This article and its tables explain the site, design, and materials criteria for the construction of a conventional septic drainfield.
We include tables that give a quick answer to how big the drainfield nees to be for various wastewater loads and soil percolation rates.
Septic drainfields, also called leach fields, absorption beds, soil absorption systems, soakaway beds, and leaching beds, perform the functions of septic effluent treatment and disposal in onsite wastewater treatment systems, conventionally called "septic systems".
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?
A conventional septic tank performs roughly 45% of the sewage treatment or less at a private home served by a septic system.
The rest of the wastewater treatment and ultimately the liquid disposal occurs in the drainfield.
[Click to enlarge any image] Sketch - USDA.
As you will read below, there is no one "right" septic absorption field size. Rather, the size needed (in square feet of area, presumably also unencumbered by trees, driveways, buildings, etc.) depends on several variables such as the rate at which the soil can accept liquid (the percolation or "perc" rate), and the expected daily volume of wastewater.
A lot with a good percolation rate or "perc" of perhaps one inch of percolation in 1-5 minutes might require about 125 feet of drainfield trench for a typical two bedroom home. If the same home were built where there was a poor soil percolation rate of 46-60 minutes per inch, 333 linear feet or more might be required for the absorption area. (See our drainfield sizing TABLE 4A below).
Typically, septic leach fields (synonyms: drainfield, leach bed, soakaway bed, absorption bed) are built by placing perforated effluent distribution pipes in a field or bed of gravel.
There are several types of absorption systems however, each having different effluent disposal capacity.
The leach field is a series of trenches that may be up to 100-feet long and 1 foot to 3 feet in width, separated by six feet or more, depending on local requirements, and sometimes constructed leaving space between the original lines to install replacement leach lines when needed. - paraphrasing USDA.
Drainfield size and location also have to take into account local zoning - setback requirements from property borders, setbacks from streams, wetlands, wells, water supply lines, and other encumbrances.
In the most common design of drainfield, perforated pipes are buried in gravel-filled trenches to form the drainfield.
[Click to enlarge any image]
This sketch shows a cross section of a typical drainfield trench, and places below the trench the critical biomat as well as other septic field design areas and considerations. (Source :US EPA who in turn obtained the drawing from Ayres Associates)
This section discusses the design requirements for conventional septic absorption fields, also called leach fields, drain fields, drainfields, soakaway beds, seepage beds, or conventional soil absorption systems.
(i) The minimum distances that absorption fields shall be separated from other facilities are shown in the sketch below.
[Click to enlarge any image]
See details and tables of septic component separation distances from various site features found
at CLEARANCE DISTANCES, SEPTIC SYSTEM
(ii) A minimum of four feet of usable soil shall exist above bedrock and groundwater with a minimum separation of two feet to the lowest part of any trench.
(iii) Absorption fields shall not be built under driveways, parts of buildings or under above-ground swimming pools or other areas subject to heavy loading. Surface waters shall be diverted from the vicinity of the system.
...
(i) The required length of absorption trench is determined from Table 4A based upon the percolation test results and confirmed by the soil evaluation. The maximum trench width for design purposes shall be 24 inches. Only 24 inches shall be allowed for absorption area calculations. W
here trenches exceed 24 inches in width, calculations of absorptive area shall be based on a width of 24 inches.
(ii) Adjacent trenches shall be separated by at least four feet of undisturbed soil. Individual trenches shall be constructed parallel to the ground contours with trench bottoms as near level as possible. They need not be perfectly straight but abrupt changes in direction shall be avoided.
P
|
Table 4A - Septic Wastewater Effluent Input Flow Rate (Gallons per Day) [1] |
||||||||||
Minutes / Inch |
2 Bdrms |
3 Bdrms |
4 Bdrms |
5 Bdrms |
6 Bdrms |
||||||
260 gpd |
300 gpd |
390 gpd |
450 gpd |
520 gpd |
600 gpd |
650 gpd |
750 gpd |
780 gpd |
900 gpd |
||
Required number of feet of absorption trench, assuming a 2-ft wide conventional gravel trench |
|||||||||||
1 - 5 | 108 ft. | 125 ft. | 162 ft. | 187 ft. | 216 ft. | 250 ft. | 270 ft. | 312 ft. | 325 ft. | 374 ft. | |
6 - 7 | 130 | 150 | 195 | 225 | 260 | 300 | 325 | 375 | 390 | 450 | |
8 - 10 | 145 | 167 | 217 | 250 | 290 | 333 | 360 | 417 | 433 | 500 | |
11 - 15 | 162 | 188 | 244 | 281 | 325 | 375 | 406 | 469 | 488 | 563 | |
16 - 20 | 186 | 214 | 279 | 321 | 372 | 429 | 464 | 536 | 557 | 643 | |
21 - 30 | 217 | 250 | 325 | 375 | 433 | 500 | 542 | 625 | 650 | 750 | |
31 - 45 | 260 | 300 | 390 | 450 | 520 | 600 | 650 | 750 | 780 | 900 | |
46 - 60 | 290 | 333 | 433 | 500 | 578 | 667 | 722 | 833 | 867 | 1000[2] | |
Dosing not required (but recommended) |
Dosing system or alternative design is required |
[1] Original source: New York State NYS75-A.8 Table 4A [image file]
[2] Conditions that require more than 1000 feet of septic drainfield trench must have an alternative dosing system design.
The following is adapted from our engineer's article summarizing "How Big Should the Septic Leach Field Be" found at
HOW BIG SHOULD THE LEACH FIELD BE?
Determining the required size of a leach field is a bit more complicated. The first thing to consider is the nature of the soil in which the leach field is to be constructed. Because water has to be absorbed in the soil, we need to know how fast it can be absorbed.
This is called the percolation rate and is expressed as the time it takes for water in a test hole to decrease in level by one inch (minutes/inch).
We must also know the type of soil and whether seasonal changes in the natural level of groundwater will interfere with the satisfactory operation of the system. Seasonal groundwater must be more than four feet from the bottom of the leach field trenches.
Judgments regarding the soil conditions and percolation rates are best left to a professional. If the soil percolates very quickly, (less than one minute per inch) or very slowly (greater than 60 minutes per inch) it will not be possible to install a standard leach field in the existing soil.
We must now determine the amount of water that has to be absorbed each day. As with the septic tank sizing, there are also "rules of thumb" that can be used to find out how much water must be absorbed each day for each bedroom in the house (expressed as gallons per day per bedroom).
The required flow rate is found by multiplying the appropriate flow by the number of bedrooms (in this case, we do not have to count a garbage disposal as a bedroom).
Knowing the rate at which water can be absorbed by the soil (the percolation rate) and the flow rate (in gallons per day), we can use the following table to calculate how many square feet of absorption field is needed.
Readers will notice that this table is similar to but less detailed than our typical state or board of health table above at TABLE 4A.
This table specifies the allowable wastewater application rate into the soil of a conventional septic system drainfield as a function of the soil percolation rate for percolation rates between 1 minute per inch to 60 minutes per inch.
This table specifies the allowable wastewater application rate into the soil of a conventional septic system drainfield as a function of the soil percolation rate for percolation rates between 1 minute per inch to 60 minutes per inch.
In other words, the table shows the allowable volume of wastewater in gallons that can be applied per day per square foot of septic field size.
Soils with a percolation rate of less than 1 minute per inch should not be used for a conventional septic drainfield.
Readers will note that this table considers only the dimensions of the bottom of the drainfield trench in considering the effective soil absorption area.
Typically a conventional drainfield trench is 2 ft. wide, so the effective absorption area is simply 2 ft. x field-length in ft.
Beware that in some jurisdictions, when calculating required drainfield trench lengths the authorities may consider the trench width to be a nominal one-foot wide regardless of its actual width.
Table 4B - Required Size Septic Leach Field for Non-Standard Flows |
|
Absorption Percolation Minutes per Inch |
Allowable Application Rate - Gallons per Day per Square Foot |
> 1 | Not Acceptable |
1 - 5 | 1.2 |
6 - 7 | 1.0 |
8 - 10 | 0.9 |
11 - 15 | 0.8 |
16 - 20 | 0.7 |
21 - 30 | 0.6 |
31 - 45 | 0.5 |
46 - 60 | 0.45 |
Original source: New York State Septic Design Code TABLE 4B - APPLICATION RATES [Image File]
...
(i) Perforated distributor pipe shall be used in the trenches.
(ii) Solid (non-perforated) pipe shall be used between the distribution box and the trenches.
(iii) Perforated pipe shall be made of rigid or corrugated plastic and be labeled as fully meeting ASTM standards for use in septic
systems.
(iv) Corrugated plastic pipe delivered in coils is not to be used unless provision is made to prevent the recoiling or movement of the
pipe after installation.
(v) Aggregate shall mean washed gravel or crushed stone 3/4 - 1 1/2 inches in diameter. Larger diameter material or finer substances and run-of-bank gravel are unacceptable.
(vi) The aggregate shall be covered with a material that prevents soil from entering the aggregate after backfilling, yet must permit air and moisture to pass through.
(vii) The preferred material for covering the aggregate is a permeable geotextile. Untreated building paper or a four inch layer of hay or straw is acceptable. Polyethylene and treated building paper are relatively impervious and shall not be used.
...
(i) Septic drain field trench locations and depths
should be marked by stakes before the trenches are excavated. The natural surface shall not be significantly
disturbed.
If
the site is re-graded or similarly disturbed, the soil shall be allowed to stabilize and new percolation tests conducted.
(ii) Septic drainfield trench depth shall be as shallow as possible,
but not less than 18 inches. At least six inches of aggregate is placed below the
distribution line and two inches above the line. The earth cover over the aggregate should not exceed 12 inches in order to enhance natural
aeration and nitrogen uptake by plant life.
(iii) Septic drainfield or soakaway trenches shall be excavated
to design depth with bottoms practically level.
(iv) Heavy equipment
shall be kept away from the field because the weight may permanently alter
soil characteristics due to compaction, cause trench cave-ins, and/or mis-align and break pipe.
(v) Septic drainfield or soakbed trench bottoms
are to be raked and immediately covered with at least six inches of aggregate.
(vi) Septic drainfield / leachfield trench walls:
Any smeared surfaces on the trench walls are to be raked.
(vii) Septic drainfield effluent distribution lines
are carefully placed on the aggregate and covered with
aggregate to a depth of at least two inches over the top of the pipe. Additional aggregate may be required to bring the top of the aggregate
to within six to 12 inches of the surface.
(viii) In gravity distribution septic systems, the pipe shall be carefully sloped
at between 1/16 inch and 1/32 inch per foot. Grades shall be determined
by an engineer's level, transit or carpenter's level.
(ix) Septic drainfield / soakbed trench cover:
After the upper aggregate is placed, the geotextile, untreated building paper, hay or straw is to be immediately installed and the
trench backfilled with native soil.
If the drainfield trenches cannot be immediately backfilled, they should be temporarily covered with an
impervious material such as treated building paper to prevent sidewall collapse and siltation into the aggregate.
(x) Septic drainfield / soakaway trench backfill:
The earth backfill is to be mounded slightly above the original ground level to allow for settling and after settlement the entire area
should be graded without the use of heavy equipment and seeded with grass.
[See our warnings at CONSTRUCTION OF SHALLOW SEPTIC SYSTEM ABSORPTION TRENCHES]
...
Continue reading at SEPTIC DRAINFIELD SHAPE or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see SEPTIC DRAINFIELD SIZE FAQs - reader questions & answers.
Or see these
SEPTIC DRAINFIELD DESIGN - CONVENTIONAL at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Questions & answers or comments about septic drainfield or soakaway bed size or capacity requirements & design.
Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.
Search the InspectApedia website
Note: appearance of your Comment below may be delayed: if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.
Only one image can be added per comment but you can post as many comments, and therefore images, as you like.
You will not receive a notification when a response to your question has been posted.
Please bookmark this page to make it easy for you to check back for our response.
Our Comment Box is provided by Countable Web Productions countable.ca
In addition to any citations in the article above, a full list is available on request.