedia®   -   Search InspectApedia

furnace fan limit switch Honeywell L4064B Fan Limit Switch Setting FAQs
Q&A on Limit Control Adjustment, Settings, Repair

  • POST a QUESTION or COMMENT about the settings on the furnace blower fan limit switch and about the manual "fan on" or blower fan override switch.

Q&A about air handler or furnace blower fan limit switch temperature settings.

This article series describes in detail the setting of furnace combination controls, also commonly called the "fan limit switch" on warm air heating systems.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

FAQs on Settings for a Furnace Fan & Limit Control Switch

Honeywell L4046 Fan Limit Control Switch (C) InspectApedia.comThese questions and answers about making the proper settings on a fan limit controller or troubleshooting that control were posted originally at FAN LIMIT CONTROL SETTINGS - be sure to read that article too.

On 2018-11-10 17:01:41.794710 by (mod) -

Herb the fan limit switch probably will look a lot like the unit shown in the article above and will use the FAN ON and FAN OFF and FAN LIMIT numbers given there.

If you can attach a sharp photo of your fan limit controller as well as of the Hobart furnace and any data tags on the equipment I can comment further.

On 2018-11-10 12:03:21.085477 by Herb

Have a old Hobart furnace it runs and stop have heat what does the limit switch look like is it the one that said fan auto on it and r the universeal

On 2018-06-14 01:07:06.206361 by (mod) -

I'd look for an intermittent short between the thermostat wires.

On 2018-06-13 15:26:13.934498 by mc63

With the thermostat set to 'off', my fan blower motor has suddenly started to randomly turn on, run for 10-15 minutes, then shut off. I replaced the thermostat thinking that was the problem, but the problem persists. An when I say randomly, it could be several hours or several days between incidents. Is the fan limit switch the problem? (The A/C furnace unit is probably 16-17 years old.)

On 2018-02-06 16:40:24.390108 by (mod) -

Bill

watch out calling you should never turn the fan limit switch spring by hand as doing so bends the internal spring, makes the switch inaccurate, and mix the control unsafe.

What's up morning completed I would watch the behavior of the switch when the burner comes on at your furnace. If the burner is coming on and they dialed or switch doesn't respond to the temperature change and then indeed the switch needs to be replaced.

On 2018-02-04 19:21:01.758260 by Bill

I have a furnace with a limit switch that won't turn my blower fan on when heat is on. The blower works fine in A/C mode but doesn't turn on when the thermostat is set to heat the house. I can manually turn the dial inside the Honeywell box, but when I let go, a spring pops the dial back into place and the blower turns off again. Any help would be awesome!

On 2017-11-29 23:35:42.812546 by (mod) -

Ron

Well I used to say no, just replace the switch, but a reader who is apparently somewhat a meticulous and careful worker, wrote to me that he drilled a tiny hole into the broken stub of the push pullswitch on the fan on switch on his limit control, then he inserted a little screw and used that to pull the button back out.

I can't officially recommend modifying any heating safety control since if you foul it up or damage it it is unsafe and could risk a building fire. Just sayin'

On 2017-11-28 11:50:45.585749 by Ron Hupe

My manual override switch Honeywell broke in manual position. Is there a way I can set it back to auto?

On 2017-09-25 23:42:35.815970 by (mod) -

Well SUPER going. Especially as you managed to drill into a safety control without drilling too far and snagging it or getting zapped.

On 2017-09-24 23:21:02.295131 by Anonymous


Thanks for the reply. After sending the question I had an idea to drill out the remaining plastic stub and try and hook the little bit of remaining plastic with a sharp dental tool. Amazingly it worked! The furnace cycled on and off as it should. And if I hadn't of thought of that, I would have tried something similar after reading your reply. We've had snow already this year, so having the furnace working is a wonderful thing. Thanks again!

On 2017-09-24 21:09:35.236509 by (mod) -

Betsy

On most fan limit switches that include this control pushing the button IN puts the fan in manual ON mode - just as you say. If you can't hook and pull out the broken off switch stub you will want to replace the switch. Disassembling the switch - which is not intended by its design, risks even slightly bending its temperature sensing movement that would render the switch unsafe.

On 2017-09-24 17:20:37.331102 by betsy

Hi there, my manual fan-on switch was pushed in and the part that sticks out broke off when removing the honeywell cover. So it is stuck in the fan on mode and runs constantly (unless i turn off the breaker). There is no way to get at it to get it back to auto setting. I don't want to replace the whole limit switch if I don't have to. Is there any way to get at it from inside or behind to at least get it to the pulled out setting and being automatic again?

On 2017-03-04 18:38:48.750723 by (mod) -

Chris:

If there is a separate FAN ON switch on your thermostat you can set that to "ON" - or if your furnace blower unit uses a fan limit switch, some of those switches also have a manual fan-on switch that you can use.

On 2017-03-04 08:49:04.024883 by Chris

I have a unit in my apt with the blower below the heater. The a/c unit is outside. The problem is this: when I set my thermostat to "ON" instead of "AUTO", the unit works as expected for heat. As furnace goes off/on, the blower stays on. However, when I try the same thing with the A/c, the blower shuts off briefly (for a second or two) and then restarts. I need to fix this; I need the thermostat set to the On position at night, so the blower runs constantly and does not briefly "reset" when the a/c comes on. Help please!

On 2017-01-06 05:00:03.570673 by Anonymous

at end of cycle it blows out cold air and cools off house

On 2017-01-06 04:00:59.917256 by (mod) -

Ken,

Pretty much any furnace will use a fan limit control. However some furnaces may use a control that is set at the factory and that has no adjustments.

I'm not sure what you mean by it cools off the house. But I don't think that changing the actual temperature ranges on the limits which would cure the problem that you described.

However if what you mean is that the fan continues to run at the end of a heat cycle, does blowing cold air into the occupied space, then I agree that the limit switch is not working properly. Most likely it needs to be replaced.

On 2017-01-05 23:38:09.333606 by Ken

i have a gas powered furnace horizontal in my crawl space under my house and it heats fine but it is to cold when it shuts down it cools off house. how do it set furnace is about 4 hears old and i can not find the limit switch on it i have changed and adjusted them before is there a limit on this one that can be adjusted

On 2016-12-11 03:28:08.716289 by (mod) -

Elc,

Do not keep pushing the reset button. On an oil-fired heating system when you keep pushing that button your risk ultimately causing a puff back explosion. You can search inspectapedia.com forPUFF BACK EXPLOSION to read details.

Several things can cause difficulty that prevents an oil burner from starting or running reliably. They're not things that a homeowner can repair. I suggest that you call your heating Service Company.


On 2016-12-10 23:33:10.429199 by Elc

I have a Honeywell oil hotter furace and it fires up and runs gets to temp, and blower runs for what I think is fine, so I think great no problem so this goes on for 3-5 cycles and then the furace does not fire up and I have to push the reset button it runs for a few seconds and then I have to push the reset again some times the green light comes on sometimes it doesn't , and it goes into lock out mode and I have to hold the reset for 20seconds and off we go again for another 3-5 cycles what is the problem, and do you have any segustions I'm so frustrated please help if possible and thank you. ELC

On 2016-10-11 11:27:02.749901 by Richard

Can you hook G wire for fan On directly to the R wire on a regular thermostat?

On 2016-09-17 22:54:21.533284 by (mod) -

Thanks for the follow-up, Bob, keep us posted as what you learn will certainly help other readers. To permit space for citations and diagrams I've moved our discussion to the bottom of the article above, pending another home.

D

On 2016-09-17 20:35:23.587694 by Bob

Dan, your comments helped me with a search string that found this link:
http://www.learningaboutelectronics.com/Articles/How-to-connect-a-double-pole-double-throw-relay-in-a-circuit
It shows the circuits on the relay I have. My blower does have a multi speed motor with 3 speeds of which I am using two. I will study the link above and see if I can figure out how to activate low speed for heat. I am currently wired up as specified in my previous message, this link should allow me to determine if I can change it or not. I'll let you know after I study it.

On 2016-02-12 23:24:06.288604 by Ricky H

Have oil furnace, my problem is burner starts fine but then it will shut down before fan starts. Fan switch is rotating and once burner shuts off, the fan will start and then the burner will restart several seconds later.

On 2016-02-02 15:11:08.666316 by Steve Beukema

Thank you for this info, it was very helpful.

Question: operating the limit switch FAN ON switch

(Jan 31, 2014) marie said:

My fan limit control says push man and an arrow, no white button, only an empty hole. What should I do? I set the numbers at their correct positions but the blower still remains on for a while and then comes back on after going off. I was lucky enough to replace my blower motor on my own after ordering it online. NO HELP FROM ANY MEN! The least of my worries was the fan limiter. Now after a month of heat I need help! Thank you

Reply:

If your limit control has no actual operable push-pull button or switch, then it's a model that omitted that feature. The switch will still work automatically. The manual switch is an extra, not mandatory.

Be careful not to mess with, force, or bend the switch parts - doing so could make it unsafe.

Question: olsen ultramax furnace NG that clicks on for 3 seconds

(Mar 5, 2014) norm williams said:
have an olsen ultramax furnace NG that clicks on for 3 seconds off on for 4 seconds 3rd time kicks in to running. going to change the pilot assembly kit, hope that's all. runs a lot. put in a new thermostat already. hope to hear from you. norm

Reply:

Norm,
I don't blame you for thinking about the pilot assembly as it sounds as if the unit has trouble starting. Keep in mind that dirt or debris at the igniter or pilot could be the problem, as could a sensor, or at the thermocouple itself. Often by watching the flame at start up we can figure out what's going on. For example if a the pilot lights but then goes out I suspect that a thermocouple is bad.

Question: Does the Honeywell fan and limit control have any part in controlling the fan in a/c operation

(Sept 22, 2014) JT said:
Does the Honeywell fan and limit control have any part in controlling the fan in a/c operation or is that done strictly by the fan relay and thermostat? I just installed a new fan and limit control ion my furnace and the blower continues to run for 10 minutes after the a/c condenser shuts off?

Reply: no but ...

JT

The fan limit switch is a heating control and does not work during cooling

except

if someone puts the switch in manual FAN ON position then the blower fan will simply keep running.

Question: replacement fan limit switch L4064w1296 19538c

(May 27, 2015) Ron said:
I need a replacement fan limit switch L4064w1296 19538c. It is no longer listed. I am using a dual energy system (oil/electricity)at my choice. Where can I get a replacement ?

Reply:

A check with the manufacturer of your heating furnace and with your heating service technician should confirm that you can use one of the more generic fan limit switches.

Question: 1971 GE split system HVAC single knob temperature control

(June 19, 2015) john.nordo said:
I have a 1971 GE split system HVAC unit at my residence. It has a single knob temperature adjustment for the fan blower timer. What is the proper sequence to adjust this style? It's set somewhere around 110 now
Thanks

Reply:

I dunno, John. Give us the model and serial number and we can perhaps locate the manual for you.

On 2013-01-15 21:24:54.465092 by Jerry Ciardelli

My Honeywell limit switch is similar to your pics except mounted horizontal. Adj. wheel appears to be same.
Problem:I cannot move (red in your info) adjuster to increase temp from 150 to 200. Next to the adj. lever is what appears to be a factory set blocker. I do not see the hole for the pen tip or similar device and I do not know what a slog is (dictionary no help) Do you have a picture or other advise?

On 2012-12-29 00:51:57.950419 by Anonymous

this was the best answer i have ever gotten,thank you so much

On 2012-12-04 23:17:37.438368 by Scott

I am setting up a Hydronic Heating system where I have put a heat exchanger into the existing heathing duct. The hot water will circulate through the heat exchanger and we would like to use the existing fan/blower from the Olsen oil burning furnace to blow air through the heat exchanger. We obviously want the fan to come on separate from the oil burning furnace and do not want to have to rely on running the fan in manaul mode on the Honeywell Fan Limit Switch. I think we have everything figured out, use of aquastat etc except for how to turn the fan on with the hydronic thermostat. I do not see where there is a G connector or anything like that on the stove to just run the fan by itself.

On 2012-12-02 17:07:26.455069 by Dgeorge@georgegems.vom

This is exactly what I needed. My heating co set at 60 and 150...very frequent short cycles.

On 2012-11-11 15:57:02.547423 by Abimael Luciano

really good info here. im studing HVACR and there is amazing information on heating systems.

On 2012-10-08 01:43:49.470827 by (mod) -

Warren,
Thank you for the helpful short on cycle diagnostic comment. I will ad it to the article text.

On 2012-10-07 01:24:07.596196 by Warren

Just lit the furnace, and it was cycling the blower off in less than a minute. After reading the article, I pulled the cover off to watch the limit switches. They were set right on. What I found was, that I hadn't turned the gas full on, so after the blower kicked in, the switch was cooling down to the shutoff. A little more gas kept the the dial where it was running.

On 2012-09-30 13:07:31.848116 by S .P. dolce

furnace goes off and on does not stay on long enough

On 2012-09-26 18:57:09.050240 by Dennis

The problem I’m having with my Honeywell Fan Limit Control is; when the thermostat calls for heat, the oil furnace burner turns on as it should – however the burner continues operate and the blower fan does NOT turn on. The burner continues to run until the plenum temperature reaches High Limit setting of the fan limit control – at which point the furnace burner is shut off. As the plenum temperature cools down the fan will start to run and continue to run until the low set point is reached, if the thermostat temperature is not satisfied – the burner will come back on and 90% of the time the fan will operate as it should; however if the plenum cools all the way down and a totally new heating cycle is called for, the problem repeats. This problem occurred with my old (20 years) Honeywell fan limit control – so I replaced the control with a new Honeywell Fan Limit Control. The problem repeated itself with the new control. I rechecked the wiring and that was correct. The bimetal probe is the same recommended length as the old one and does not seem to be binding. I did not change the factory setting on the control dial. I returned the Honeywell Fan Limit Control and replaced it with a second Honeywell Fan Limit Control. Everything worked fine for the first several cycles and then the problem repeated itself. I have a 10 year old Honeywell 7 day programmable thermostat and have made sure it has fresh batteries and it cycles off and on as it should. As usual new filters have been placed in the furnace, the furnace has been cleaned and the blower motor seems to function as it should when I set it to manual operation with the switch on the control. Any ideas?
Thanks,
Dennis

On 2012-09-26 18:56:22.389764 by Dennis

The problem I’m having with my Honeywell Fan Limit Control is; when the thermostat calls for heat, the oil furnace burner turns on as it should – however the burner continues operate and the blower fan does NOT turn on. The burner continues to run until the plenum temperature reaches High Limit setting of the fan limit control – at which point the furnace burner is shut off. As the plenum temperature cools down the fan will start to run and continue to run until the low set point is reached, if the thermostat temperature is not satisfied – the burner will come back on and 90% of the time the fan will operate as it should; however if the plenum cools all the way down and a totally new heating cycle is called for, the problem repeats. This problem occurred with my old (20 years) Honeywell fan limit control – so I replaced the control with a new Honeywell Fan Limit Control. The problem repeated itself with the new control. I rechecked the wiring and that was correct. The bimetal probe is the same recommended length as the old one and does not seem to be binding. I did not change the factory setting on the control dial. I returned the Honeywell Fan Limit Control and replaced it with a second Honeywell Fan Limit Control. Everything worked fine for the first several cycles and then the problem repeated itself. I have a 10 year old Honeywell 7 day programmable thermostat and have made sure it has fresh batteries and it cycles off and on as it should. As usual new filters have been placed in the furnace, the furnace has been cleaned and the blower motor seems to function as it should when I set it to manual operation with the switch on the control. Any ideas?
Thanks,
Dennis

On 2012-01-31 19:58:25.549130 by Gary

My limit switch is cycling the BURNER about every 4 minutes, followed by about 90 seconds off. I think that this is a recent change in furnace behaviour. I removed the switch cover, and indeed the dial rotates up to about 200F, shuts off for a bit, then cools down. Since this behaviour begins just 8 minutes after a cold furnace start-up, and since the air flow into the rooms seems fine, I suspect a bad limit switch. Any comments?

On 2012-01-25 02:15:44.053749 by Rob

I was working on a oil furnace and the fan would not stop working.

On 2012-01-03 00:16:55.578729 by MATT 77

Thank you,My twentyone years old furnace is working find thinks to your topic on setting the limit switch. super step by step instructions.(AND FREE)BLESS YOU!
THANKS,MATT77

On 2012-01-03 00:09:37.721488 by Anonymous

Thank you,My twentyone years old furnace is working find thinks to your topic on setting the limit switch. super step by step instructions.(AND FREE)BLESS YOU!
THANKS,

On 2011-12-03 05:55:18.322033 by matt k.

Excellent instructions! I followed them and easily replaced the Limit Control in our late 80's Whirlpool furnace (Heil Quaker / Honeywell switch 1149505). Never touched the inside of a furnace before but your directions were spot on. Thank you.

On 2011-11-02 00:06:43.850436 by Sara

I should have also noted that this is a wood furnace (located in the garage and feeding into the forced air system.

On 2011-11-02 00:03:22.204164 by Sara

I am having the same issue as "anon". With the factory settings, it was cycling 10 seconds on and 1 minute off. I separated the FAN ON and FAN OFF controls to 90 and 160, respectively. Now it is running about 2 minutes on and 2 minutes off. I am worried about the motor burning out. Is this rate of cycling OK? I am not sure exactly how quickly the ideal cycling rate is. Thanks! So glad I found this forum.

On 2011-11-01 00:16:38.703773 by (mod) -

Victa there could be several problems but given that you had no trouble testing the blower assembly and found that the fan motor runs, I'd try replacing the switch. FIRST just be sure that the thermostat is calling for heat and that its wiring is hooked up. You can confirm that by calling for heat and watching to see if the burner ignites in your heater. If it does then the limit switch should turn on the fan once the plenum reaches the turn-on temp.

On 2011-10-31 19:08:40.729693 by victa

My blower did not come on after my system fired up, so I removed and tested the blower,it worked fine. Should I suspect my L4064A combination limit control? Is the limit L4064A and B the same?

On 2011-10-31 18:57:38.107033 by victa

I have a honeywell L4064A combination limit control, all you talk about is L4064B are they the same?

On 2011-10-19 03:17:58.814843 by Shanna

Thanks Dan. the dial isn't bent, it just appears as though it has been turned about 72 degrees counter-clockwise.

Will a heating company charge to look at it? Or will they come and give a free estimate?

On 2011-10-19 01:31:05.867429 by (mod) -

Shanna if the dialnon your fan limit switch is bent askew I am afraid it may be unsafe and need replacement. Mishandling the dial during setting can bend internal parts.

The modified temperature settings could also point to inexpert hands on the switch.


Because the dvice depends on an intact bimetallic spring to work, it may not safely respond to a high furnace temperature. I'd ask your heating service co to take a look and to replace the switch if appropriate.

On 2011-10-19 00:55:40.921092 by shanna

The off is at 50, on at 100 and OFF at 150. I see above it should be 90, 130 and 200 from factory. I also noted the the disc it self is not level (text doesn't read straight across it is on an angle) any advice?

On 2011-10-19 00:50:44.086980 by Shanna

there is no white fan button and the fan never shuts off. The limit setting is really low, can I change it? is this something I can do myself or should I call a furnace tech?

On 2011-10-08 23:34:13.071170 by (mod) -

Anon:

The temperature settings on the fan limit switch pertain to temperatures inside the warm air plenum in the air handler and should not be affected by outdoor temperatures. If the fan switch is cycling on and off too rapidly I suspect that either

- the switch is defective

or

- the limit switch is doing its job but you are blowing very cold air into the plenum, dropping it below the cut-in temperature quickly. This can happen if the incoming air temperature and flow rate is more than the heater is able to keep up with.

On 2011-10-08 18:19:28.541680 by Anonymous

We have a 1600EF USSC outdoor wood stove and the fan kicks on and off a lot. a minute on, a couple minutes off. We haven't changed the preset settings of 100/150/200. What can we change so it kicks on and off less? Does this change with outside temperature?

On 2011-10-04 15:25:42.032580 by (mod) -

Shawn
First take a look at our page top photo - if your switch looks like the one we show, check that white pull/push knob - it may have been switched to keep the fan on continuously.

Second check your thermostat - it may have a "FAN ON" switch - be sure your switch is set to AUTO or try OFF to see what happens.

Third if those steps don't work I'd call a service tech as you may have a bad thermostat or fan limit control switch.

On 2011-10-04 12:54:09.822796 by Shawn

My fan will not shut off...what do I do ?


...

Continue reading at FAN LIMIT SWITCH TROUBLESHOOTING or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.

Or see these

Recommended Articles

Suggested citation for this web page

FAN LIMIT CONTROL SETTING FAQs at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.


Or see this

INDEX to RELATED ARTICLES: ARTICLE INDEX to HEATING FURNACES

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Ask a Question or Search InspectApedia

Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.

Search the InspectApedia website

Note: appearance of your Comment below may be delayed: if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.

Only one image can be added per comment but you can post as many comments, and therefore images, as you like.
You will not receive a notification
when a response to your question has been posted.
Please bookmark this page to make it easy for you to check back for our response.
Our Comment Box is provided by Countable Web Productions countable.ca

Comment Form is loading comments...

Citations & References

In addition to any citations in the article above, a full list is available on request.



ADVERTISEMENT