Building Inspection, Diagnosis & Repair Info

sewage contamination sludge on the floor in a basement from a sewer line backupResponse to Sewage Backup, FAQs

Sewage or septic system backup response Q&A:

Answers to frequently-asked questions about what to do if your home or building has had a sewage spill or septic system backup into, below, or around the structure.

This article series explains just what to do in response to a septic or sewer backup into or even outside and around a building or in response to building flooding: this article explains how to respond to septic system or sewer backups in a building.

We explain the inspection, cleanup and other steps necessary to sanitize a building that has suffered flooding or sewage-contaminated backups as well as steps to return the building drain, waste, vent system to operation.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?





ADVERTISEMENT





Q&A on What to do When the Septic or Sewer System Backs Up

Evidence of sewage backup outdoors near a drain line cleanout (C) InspectApedia.com PG

Questions & answers posted originally at this article SEWAGE BACKUP, WHAT TO DO IMMEDIATELY - be sure you read the advice and procedures suggested there.

Watch out: sewage spills contain contaminants that can cause serious illness or disease. Disease causing agents in raw sewage include bacteria, fungi, parasites, and viruses and can cause serious illnesses including Hepatitis A.

Article Index

...

What could have caused sewage to come out of the basement toilet?

My basement flooded with sewage. It appears that it all exploded out of the downstairs toilet and out into the downstairs kitchen and laundry area.

We did not use enough water the last 48 hours to cause that much water(sewage) to spill out everywhere .

What could have caused this ?

Also everything over flowed in the middle of the night , I found it all like this in the morning On 2017-02-09 by Anonymous

Answer by (mod)

Possibly your sewer main or septic tank is backing up into your building.

When the building main sewer line is blocked or when a septic tank or system is blocked, and when an upstairs plumbing fixture is run, that water enters the upper portions of the building drain system.

When the main drain is blocked and wastewater cannot exit the building the waste from above creates a pressure in the drain system that will force wastewater or sewage out of any opening that is below the upper floor toilet, sink or other fixture.

That means that flushing a second floor toilet into a blocked drain may cause sewage to pour out of a lower floor toilet or enter a tub or shower through its drain.

...

After a forest fire our septic contents backed up into a toilet

My vacation house was in a recent forest fire. Minimal fire damage to house but complete burn up of trees and all ground cover.

We find septic system contents backed up full in the toilet, but not overflowed it. We were at the house 2 weeks before the fire and had no problems with the toilet flushing etc. Was it the heat that caused this to happen ? On 2016-07-24 by Anonymous

Answer by (mod)

Interesting question, anon. I don't know. If plastic sewer pipes were overheated and melted or collapsed by fire that could certainly give a backup condition; that combined with water entering the system from fire fighting or from rainfall might combine to push sewage back into the building.

I suggest exploring the sewer piping, perhaps by a sewer line camera, to find where it's blocked or damaged.

...

Sewage entered the slop sink - could that cause a mold problem in the AC system?

I had a sewer main break in the street. Sewage was backing up in my slop sink for weeks and slowly draining.

It never overflowed into my basement. Is there a possibility that my central AC unit was compromised since it is across from my slop sink? Possible mold contamination? On 2016-06-12 by KST

by (mod) re:

K

I'm assuming you're talking about the condensate drain for your A/C system? If so, only if the A/C drain was under sewage would it be particuarly worrisome.

If you are asking if there was airborne bacterial contamination in the HVAC system, that's possible; you might want to swab test your air handler and duct system for bacterial contaminants.

...

Is there a home remedy for sewage backup into washing machine?

Is there a home remedy?

Sewer water is coming out of the washing machine drain pipe and garbage disposal On 2015-12-07 by Mona

by (mod) re: probably not

Mona:

you'd need professional cleanup if there was an extensive sewer smell througout the floor of your home.

The cause of sewer backup may be a blockage in your own drain or on public sewer there could be a system problem. I don't have enough data about your home to guess.

...

What Makes Septic or Sewer Backup Wastewater Appear on Different Building Floors?

Can sewage or septic backups appear on upper building floors due to a bad drain line?

If you have a septic and the line is back pitched from the house to the tanks:

Is it possible for the backup to overflow the basement toilet and the 1st floor toilet? Or is it impossible for the backup to reach the main floor after the basement toilet overflows.

Is it possible for the main floor toilet to overflow and not the basement ?

Thanks in advance for your help, M.L.

Reply: Possible causes of septic or sewage backup

A competent onsite inspection by an expert who is familiar with septic and sewer systems usually finds additional clues that help accurately diagnose a problem with septic piping, backups, failures and overflows into the building. That said, here are some things to consider:

A septic system or a clogged sewer line, or a flooded sewer or septic system can certainly back up into a basement, crawl space, or other lowest floor of a building

A septic system (or even a sewer) draining out at basement level from a muilti-story house would not be expected to back up onto upper floors because it would find exit points first in the basement at toilets or other fixtures, and because it would be unlikely to develop enough pressure to force sewage out onto upper floors.

An exception to the point above would be the case of a building whose main drain is lower than a sewer or septic piping system. Such buildings use a pumping chamber to push wastewater to its destination.

If the septic or sewer pumping system failed and if the necessary check valves were not in place or were defective, sewage could back up to higher levels in the building What would more likely cause both sewage backup into a basement and onto upper floors in a building would be blocked system drains.

Follow-up from reader:

Just further clarification if you don't mind: i had a belly in my pipes and had a back up 3 times, 2 times for sure in the walkout basement and 1 time I believe it went to the floor above the walkout basement. I just wanted to know if that might have been the cause of the other floor or was it just coincidence that this happened during the same time as the other problem. Is it possible that this was the result of the belly in the pipes or just a random occurence ?

Reply: a belly or sag in sewer piping can cause partial and eventual complete drain blockage and sewer backups

Sewer backups may seem to be a random occurrence but in fact if we knew exactly what was going on with the drain, waste, vent system and the local sewer or septic system, there would be no backups attributed to just "chance".

A sag in a drain pipe can, over time, collect sediment, corrosion, and sewage that can lead to an eventual clog and backup. That's why plumbing codes specify that building drain piping should slope continuously with "horizontal" runs sloping at 1/8" to 1/4" per foot.

What can happen is that a partial blockage of a drain line accumulates more and more debris and becomes more and more solidified until a combination of a particularly large "dose" of solid waste, say feces and toilet paper, has trouble making it past the slow or partly blocked area. That in turn can lead to an actual sewer backup.

...

Testing for illnesses related to sewage backups or sewage contamination: Leptospirosis, Typhoid Fever or Yersiniosis

Approximately 2 months ago I moved into a new house, and 1 week in there was a sewage leak into the backyard. All of the piping needs to be replaced but only a small section has been, so although it is not spilling onto the surface of the yard anymore, I believe it is still leaking into the ground under the surface.

My dog has been very ill since living here (vomiting, diarrhea, and is now developing skin lesions). The tests come up negative for Giardia, but he gets better when on antibiotics. As soon as he is off the antibiotics he relapses and it finally occurred to me this may be due to the fact that the incoming water is contaminated.

He has not been specifically tested for Leptospirosis, Typhoid Fever or Yersiniosis, which I plan on having done today. Is there anything else you feel I should have him tested for?

In regards to the water testing, do you know of a laboratory in the Sacramento, CA area? If so, I would greatly appreciate you providing me with their contact information. Would the Total Coliform test be sufficient, or is there further testing you would recommend?

Thank you in advance for your help. - Best, L.S.

Reply: Warning about An incomplete treatment for Typhoid,

L.S. these are questions to ask your veterinarian and your doctor. Having some experience with Typhoid fever I can mention that our doctor advised that it was very important to be sure that any treatment for Typhoid be continued until the doctor is sure that the treatment has been effective, and thence it is important to avoid re infection.

Watch out: An incomplete treatment for Typhoid, such as failure to complete an effective course of antibiotics, risks leaving behind a antibiotic-resistant strain that could make future treatment still more difficult.

While the physician with whom we consulted, [S.R. SmDA, Nov 2011] is convinced that the only vector for Typhoid fever is from eating [Typhoid strain of salmonella-] contaminated food, we have also read that a secondary vector might be possible via mosquitoes or flies in contact with sewage.

...

Toilet pipe leaked sewage under my trailer home; I need help getting it cleaned up and tested

Live in Single Wide Trailer, toilet pipe disconnected and waste under trailer. It needs to be cleaned up and treated On 2015-04-15 by Saundra E. Brown

Reply by (mod) -

Saundra

You will need to call a local water damage/ restoration company. Beware of doing an extensive sewage cleanup yourself or by using someone else who does not understand the health hazards involved. You may want to ask your local board of health for advice.

...





ADVERTISEMENT





...

Continue reading  at SEWAGE BACKUP, WHAT TO DO IMMEDIATELY or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.

Or see SEWAGE BACKUP RESPONSE FAQs-2 - more-recently-posted questions and answers about sewage or septic backups and what to do

Or see these

Recommended Articles

Suggested citation for this web page

SEWAGE BACKUP RESPONSE FAQs at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

Or see this

INDEX to RELATED ARTICLES: ARTICLE INDEX to SEPTIC SYSTEMS

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Ask a Question or Search InspectApedia

Share this article:

Search the InspectApedia website

Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.

Citations & References

In addition to any citations in the article above, a full list is available on request.



ADVERTISEMENT