AIR CONDITIONING & HEAT PUMP SYSTEMS

A/C - HEAT PUMP CONTROLS & SWITCHES
A/C DATA TAGS
A/C - HEAT PUMP CRITICAL DEFECTS
A/C DIAGNOSTIC FAQs
A/C REFRIGERANTS
A/C TYPES, ENERGY SOURCE
AGE of AIR CONDITIONERS & HEAT PUMPS

AIR CONDITIONER BTU CHART
AIR CONDITIONER COMPONENT PARTS
AIR CONDITIONER TYPES, ENERGY SOURCES
AIR CONDITIONER NOT WORKING

AIR FILTERS for HVAC SYSTEMS

AIR HANDLER / BLOWER UNITS
  DIRTY A/C BLOWERS
  DAMAGED COOLING COIL
  DIRTY COOLING COIL
  DIRTY COIL CLEANING PROCEDURES
  FROST BUILD-UP on AIR CONDITIONER COILS
  BLOWER FAN CONTINUOUS OPERATION
  BLOWER FAN OPERATION & TESTING
  BLOWER LEAKS, RUST & MOLD
  ADDING A/C: RETROFIT SIZING
ANIMAL ALLERGENS / PET DANDER
ANIMAL ENTRY POINTS in buildings
ANIMAL ODORS IN buildings
APPLIANCE EFFICIENCY RATINGS
ASBESTOS IDENTIFICATION IN buildings

BACKUP HEAT for HEAT PUMPS

BLOWER DOORS & AIR INFILTRATION
BLOWER FAN CONTINUOUS OPERATION
BLOWER FAN OPERATION & TESTING

BOOKSTORE - Air Conditioning "How To" Books

CAPACITORS for HARD STARTING MOTORS
CAPILLARY TUBES
CHINESE DRYWALL HAZARDS
CIRCUIT BREAKER SIZE for A/C or HEAT PUMP
CLEANING & Legionella BACTERIA
CHINESE DRYWALL HAZARDS
COMBUSTION GASES & PARTICLE HAZARDS
CONDENSATE HANDLING, A/C
CONDENSATION or SWEATING PIPES, TANKS
COMPRESSOR & CONDENSING COIL, A/C
  BURNED-OUT COMPRESSOR
  CAPACITORS for HARD STARTING MOTORS
  CONDENSING COIL REPAIR REPLACE
  CONTACTOR RELAY DIAGNOSIS & REPAIR
  CONTROL CIRCUIT BOARD, A/C
  FAN, COMPRESSOR/CONDENSER UNIT
  HARD STARTING COMPRESSOR MOTORS
  INSPECTION CHECKLIST - OUTDOOR UNIT
  INSTALLATION ERRORS, COMPRESSORS
  LONG-ON CYCLING AC COMPRESSOR
  MOTOR OVERLOAD RESET SWITCH
  NOISES, COMPRESSOR CONDENSER
  Pressure Controls & Safety Switches
  PRESSURE READINGS, COMPRESSOR
  REPLACING A COMPRESSOR
  SHORT CYCLING AC COMPRESSOR
  TIGHT or SEIZED AC COMPRESSORS

CONDENSATE HANDLING, A/C
  DRIP TRAY DEFECTS
  CONDENSATE LEAKS
  CONDENSATE PUMPS
  CONDENSATE DRAINS
  CONDENSATE DRAIN CLEAN & DE-CLOG
  CONDENSATE TRAY CLEANING
CONTROLS & SWITCHES, A/C - HEAT PUMP
COOL OFF HEAT Thermostat Switch
COOLING CAPACITY, RATED
COOLING COIL or EVAPORATOR COIL
COOLING LOAD REDUCTION by ROOF VENTS
COMBUSTION GASES & PARTICLE HAZARDS
CONDENSATE HANDLING, A/C
CONDENSATION or SWEATING PIPES, TANKS

DATA TAGS on AIR CONDITIONERS
DEFINITION of Heating & Cooling Terms

DEHUMIDIFICATION PROBLEMS
DEW POINT CALCULATION for WALLS
DEW POINT TABLE - CONDENSATION POINT GUIDE

DIAGNOSE & FIX AIR CONDITIONER / HEAT PUMP
DUCT SYSTEM & DUCT DEFECTS
  AIR FILTERS for HVAC SYSTEMS
  ALLOY SYSTEMS FLEXDUCT
  ASBESTOS HVAC DUCTS
  ASBESTOS PAPER on DUCTWORK
  ASBESTOS TRANSITE DUCTWORK
  BALANCING AIR DUCT FLOW
  DUCT & AIR HANDLER ODORS
  DUCT DAMAGE, MECHANICAL
  DUCT INSULATION - Asbestos Paper
  DUCT ROUTING & SUPPORT
  DUST CONTAMINATION FROM HVAC?
  FIBERGLASS DUCT, RIGID CONSTRUCTION
  FIBERGLASS HVAC DUCTS
  FIRE DAMPERS in DUCTWORK
  FLOOD DAMAGE in DUCT WORK
  GOODMAN GRAY FLEXDUCT
  INCREASING RETURN AIR
  LEAKY DUCT CONNECTIONS
  LOCATION OF REGISTERS & DUCTS
  MOLD in AIR HANDLERS & DUCT WORK
  NOISES in DUCT SYSTEM
  ODORS in AIR HANDLERS & DUCT WORK
  OWENS CORNING FLEXDUCT
  OWL FLEXDUCT
  RETURN AIR REGISTERS & DUCTS
  SOUNDPROOFING for DUCTWORK
  SUPPLY DUCTS & REGISTERS
  TRANSITE PIPE AIR DUCTS
  UNDERSIZED RETURN DUCTS
  UNSAFE DUCT OPENINGS
  VIBRATION DAMPENERS
  WATER & ICE IN DUCT WORK
  WET CORRODED DUCT WORK
  ZONE DAMPER CONTROLS

DUST CONTAMINATION FROM HVAC?

EDUCATION, HVAC SCHOOLS
ELECTRIC MOTOR DIAGNOSTIC GUIDE
ELECTRIC MOTOR OVERLOAD RESET SWITCH
ELECTRICAL POWER SWITCH FOR HEAT

ENERGY SAVINGS in buildings
EVAPORATIVE COOLING SYSTEMS
EVAPORATOR COIL or COOLING COIL
EXPANSION VALVES, REFRIGERANT

FAN, AIR HANDLER BLOWER UNIT
FAN AUTO ON Thermostat Switch
FAN, COMPRESSOR/CONDENSER UNIT
FAN CONVECTOR HEATERS - HYDRONIC COILS
FAN LIMIT SWITCH
FAN NOISES

FURNACES WARM AIR HEATING SYSTEMS

GASES, EXPOSURE, TESTING
  Carbon Dioxide - CO2
  Carbon Monoxide - CO
  METHANE GAS SOURCES
GAS MEASUREMENT TOOLS
GAUGE, REFRIGERATION PRESSURE TEST

HEAT LOSS (or GAIN) in buildings
HEAT PUMPS

HUMIDITY LEVEL TARGET

INDOOR AIR QUALITY IMPROVEMENT GUIDE

INSPECTION CHECKLIST - OUTDOOR UNIT
INSPECTION LIMITATIONS
LEED GREEN BUILDING CERTIFICATION

LOST COOLING CAPACITY
  What to Check First
  A/C Flow Too Weak
  A/C Filter Problems
  A/C Compressor Problems
  A/C Off - Condensate Pan Switch
  A/C Cooling Coil Icing
  A/C Not Dehumidifying
  A/C Air Duct Problems
  Air Conditioner Won't Start
  Air Conditioner Refrigerant Problems
  Blower Fan No Start / No Stop
  Compressor Diagnosis: Diagnose & Repair
  Cooling Capacity of the Duct System
  Repair Guide Master List

MANUALS & PARTS GUIDES - HVAC
MOTOR OVERLOAD RESET SWITCH

NOISY AIR CONDITIONER / HEAT PUMP

OPERATING COST
OPERATING DEFECTS
OPERATING TEMPERATURES
  Air Conditioning System Temperatures
  Instruments Used to Measure A/C Temperatures
  Procedures for Making Temperature Measurements

PORTABLE ROOM AIR CONDITIONERS
PRESSURE READINGS, REFRIGERANT

REPAIR GUIDE, AIR CONDITIONERS / HEAT PUMPS
REPAIR & DIAGNOSTIC FAQs for A/C

REFRIGERANTS
  GAUGE, REFRIGERATION PRESSURE TEST
  REFRIGERANT CHARGING PROCEDURE
  REFRIGERANT DRIERS & FILTERS
  REFRIGERANT LEAK DETECTION
  REFRIGERANT LEAK REPAIR
  REFRIGERANT METERING DEVICES TEVs
  REFRIGERANT METERING CAPILLARY TUBES
  REFRIGERANT PIPING & DISTANCES
  REFRIGERANT PRESSURE READINGS
RETROFIT SIZING for A/C or HEAT PUMPS

SEER RATINGS & OTHER DEFINITIONS
SOLAR ENERGY SYSTEMS
SPLIT SYSTEM AIR CONDITIONERS & HEAT PUMPS
SWAMP COOLERS
SYSTEM OPERATION

THERMOSTATS, HEATING / COOLING
THERMOSTATIC EXPANSION VALVES

WATER COOLED AIR CONDITIONERS

More Information

Photograph of  this unusual attic air conditioning system is an example of
the range of human creativity observed during a career of building inspections Air Conditioner or Heat Pump System Operating Defects & How to Fix Them
InspectAPedia®  -         

  • Air conditioning & heat pump operating defects & what to do
  • Air conditioner won't start, noisy, or short cycling
  • Air conditioner does not produce enough cool air volume or air is not cool enough
  • High air conditioner bills or tripping air conditioner circuit breakers
  • Questions & answers about heat pump problem diagnosis and repair

This A/C diagnosis article lists common air conditioning or heat pump operating defects, tells you what to check, and recommends specific air conditioner or heat pump repair guide articles found at this website.

InspectAPedia offers impartial, unbiased advice without conflicts of interest. We will block advertisements which we discover or readers inform us are associated with bad business practices, false-advertising, or junk science. Our contact info is at InspectAPedia.com/Contact.htm.

This A/C repair article is part of our more extensive air conditioning inspection, diagnosis, & repair document which describes the inspection, diagnosis, and repair of residential air conditioning systems (A/C systems) for home buyers, owners, and home inspectors. Contact us to suggest text changes and additions and, if you wish, to receive online listing and credit for that contribution.

© Copyright 2012 InspectAPedia.com, All Rights Reserved. Information Accuracy & Bias Pledge is at below-left. Use page top links to major topics or use links at the left of each page to navigate within topics and documents at this website. Green links show where you are in a document series or at this website.

OPERATING DEFECTS - Air Conditioning System Maintenance & Operating Defect Diagnosis & Repair Guide

Air conditioner or heat pump basic schematic (C) D FriedmanHere we list typical, readily observed, air conditioning system operating defects. Use the links at the left side of any of our pages to find more detailed information about these and other air conditioning system defects, as well as diagnostic and repair procedures.

In our sketch at left and in more detail at AIR CONDITIONING & HEAT PUMP SYSTEMS, the major components of an air conditioning system are described, sketches and photographs are provided, and common defects for each component are listed along with visual or other clues that may suggest a problem or probable failure of A/C components.

Here at OPERATING DEFECTS we take you through the major air conditioning problem symptoms and how to get the air conditioning system working again. At a companion article, LOST COOLING CAPACITY, our focus is on the case in which the air conditioning system seems to be "running" but not enough cool air, or no cool air at all is being delivered to the occupied space. At A/C - HEAT PUMP CONTROLS & SWITCHES we explain the many electrical switches and controls that control an air conditioner or heat pump system. You'll need to check these if your air conditioner won't start.

  • The air conditioning system will not operate at all - it won't start up: If the air conditioning system won't run at all, electrical power may be off, controls may be improperly set, or the system may be inoperative for other reasons. First confirm that the system has electrical power and that all of its control switches and thermostat are set to "on" and "cooling" positions. see CONTROLS & SWITCHES and see THERMOSTATS. Keep in mind that there are some hard-to-find switches that could be keeping your air conditioner off, such as a Float Switch on Condensate Tray or a blower MOTOR OVERLOAD RESET SWITCH
  • The air conditioning system operates but does not produce any cool air, or not enough cool air. see LOST COOLING CAPACITY
  • The air conditioning system operates but there is not enough cool air flow at the registers. (see DUCT SYSTEM DEFECTS and see LOST COOLING CAPACITY.)
  • The compressor was short-cycling, that is, turning itself on and off rapidly, perhaps every few seconds or minutes rather than producing a normal on-cycle of 10 minutes or longer. (see COMPRESSOR CONDENSER). See FAN, COMPRESSOR/CONDENSER UNIT for help in diagnosing and fixing problems with the outdoor compressor/condenser fan and fan motor.
  • The compressor was noisy, during startup, indicating an operating problem. (see COMPRESSOR NOISES.)
  • The compressor squealed at startup, indicating that service may be needed promptly to prevent possibly costly damage to the system. This repair/maintenance item should not be deferred. (see COMPRESSOR NOISES.)
  • Inside cooling or evaporator coil defects that can be seen by eye: dirty coil, blocked coil, frost on the coil, improperly sized evaporator coil, improper evaporator or cooling coil placement in the system. (See COOLING COIL or EVAPORATOR COIL and also AIR HANDLER / BLOWER UNITS for details.)

    Air flow requirements across the air conditioning evaporator coil: if airflow is weak for any reason (dirty coil, duct system defects, blower fan defects, dirty blower squirrel cage fan), the air conditioning system will not operate properly.

    How many cubic feet of air per minute should move across the evaporator coil? Some experts write that there should be between 350 and 400 cubic feet of air per minute (CFM) moving across the evaporator (cooling) coil for each ton of air conditioner capacity. (One ton = 12,000 BTUH so if your AC unit is a 24,000 BTUH unit it is a "two ton" unit and needs to see 700 to 800 CFM of air across the evaporator coil.

    Some home inspectors and air conditioning service technicians carry a small airflow meter that can actually measure this number with fair accuracy. (The same tool is nice for comparing air flow and balancing air flow at various building supply ducts and registers.

    Evaporator coil cleaning often requires cutting refrigerant lines, removal of the coil and other components for cleaning, and reinstallation, pulling a vacuum on the refrigerant lines, and recharge with refrigerant. Such service and repair may involve significant expense, although there are some "in place" cleaning methods using foams and sprays that are a simpler procedure. (see OPERATING TEMPERATURES.)

  • Dirty air conditioning filters, - a source of increased operating costs. Very dirty filters can eventually block the fan itself, leading to more costly repairs. The filters should be changed monthly when the system is in use. Failure to properly filter dust from the return air supply can load the fan or evaporator coil with dust and prevent proper system operation. Installing a filter is normally a minor expense. D

    irty, blocked evaporator coils can result in improper system operation, very low output temperatures, low air flow (compensated sometimes by increased fan speed), and sometimes frost on the coil and failure of system components. (see AIR HANDLER / BLOWER UNITS.) (see OPERATING TEMPERATURES.)
  • The air conditioner operates but our electrical bills are too high. (see SEER RATINGS and see DUCT SYSTEM DEFECTS.)
  • The heat pump will provide cool air but does not provide heat when heating is required. (See BACKUP HEAT).
  • The heat pump will provide heat but not cool air when cooling is required. (See BACKUP HEAT).
  • The air conditioner fuse keeps blowing or the circuit breaker trips: could mean a compressor which needs repair or replacement, or it could mean a problem with the unit's electrical wiring, such as use of aluminum wiring combined with bad electrical connections.

    Have your service technician check the condition of the electrical circuit first (that's cheaper than a new air conditioning compressor) and then check the condition of the compressor. see COMPRESSOR CONDENSER for air conditioner compressor diagnosis and repair; and if your air conditioning system electrical wiring is aluminum, review the aluminum wiring hazards at ALUMINUM WIRING HAZARDS & REPAIRS since a serious fire hazard could be present.

How to diagnose and fix an air conditioning system that is not working

Since the failure of an air conditioner to turn on, loss of air conditioner cooling capacity, reduced air conditioning output temperatures, loss of cool air supply, or even loss of air flow entirely can be due to a variety of problems with one or more components of an air conditioner or air conditioning system, after reviewing the lost air conditioner cooling diagnosis procedures described in this article, be sure to also review the diagnostic procedures at each of the individual air conditioning diagnosis and repair major topics listed just below. To return to our air conditioning and refrigeration home page go to AIR CONDITIONING & HEAT PUMP SYSTEMS.

If your air conditioning or heat pump system has lost its cooling capacity or won't start select one or more of the diagnostic articles listed below.

  • A/C - HEAT PUMP CONTROLS & SWITCHES: air conditioner controls and switches - begin here if your A/C won't start. Here's an important tip: most refrigeration problems, in air conditioners, refrigerators, or freezers, are electrical, not mechanical. In air conditioning school, we used to drive out and collect abandoned refrigerators that people were tossing out during our community's spring cleanup week. Taking these appliances back into the shop we found that almost always the problem that had caused the owner to dispose of their air conditioner or freezer was in an electrical connection or electrical control. So it's worth checking out switches and controls on an air conditioner before replacing more costly components.
  • OPERATING DEFECTS: major air conditioning problem symptoms and how to get the air conditioning system working again,e.g. compressor or fan noises, failure to start, and inadequate cool air volume
  • LOST COOLING CAPACITY: what to do when not enough cool air comes out of the system
    • What to check first if there is no cool air or not enough cool air
    • Compressor failure diagnosis: basic checks of the air conditioner compressor
    • Ducts & Air Handler diagnosis: basic checks of the indoor air handler (blower), air ducts, and filter systems
  • COMPRESSOR CONDENSER: problems with air conditioner compressor/condenser units. Also see FAN, COMPRESSOR/CONDENSER UNIT for help in diagnosing and fixing problems with the outdoor compressor/condenser fan and fan motor.
  • AIR HANDLER UNIT: problems with the air handler, air filters, and the cooling coil itself
  • DUCT SYSTEM DEFECTS: problems with the air duct system, air filters, supply registers, return air registers
  • A/C REFRIGERANT LEAK DETECTION: how to use a TIF5000 to detect air conditioning refrigerant gas leak
  • A/C DIAGNOSTIC FAQs: air conditioning system diagnostic FAQs: Q&A about air conditioner repair - a detailed air conditioning system diagnostic checklist

Questions & Answers regarding this article

.

Ask a Question or Search InspectAPedia

HTML Comment Box is loading comments...

Share this Article      

...

Technical Reviewers & References

  • InspectAPedia.com® - Daniel Friedman - Publisher & Editor.
  • InspectAPedia Bookstore lists recommended books, organized by topic & available for purchase. Most of our articles also include a list of recommended books for the specific article topic as well as other references, and information sources.
  • Critique, contributions wanted: Contact Us to suggest corrections or additions to articles at this website, and if you wish, to receive online listing and credit as a contributor. Particular thanks are due to the many experts and also consumers who read and critique technical articles at InspectAPedia.com.
  • Additional technical contributors & reference sources for this article are listed below.

Use links just below or at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website.

AIR CONDITIONING & HEAT PUMP SYSTEMS

A/C - HEAT PUMP CONTROLS & SWITCHES
A/C DATA TAGS
A/C - HEAT PUMP CRITICAL DEFECTS
A/C DIAGNOSTIC FAQs
A/C REFRIGERANTS
A/C TYPES, ENERGY SOURCE
AGE of AIR CONDITIONERS & HEAT PUMPS

AIR CONDITIONER BTU CHART
AIR CONDITIONER COMPONENT PARTS
AIR CONDITIONER TYPES, ENERGY SOURCES
AIR CONDITIONER NOT WORKING

AIR FILTERS for HVAC SYSTEMS

AIR HANDLER / BLOWER UNITS
  DIRTY A/C BLOWERS
  DAMAGED COOLING COIL
  DIRTY COOLING COIL
  DIRTY COIL CLEANING PROCEDURES
  FROST BUILD-UP on AIR CONDITIONER COILS
  BLOWER FAN CONTINUOUS OPERATION
  BLOWER FAN OPERATION & TESTING
  BLOWER LEAKS, RUST & MOLD
  ADDING A/C: RETROFIT SIZING
ANIMAL ALLERGENS / PET DANDER
ANIMAL ENTRY POINTS in buildings
ANIMAL ODORS IN buildings
APPLIANCE EFFICIENCY RATINGS
ASBESTOS IDENTIFICATION IN buildings

BACKUP HEAT for HEAT PUMPS

BLOWER DOORS & AIR INFILTRATION
BLOWER FAN CONTINUOUS OPERATION
BLOWER FAN OPERATION & TESTING

BOOKSTORE - Air Conditioning "How To" Books

CAPACITORS for HARD STARTING MOTORS
CAPILLARY TUBES
CHINESE DRYWALL HAZARDS
CIRCUIT BREAKER SIZE for A/C or HEAT PUMP
CLEANING & Legionella BACTERIA
CHINESE DRYWALL HAZARDS
COMBUSTION GASES & PARTICLE HAZARDS
CONDENSATE HANDLING, A/C
CONDENSATION or SWEATING PIPES, TANKS
COMPRESSOR & CONDENSING COIL, A/C
  BURNED-OUT COMPRESSOR
  CAPACITORS for HARD STARTING MOTORS
  CONDENSING COIL REPAIR REPLACE
  CONTACTOR RELAY DIAGNOSIS & REPAIR
  CONTROL CIRCUIT BOARD, A/C
  FAN, COMPRESSOR/CONDENSER UNIT
  HARD STARTING COMPRESSOR MOTORS
  INSPECTION CHECKLIST - OUTDOOR UNIT
  INSTALLATION ERRORS, COMPRESSORS
  LONG-ON CYCLING AC COMPRESSOR
  MOTOR OVERLOAD RESET SWITCH
  NOISES, COMPRESSOR CONDENSER
  Pressure Controls & Safety Switches
  PRESSURE READINGS, COMPRESSOR
  REPLACING A COMPRESSOR
  SHORT CYCLING AC COMPRESSOR
  TIGHT or SEIZED AC COMPRESSORS

CONDENSATE HANDLING, A/C
  DRIP TRAY DEFECTS
    Missing Condensate Overflow Pan
    Improper Condensate Drain Connects
    Float Switch on Condensate Tray
    Water in Condensate Overflow Pan
  CONDENSATE LEAKS
  CONDENSATE PUMPS
  CONDENSATE DRAINS
    Locations for Condensate Disposal
    Plumbing Code for Condensate Drains
    Improper Condensate Disposal
    Condensate Drains Connected to Vent Pipe
    Condensate Spills in Crawl Spaces
    Condensate Leaks Onto Heat Exchangers
    Condensate Disposal Outdoors
    Condensate Drains to Hidden Location
  CONDENSATE DRAIN CLEAN & DE-CLOG
  CONDENSATE TRAY CLEANING
CONTROLS & SWITCHES, A/C - HEAT PUMP
COOL OFF HEAT Thermostat Switch
COOLING CAPACITY, RATED
COOLING COIL or EVAPORATOR COIL
COOLING LOAD REDUCTION by ROOF VENTS
COMBUSTION GASES & PARTICLE HAZARDS
CONDENSATE HANDLING, A/C
CONDENSATION or SWEATING PIPES, TANKS

DATA TAGS on AIR CONDITIONERS
DEFINITION of Heating & Cooling Terms

DEHUMIDIFICATION PROBLEMS
DEW POINT CALCULATION for WALLS
DEW POINT TABLE - CONDENSATION POINT GUIDE

DIAGNOSE & FIX AIR CONDITIONER / HEAT PUMP
DUCT SYSTEM & DUCT DEFECTS
  AIR FILTERS for HVAC SYSTEMS
  ALLOY SYSTEMS FLEXDUCT
  ASBESTOS HVAC DUCTS
  ASBESTOS PAPER on DUCTWORK
  ASBESTOS TRANSITE DUCTWORK
  BALANCING AIR DUCT FLOW
  DUCT & AIR HANDLER ODORS
  DUCT DAMAGE, MECHANICAL
  DUCT INSULATION - Asbestos Paper
  DUCT ROUTING & SUPPORT
  DUST CONTAMINATION FROM HVAC?
  FIBERGLASS DUCT, RIGID CONSTRUCTION
  FIBERGLASS HVAC DUCTS
  FIRE DAMPERS in DUCTWORK
  FLOOD DAMAGE in DUCT WORK
  GOODMAN GRAY FLEXDUCT
  INCREASING RETURN AIR
  LEAKY DUCT CONNECTIONS
  LOCATION OF REGISTERS & DUCTS
  MOLD in AIR HANDLERS & DUCT WORK
  NOISES in DUCT SYSTEM
  ODORS in AIR HANDLERS & DUCT WORK
  OWENS CORNING FLEXDUCT
  OWL FLEXDUCT
  RETURN AIR REGISTERS & DUCTS
  SOUNDPROOFING for DUCTWORK
  SUPPLY DUCTS & REGISTERS
  TRANSITE PIPE AIR DUCTS
  UNDERSIZED RETURN DUCTS
  UNSAFE DUCT OPENINGS
  VIBRATION DAMPENERS
  WATER & ICE IN DUCT WORK
  WET CORRODED DUCT WORK
  ZONE DAMPER CONTROLS

DUST CONTAMINATION FROM HVAC?

EDUCATION, HVAC SCHOOLS
ELECTRIC MOTOR DIAGNOSTIC GUIDE
ELECTRIC MOTOR OVERLOAD RESET SWITCH
ELECTRICAL POWER SWITCH FOR HEAT

ENERGY SAVINGS in buildings
EVAPORATIVE COOLING SYSTEMS
EVAPORATOR COIL or COOLING COIL
EXPANSION VALVES, REFRIGERANT

FAN, AIR HANDLER BLOWER UNIT
FAN AUTO ON Thermostat Switch
FAN, COMPRESSOR/CONDENSER UNIT
FAN CONVECTOR HEATERS - HYDRONIC COILS
FAN LIMIT SWITCH
FAN NOISES

FURNACES WARM AIR HEATING SYSTEMS

GASES, EXPOSURE, TESTING
  Carbon Dioxide - CO2
  Carbon Monoxide - CO
  METHANE GAS SOURCES
GAS MEASUREMENT TOOLS
GAUGE, REFRIGERATION PRESSURE TEST

HEAT LOSS (or GAIN) in buildings
HEAT PUMPS

HUMIDITY LEVEL TARGET

INDOOR AIR QUALITY IMPROVEMENT GUIDE

INSPECTION CHECKLIST - OUTDOOR UNIT
INSPECTION LIMITATIONS
LEED GREEN BUILDING CERTIFICATION

LOST COOLING CAPACITY
  What to Check First
  A/C Flow Too Weak
  A/C Filter Problems
  A/C Compressor Problems
  A/C Off - Condensate Pan Switch
  A/C Cooling Coil Icing
  A/C Not Dehumidifying
  A/C Air Duct Problems
  Air Conditioner Won't Start
  Air Conditioner Refrigerant Problems
  Blower Fan No Start / No Stop
  Compressor Diagnosis: Diagnose & Repair
  Cooling Capacity of the Duct System
  Repair Guide Master List

MANUALS & PARTS GUIDES - HVAC
MOTOR OVERLOAD RESET SWITCH

NOISY AIR CONDITIONER / HEAT PUMP

OPERATING COST
OPERATING DEFECTS
OPERATING TEMPERATURES
  Air Conditioning System Temperatures
  Instruments Used to Measure A/C Temperatures
  Procedures for Making Temperature Measurements

PORTABLE ROOM AIR CONDITIONERS
PRESSURE READINGS, REFRIGERANT

REPAIR GUIDE, AIR CONDITIONERS / HEAT PUMPS
REPAIR & DIAGNOSTIC FAQs for A/C

REFRIGERANTS
  GAUGE, REFRIGERATION PRESSURE TEST
  REFRIGERANT CHARGING PROCEDURE
  REFRIGERANT DRIERS & FILTERS
  REFRIGERANT LEAK DETECTION
  REFRIGERANT LEAK REPAIR
  REFRIGERANT METERING DEVICES TEVs
  REFRIGERANT METERING CAPILLARY TUBES
  REFRIGERANT PIPING & DISTANCES
  REFRIGERANT PRESSURE READINGS
RETROFIT SIZING for A/C or HEAT PUMPS

SEER RATINGS & OTHER DEFINITIONS
SOLAR ENERGY SYSTEMS
SPLIT SYSTEM AIR CONDITIONERS & HEAT PUMPS
SWAMP COOLERS
SYSTEM OPERATION

THERMOSTATS, HEATING / COOLING
THERMOSTATIC EXPANSION VALVES

WATER COOLED AIR CONDITIONERS

  • Thanks to Mark Cramer, Tampa Florida, for assistance in technical review of the "Critical Defects" section and for the photograph of the deteriorating gray Owens Corning flex duct in a hot attic. Mr. Cramer is a Florida home inspector and home inspection educator.
  • Thanks to Mike Giaquinto and Scott at SJM Inspect for technical editing remarks, 5/16/07
  • Thanks to Jon Bolton, an ASHI, FABI, and otherwise certified Florida home inspector who provided photos of failing Goodman gray flex duct in a hot attic.
  • Carson Dunlop, Associates, Toronto, have provided us with (and we recommend) Carson Dunlop Weldon & Associates' Technical Reference Guide to manufacturer's model and serial number information for heating and cooling equipment ($69.00 U.S.).

Books & Articles on Building & Environmental Inspection, Testing, Diagnosis, & Repair

  • Our recommended books about building & mechanical systems design, inspection, problem diagnosis, and repair, and about indoor environment and IAQ testing, diagnosis, and cleanup are at the InspectAPedia Bookstore. Also see our Book Reviews - InspectAPedia.
  • Complete List of Air Conditioning & Heat Pump Design, Inspection, Repair Books at the InspectAPedia Bookstore.
  • Home Reference Book - Carson Dunlop The Home Reference Book - the Encyclopedia of Homes, Carson Dunlop & Associates, Toronto, Ontario, 2010, $69.00 U.S., is available from Carson Dunlop. The Home Reference Book is a bound volume of more than 450 illustrated pages that assist home inspectors and home owners in the inspection and detection of problems on buildings. The text is intended as a reference guide to help building owners operate and maintain their home effectively. InspectAPedia.com ® author/editor Daniel Friedman is a contributing author. Field inspection worksheets are included at the back of the volume.
  • Modern Refrigeration and Air Conditioning, A. D. Althouse, C.H. Turnquist, A. Bracciano, Goodheart-Willcox Co., 1982
  • Principles of Refrigeration, R. Warren Marsh, C. Thomas Olivo, Delmar Publishers, 1979
  • "Air Conditioning & Refrigeration I & II", BOCES Education, Warren Hilliard (instructor), Poughkeepsie, New York, May - July 1982, [classroom notes from air conditioning and refrigeration maintenance and repair course attended by the website author]
  • Refrigeration and Air Conditioning Technology, 5th Ed., William C. Whitman, William M. Johnson, John Tomczyk, Cengage Learning, 2005, ISBN 1401837654, 9781401837655 1324 pages
  • Carson Dunlop, Associates, Toronto, have provided us with (and we recommend) Carson Dunlop Weldon & Associates' Technical Reference Guide to manufacturer's model and serial number information for heating and cooling equipment ($69.00 U.S.).
  • Air Conditioning Inspection, Diagnosis, Repair, Efficiency all the basics for home owners, inspectors, new repairmen
  • NewAir Conditioning SEER - New DOE Air Conditioner and Heat Pump Efficiency Standard
  • Asbestos HVAC Ducts and Flues field identification photos and guide
  • Fiberglass: Indoor Air Quality Investigations: Fiberglass in Indoor Air, HVAC ducts, and Building Insulation
  • ...
  • Home About Us Accuracy Contact Us Content Use Policy Privacy Website Description © 2012 Copyright InspectAPedia.com