Water System Check Valve FAQs
Check valves on water supply systems: FAQs
Questions & answers about water supply piping check valves used on both municipal water supply piping and on private pump and well water supply systems.
These check valve FAQs help in the selection, installation and troubleshooting of various types of water system check valves and backflow preventer valves and foot valves.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?
These questions and answers about check valves and backflow preveners used on water supply systems were posted originally
at CHECK VALVES, WATER SUPPLY, DRAINS, PUMPS - be sure to read the details about installation and troubleshooting and checkvalve types in that article.
Also see our index to all well pump & piping check valve questions and answers at FOOT VALVE DIAGNOSIS & REPAIR FAQs
...
Just curious as to some input on the two types of check valves and is one better than the other? It would seem that the flapper type would be less restrictive than the spring type?
I have a well system and I need to replace the booster pump at the house so I want to replace the check valve to the pump suction at the same time. I currently have the spring type and it has worked OK but maybe the flapper type would be better? - Terry
Reply: Spring Loaded Check Valves are Recommended
Terry expert sources such as the Water Systems Council and many plumbers recommend spring-loaded check valves, not gravity-operated check valves and not swing-type check valves.
These recommendations have been added to our water system check valve article above.
Wayne, you mentioned that for a well system you recommend a spring loaded check valve (any particular brand) - My well tank and tank tee are in need of replacing after about 25 years of service and
I was looking at getting a Watts 1” Brass Female In-Line Dual Check Valve Lead Free LF7R-U2-2 -
Could you explain what a dual check valve is and is it okay to use with my well system? On 2016-08-15 by LarrY H
Answer by (mod)
Watts is a perfectly fine brand.
Dual check valves means that there are two check valves connected in series. That arrangement reduces the chance of a leak or backflow.
Can a check valve be mounted directly on a foot valve for negative suction in fire fighting pump installation? 2 July 2015 Vincent Iweze
Reply:
VIncent
The foot valve is itself a check valve.
For deep wells (hundreds of feet) the well pump manufacturer will usually recommend additional check valves at intervals in the riser pipe.
But there are special requirements for check valves on water supply systems and pump systems used fire fighting applications.
Take a look at NFPA 20, Standard for the Installation of Stationary Pumps for Fire Protection (2025) (NFPA website)
NFPA 20 protects life and property by providing requirements for the selection and installation of pumps to ensure that systems will work as intended to deliver adequate and reliable water supplies in a fire emergency.
The following excerpt is quoted from an article by Milosh Puchovsky in CSE Magazine in 2012:
Certain devices in the suction piping can cause an undesirable degree of uneven flow and turbulence, and impede pump operation and performance.
NFPA 20 currently states that within 50 ft of the pump suction flange, no valve other than a listed outside stem and yoke (OS&Y) valve can be installed in the suction piping.
This provision was revised to clarify that no “control” valve other than a listed OS&Y valve is to be installed within 50 ft.
The provision was further revised to specifically address backflow devices.
These changes provide for better consistency with other provisions of the standard and clarify the intent of the requirement, which is to restrict only the use of butterfly valves, and allow the installation of OS&Y gate valves, check valves, and backflow devices in the suction piping.
Note, however, that the installation of check valves and backflow devices in the suction piping is only permitted where such devices are required by other standards or by the AHJ.
Where a check valve or backflow prevention device is required upstream of the fire pump suction, NFPA requires the device to be a minimum of 10 pipe diameters upstream of the pump suction flange. - Puchovsky, Milosh, P.E., FSFPE, " NFPA 20: Changes to the standard on fire pumps - Regardless of whether the 2013 edition of NFPA 20 will be applicable to your next project, fire protection engineers need to be aware of the changes to the standard." - CSE Magazine - By Milosh Puchovsky, PE, FSFPE, Worcester Polytechnic Institute, Worcester, Mass 11/15/2012
...
Just curious as to some input on the two types of check valves and is one better than the other? It would seem that the flapper type would be less restrictive than the spring type?
I have a well system and I need to replace the booster pump at the house so I want to replace the check valve to the pump suction at the same time. I currently have the spring type and it has worked OK but maybe the flapper type would be better? - Keith
Reply: List of Check Valve Locations on Water Supply Piping & Well Installations
Keith, some experts recommend multiple check valves while others make reasonable arguments for installing only one check valve on water systems.
But some of the confusion probably occurs because not every plumber or well installer is talking about the same installation conditions.
Take a look at the page top photo and you'll see a check valve on the incoming well line, between the jet pump and the building wall.
If we're talking about the same device and situation, and if your well pump itself is not providing an internal check valve, the usual spot for an external check valve that is above ground is just as you see in the photo.
A foot valve is installed on well piping at the bottom of the well in all shallow well installations, in deep well jet pump installations, and in some deep well submersible pump installations.Additional check valves may be installed on well piping inside the well, within 25 ft. of the well bottom and under-water that is, below the top of the static head level of the well water, and again every 200 feet of vertical well piping in very deep well installations.
A check valve is often installed near the end of the incoming well piping right before the one line jet pump, above ground, especially if the jet pump does not have its own working internal check valve (as many do).
Is there a check valve in this control center assembly?
Pump cycles once or twice and loses all pressure. When this happens it sounds like a check valve letting go. On 2018-05-15 by (mod) -
Reply by (mod)
Tom,
I can't quite see any check valve in your photo but it doesn't mean that your system doesn't include one elsewhere on the piping system or as a foot valve in your well.
Typically the check valve will be
- at the jet pump for an above ground one line jet pump
- in the well as a foot valve for two line jet pumps and some submersible pumps
- in the well piping between pressure tank inlet and well casing for many deeper wells
- in multiple stages in the vertical riser pipe in the well for very deep wells more than 100 ft.
How do i know if my foot valve is bad on a two line system. and how do i find the well opening? (Mar 24, 2014) Ted
Reply:
Ted,
How to Find a Water Well:
If your system keeps losing prime that's a good clue that there may be a bad foot valve (or a leak in well piping).
I can't know where your well is located, but there are some common approaches starting by noticing where well piping exits the building, inspecting the site for places we would NOT put a well (like near a septic field), contacting well drillers to ask who drilled the well (often they have records of its location), inspecting the site for obvious clues (depressions, well casing visible above ground), and ultimately, using equipment to follow well piping.
At CHOOSE WELL LOCATION & DIGGING METHOD we discuss where you want to locate a water well
At SEPTIC TANK, HOW TO FIND we discuss how to find the septic tank - but similar methods might be used to locate a well whose casing or top is buried and not immediately obvious.
If inspecting the property itself does not disclose an above-ground, visible well casing and cap then you may have an older well whose casing top was left buried.
I'd start by looking in the building for a sketch of well location - often left in a basement or crawl area over or close to the pressure tank and pump/controls, or sometimes even sketched on a ceiling joist or wall where the well pipe exits the building.
If that doesn't come up with a sketch of well location, continue by calling all of the well drillers in your area to ask if one of them installed the well.
Well piping can often be traced using pipe locating equipment.
A last resort is a series of small test excavations to follow the well line.
How to access the foot valve in this pump:
The pump can't maintain prime. I am guessing it's a bad foot valve.
#1 how do I access the foot valve? The bolts for the well cap are jammed up and are not turning even with wd-40.
#2 In the second picture (of the pipes going into the well), is that a check valve?
- Ed. - Daniel
How-to get at the foot valve in a well
this is indeed a bear.
To access the foot valve you will have to remove the well pump and piping from the well cap at the top of the casing, then either get those bolts out or cut or break them in the process.
Which should not be the end of the world in that you can replace the well casing top seal and will want to anyway. you're probably looking at a compression-type well casing top seal: two metal plates squash together squeezing a rubber center that expands to seal around pipes and well casing.
Relieving the tension unsquashes and lets you pry out the remaining parts.
Beware to avoid dropping stuff down into the well. Perhaps if just one bolt is loosened you will be able to loosen the cap seal.
No I don't see a check valve. I see ABS plastic well piping.
Watch out: A well driller would use one or more special grabbing tools to be darn sure not to drop the whole shebang down into the well in the course of trying to get the cap off.
If you insist on doing it yourself, after you've dropped the pipe into the well, you can read about well pipe & tool retrieval tools here at InspectApedia, taking comfort in the fact that many dopes were way ahead of you in dropping stuff down the well. (Including me).
Is there a disadvantage to installing a check valve at the pressure tank if the check valve on the submersible pump is not working? On 2015-04-11 by walt
Answer by (mod) - some pumps don't want multiple check valves
Walt
That's a common repair effort that might work;some pump manufacturers warn that multiple check valves in the system can cause malfunctions but that advice is inconsistent with standard advice for deep well submersible pump installations: there we're advised to install an additional check valve for every 150 feet of lift. So IMO bottom line, try it.
For closed loop systems it is not a good idea to put check valve on suction side of pump.
Check valves for well piping systems should be placed on the discharge end of the piping. Centrifugal pumps sometimes can not open check valves on the suction side of the pump especially after repairs. - Butch 21 April 2011
I replaced a foot valve (with double clamps) in under ground cistern and it didn't hold the pressure anyway. So I add check valve front of the tank and it works just about OK - Wes
Reply:
Wes, I've seen above-ground check valves installed to defer pulling and replacing the foot valve; but Butch makes a proper and correct point.
If your system is working OK you may be fine but if you find your pump is having trouble losing prime you might go ahead and replace the valve in the cistern.
Certainly in the case of a cistern the foot valve won't be so difficult to pull as we're not talking about a deep well.
I have lots of water but immediately after pump shuts off at 50 it drops to 30 and then the pump comes back on and refills my tank; k
this happens a few times every minute. And no water is running anywhere in the house. Where's the bad check valve? Or is this a bad bladder? On 2016-11-08 by john
by (mod) pressure drops after pump turns off - there is a leak to find and fix: here are common check valve locations
John:
Check for a leak in well piping or foot valve if you can by shutting off a valve between well and pump (don't let the pump keep running or it'll be damaged).If the pressure drops then there's a leak on the house side. If pressure doesn't drop but does when you open the valve again then there's a leak in well piping or foot valve.
Depending on just what type of pump you have installed there may be a check valve in the pump itself ( a one line or two line above ground jet pump)
and there may also be a check valve in the well (a foot valve at the bottom of the water pick-up line)
and for deep wells using a submersible pump or a deep well using a 2-line jet pump, if the water pick up is more than 200 feet down in the well there may be additional check valves on the vertical well pipe in the well.
I have a gravity water tank roof top on my house-Water is pumped up by the city when working OK. When the water (municipal) is not working I use the roof tank,
Where should a check valve be installed at? (June 28, 2014) John
Reply:
Kyle the supply valves, if they are provided (which I recommend) are installed at the time of connection of the fixtures to the supply piping or sooner.
For example one might install the rough-in plumbing, then install supply valves at fixture locations throughout the building, leaving them in closed position.
That allows water to be turned on and used at some building locations before fixtures have been installed throughout.
The alternative of soldering a cap on the unconnected supply pipes is less attractive since later to connect up those supplies to fixtures building water has to be turned off.
Will installing a check valve on my upstairs bathroom hot water supply line prevent water from being siphoned back down to the first floor when the hot water is turned on in the kitchen about 30 ft. away? The upstairs hot water cools in the pipes and takes a long time for the water to become hot in the kitchen. thanks. On 2017-02-27 by paul
by (mod) - no; here's how your water system works
This doesn't sound right, Paul.
First, Your water supply system is normally under pressure - depending on whether your supply is from a residential main or a private pump and well, pressure is typically between 20 psi and 70 psi - that is way more than enough to push water up to a second floor of a home.
Second, with an upper floor faucet closed, water will have a very hard time flowing backwards out of that upper piping into a fixture below, even if building water pressure were lost - until you open the tap to let air into the line.
I would look at the piping run from source to kitchen and perhaps improve hot water temperature by insulating the piping - thus reducing the amount of heat lost as hot water flows en route to the kitchen plumbing fixtures.
...
The check valve I bought for a shallow well that is being dug has an arrow on it. The check valve did not come with any instructions.
Which way should the arrow run when installing it on the well pipe? I have the exact same check valve as shown in your picture above. Thanks - Susan
Reply: The arrow cast into the check valve body marks the direction of water flow through the valve
When you are installing a check valve on water supply piping, the arrow cast into the body of the valve points to the direction of flow of the water.
So, for example, if your check valve is installed on the incoming well water supply pipe between the well and the water pressure tank or water pump, the arrow on the valve would point towards the pressure tank or pump.
Are check valves clearly marked, because on my setup there is a brass connector between the line coming in and the pump, but no arrows indicating flow? On 2016-05-30 by Anonymous
Answer by (mod)
Anon: there may be some check valves that lack a mark but usually it's cast right into the check valve surface; for some products the "in" and "out" sides may be evident by other features.
If you look into the valve body before it's installed you'll see the hinged flapper has a hinge at its upper end and you can see from the angle of the valve flapper the direction into which it will open. Install the valve so that the valve opens towards the "downstream" direction of water flow - away from the water source
You can use the page bottom CONTACT link to send me a photo for comment.
Keep in mind that there are other brass connectors (unions and couplings) that simply make it possible to join piping and are not check valves.
Should spring loaded check valves be installed vertical or horizontal? - Frank
Reply:
Frank, spring loaded check valves will operate in either horizontal or vertical position - the valve relies on the spring pressure to close the valve, not gravity.
If someone is using a gravity type or swing-type check valve, the valve can also be installed vertically or horizontally provided you notice the arrow cast into the check valve body.
A gravity or swing type check valve mounted vertically presumes water is flowing "up" through the piping and the arrow on the valve body should point up.
Watch out: as we explain in the article above, well piping experts do not recommend using swing type or gravity-operated check valves. Spring-loaded check valves are recommended.
How many check valves are install in a long water supply line i.e 30 km long supply line? On 2016-02-17 by abid
Answer by (mod)
Typical manufacturer recommendations are to put a check valve for each 200 to 250 feet of vertical well pipe rise.
ON long horizontal runs such as your 30 km line you should note the changes in elevation but the distance between check valves may of course be much greater as it's not likely to be straight up or down changes in elevation.
I am installing an indoor water storage tank and using a jet well pump (with a pre installed check valve.)
Am I able to place an inline CHECK Valve at the base of the storage tank outlet to keep from losing prime, rather than run plumbing to the storage tank at the top and attaching a foot valve to a suction pipe? Thanks in advance! On 2019-02-05 by SSG
by (mod) - no, that's not the right place
That does not sound correct to me. You want your check valve to be on the line between the pump and the well.
by SSG
Thanks for the quick reply. The pump has a pre built check valve at the suction line.
What I am thinking is adding a second check valve at the base of the storage unit to prevent the backflow of water in the line to the tank, and still keep prime. I've added a picture from this site that shows an example of my thoughts. Thanks again!
by (mod) -
I don't understand what that would buy you. The water pressure tank connects to building supply piping and keeps it pressurized. There would not normally be backflow from building supply piping into the tank.
If your well piping leaks and the pump's check valve leaks the pump is still going to lose prime.
...
My well pump was replaced 15 months ago and burned out last week. The installer thought the problem was due to iron in the water clogging the check valves.
Besides the check valve that comes in the pump there is a gate type check valve and an additional spring check valve above the pump. There is also a 6 GPM reducer in addition to the 3 check valves.
Does this seem excessive? On 2015-02-25 by JD
Answer by (mod) -
JD
If your installer can show you a clogged check valve s/he'd be on reasonable ground, as if a pump can't push water into the pressure tank to satisfy the pressure control switch it'd keep running and risk burnout.
Flow reducers have a different purpose: to slow the flow rate out of the well in an effort to avoid burning up a pump in a well that has a slow recovery or flow rate into the well bore. The presence of that device on your system makes me suspect that the root problem is poor well flow rate; if the pump gets ahead of the flow rate into the well bore it can indeed burn up unless it's protected.
InspectApedia has more advice about well pump protection devices: See WATER PUMP PROTECTION SWITCH
My well is 100' deep the check valve at the pump stuck open. I pulled the pump installed new Simmons check valve next day it's stuck open again. Any suggestions On 2016-02-06 by Carl
Suggestions by (mod)
How annoying, Carl. I'd double check that the valve was installed with the arrow cast into its body indicating the correct water flow direction;
I'd also inspect the valve for debris. Debris or mud can clog or jam a check valve.
I have a combination domestic city water supply that serves the domestic house and also the sprinkler system of my home. The domestic supply to the house has a pressure regulator to control the psi at 50 psi.
The sprinkler supply has an in line check valve installed. I have recently started to get water hammer noise on the sprinkler supply side of my service. The water hammer noise is intermittent and occurs at all hours of the day, even though no water is being used in the house.
If I close the valve to the sprinkler, it stops the water hammering sounds. Could the check valve to the sprinkler be faulty and is causing the water hammering? (Apr 7, 2014) Peter
Reply:
Peter that sounds like a very reasonable guess. It's sudden stopping of water flow that would be the initial cause of water hammer. Try changing the check valve and let us know the result - what you report will help others.
See WATER HAMMER NOISE DIAGNOSE & CURE
Water hammer broke the swing gate in our check valve
You are right about that. had a swing gate before the pressure tank . water hammer fractured the tank tee (May 26, 2015) Anonymous
My well pump was replaced 15 months ago and burned out last week. The installer thought the problem was due to iron in the water clogging the check valves. Besides the check valve that comes in the pump there is a gate type check valve and an additional spring check valve above the pump. There is also a 6 GPM reducer in addition to the 3 check valves. Does this seem excessive? 25 Feb 2015 JD
Reply:
JD
If your installer can show you a clogged check valve s/he'd be on reasonable ground, as if a pump can't push water into the pressure tank to satisfy the pressure control switch it'd keep running and risk burnout.
Flow reducers have a different purpose: to slow the flow rate out of the well in an effort to avoid burning up a pump in a well that has a slow recovery or flow rate into the well bore. The presence of that device on your system makes me suspect that the root problem is poor well flow rate; if the pump gets ahead of the flow rate into the well bore it can indeed burn up unless it's protected.
InspectApedia has more advice about well pump protection devices:
Is there something you can coat a check valve with so it doesn't build up calcium stay open when pump turns off? On 2017-05-15 by Lynette O'Quinn
Suggestion by (mod) -
Lynette
that's a great idea, but not a solution that I've seen. Certainly a spray on or rub on grease coating might be temporarily effective at reducing mineral salt deposition on a check valve but not a lasting one. Some manufacturers use more-permanent coatings and clog-resistant materials, but still, the root problem is in the water supply.
If your water supply contains such high minerals that in drainage it's clogging a check valve, then it is certainly clogging hot water piping and the water heater system even more rapidly;
Have your water tested for hardness, and if appropriate, you'll want to install a water softener. Use the on-page search box at the top or bottom of this page to find our article on WATER HARDNESS TEST and then on WATER SOFTENER INSTALLATION to see details.
...
I have shallow well so my pump is located in the crawl of my cottage. Recently we have been losing the prime
. I'm guessing it's the backflow preventer. It's located between the well and pump. Is there a better location?
How can I test to see if it's working. (July 4, 2015) Marty
Reply: turn off pump; turn off water into building; watch for pressure drop in the system.
Marty turn off water into the Home. If the pump still loses prime then the leak is between pump and bottom of the well pipe;
The check valve may be a foot valve at the bottom of the well piping - if yours is a jet pump;
...
...
Continue reading at CHECK VALVES, WATER SUPPLY, DRAINS, PUMPS - topic home, or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see these
CHECK VALVE FAQs at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Search the InspectApedia website
Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.
In addition to any citations in the article above, a full list is available on request.