House to Septic Tank Sewer Line, Model Specifications for Septic Systems
House to Septic Tank Sewer Line Specifications:
Section 5 of these model septic design regulations discusses the design specifications for installation, placement, use of bends and turns, materials, and separation requirements for the installation of a house sewer line (the line between the house and the septic tank or the piping between a building and a municipal sewer system).
This document uses the New York State wastewater treatment standard for individual household septic systems (Appendix 75-A) to provide an example of state regulated design and installation of both conventional tank and leach field septic systems and alternative septic system designs, including raised septic systems, septic mound systems, intermittent sand filter septic systems, and evaportion-transpiration septic systems.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?
DF NOTE: this section of NYS regulations discusses the installation of house sewer lines which conduct waste from the building interior to an outside septic system or onsite wastewater treatment system.
Many state codes, including New York, focus on long-used well-established onsite septic system designs, and omit discussion of other, more recent septic and onsite wastewater handling methods such as aerobic septic systems.
Readers should therefore also be sure to see SEPTIC SYSTEM DESIGN ALTERNATIVES as well as the other septic system design and design alternative topics which have links at the end of this article.]
(a) House sewers
are laid on firm foundation at a minimum grade of
one-quarter inch per foot preferably without bends. At least one
cleanout with a properly fitted plug is to be provided. The house sewer
shall allow for venting of gases from the sewage system.
(b) House sewer construction
including materials shall comply with the
applicable requirements of the State Uniform Fire Prevention and
Building Code contained in 9NYCRR, Parts 903 through 907, inclusive, and
Part 1250.
© A minimum horizontal separation of 10 feet should exist between the
house sewer and any water line.
Where lines must cross, the water
service line shall be at least 12 inches above the house sewer. If
a
water line must pass below the house sewer, the vertical separation must
be at least 18 inches.
(d) Suction waterlines
shall never cross under house sewers or any other
component of the sewage system.
...
...
Continue reading at DRAIN & SEWER PIPING - topic home, or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see these
SEWER LINE SPECIFICATIONS at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Questions & answers or comments about specifications for the waste line connecting a building to a private septic tank, cesspool, or drywell.
Search the InspectApedia website
Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.
In addition to any citations in the article above, a full list is available on request.