Takagi Water Heater Error Codes, ManualsTakagi water heater error codes master list & Takagi water heater manuals.
We give contact information for Takagi water heater, geyser, cylinder, calorifier manufacturers and for Takagi water heater installation, operation, & troubleshooting manuals.
Page top image: A Takagi T-KJr2-IN-LP Indoor Tankless Water Heater, Propane fueled, for sale at Amazon.com.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?
Takagi produces these currently-popular tankless water heaters: T-KJr2/U, T-K4/U, T-D2/U, and the T-H3 series T-H3M-DV, T-H3J-DV, T-H3S-DV, T-H3-DV
Universal Table of Takagi / A.O. Smith Condensing Water Heater Error Codes |
||
| Error Code | Meaning | Takagi Water Heater Models |
| 1 | Wrong dip switch setting Red LED / Computer Board Fault | 110 (T‐ KJr2), 310 (T‐K4) Remote |
| 2 | Inlet Thermistor / Output Thermistor / Air-fuel ratio rod failure |
|
| 3 | Ignition Failure / Flame Loss | |
| 4 | Abnormal Fan Motor | |
| 5 | Warning for 991 error code / Abnormal Combustion | |
| 6 | Abnormal Gas Valves / Abnormal Solenoid Gas Valve / False Flame Detection | |
| 03 | Wrong dip switch setting, 110 (T‐ KJr2), 310 (T‐K4) Remote | 110 (T‐ KJr2), 310 (T‐K4) Remote |
| 10 | Warning for 991 Error Code | |
| 11 | Ignition failure | |
| 12 | Flame loss | |
| 31 | Output Thermistor | |
| 32 | Inlet Thermistor | |
| 39 | Air-Fuel Ratio Rod Failure | |
| 51 | Abnormal Gas Valves | |
| 55 | Abnormal Solenoid Gas Valve | |
| 61 | Abnormal Fan Motor | |
| 70 | Computer board fault | |
| 72 | False flame detection | |
| 74 | Remote controller communication failure | |
| 99 | Abnormal combustion | |
031 |
Wrong dip switch setting, possibly LP gas set when the fuel is Natural gas, or vice versa |
T-D2, T-H2-OS T-H3-DV/OS, T-H3J-DV/OS, T-H3S-DV/OS T-M32, T-M50 |
| 070 | Computer board failure - see 701 | |
| 072 | False flame detected - see 721 | |
| 074 | Remote control problem - see 741, 751 | |
| 099 | Improper combustion - see 991 Watch out: this is an unsafe condition risking CO hazards. |
|
| 101 | Improper combustion. Watch out: this is an unsafe condition. Look for a blocked flue or chimney (or downdrafts in the chimney) or a problem with the draft inducer fan. Warning for 991 error code |
T-D2, T-H2-OS T-H3-DV/OS, T-H3J-DV/OS, T-H3S-DV/OS T-M32, T-M50 |
| 111 | Ignition failure; the burners do not light. Check for a bad igniter, flame sensor, gas valve. Check for gas supply. Check for a blown fuse on the circuit board. | T-D2, T-H2-OS, T-M32, T-M50 |
| 121 | Burner flame lost. See code 111 above. | |
| 311 | Output thermistor failure. Check the thermistor and its wires on the heat exchanger. Replace the thermistor if you don't see a loose or disconnected wire. | T-H2-OS T-H3-DV/OS, T-H3J-DV/OS, T-H3S-DV/OS T-M32, T-M50 |
| 321 | Input / Inlet thermistor failure. Check the thermistor and its wires at the water inlet. Replace the thermistor if you don't see a loose or disconnected wire. | |
| 331 | Mixing Thermistor failure | |
| 341 | Thermistor failure | , T-H2-OS, T-H3-DV/OS, T-H3J-DV/OS, T-H3S-DV/OS |
| 391 | Air-fuel ratio rod failure. Check wire connections and if no loose wire, replace the AFR rod. | T-H2-OS, T-H3-DV/OS, T-H3J-DV/OS, T-H3S-DV/OS T-D2, T-M32, T-M50 |
| 441 | Flow Sensor Failure (Easy-Link or Multi-Link System Only) Possible: Inlet filter clogged, water flow problem. Also check for loose wire connections. |
|
| 510 | Gas valve failure. Inadequate gas pressure or flow. | |
| 551 | Gas solenoid valve failure. Check gas supply and if no problem the solenoid needs replacement. | T-H2-OS, T-M32, T-M50 |
| 611 | Abnormal fan motor | T-H2-OS, T-H3-DV/OS, T-H3J-DV/OS, T-H3S-DV/OS T-D2, T-M32, T-M50 |
| 621 | Exhaust fan motor (indoor models only) | T-H2-OS |
| 631 | Pump Failure | T-H2-OS, T-M32, T-M50 |
| 651 | Flow Adjustment Valve Fault (Easy-Link or Multi-Link System only) | T-H2-OS, T-H3-DV/OS, T-H3J-DV/OS, T-H3S-DV/OS T-D2, T-M32, T-M50 |
| 661 | Bypass valve fault (540 (T-H3) model only) | T-H2-OS, T-M32, T-M50 |
| 681 | External fan motor failure | T-M50 |
| 701 | Computer board failure; check for loose wires, electrical power supply, signs of damage to the board such as black or brown marks indicating overheating or burned | T-H2-OS, T-H3-DV/OS, T-H3J-DV/OS, T-H3S-DV/OS T-D2, T-M32, T-M50 |
| 711 | High Limit Switch / Overheat Cutoff Fuse Circuit is Compromised Watch out: this is an unsafe condition. |
T-H2-OS, T-H3-DV/OS, T-H3J-DV/OS, T-H3S-DV/OS |
| 721 | False flame detected. Check for condensate accumulation, blocked or missing condensate drain, condensate leaks. |
T-H2-OS, T-H3-DV/OS, T-H3J-DV/OS, T-H3S-DV/OS T-D2, T-M32, T-M50 |
| 741 | Remote control not communicating with the water heater, check remote batteries, check remote sensor wiring, remote control access line of sight. | T-H2-OS, T-H3-DV/OS, T-H3J-DV/OS, T-H3S-DV/OS T-M32, T-M50 |
| 751 | Temperature Controller Problem | T-H3-DV/OS, T-H3J-DV/OS, T-H3S-DV/OS |
| 761 | Communication Error in Easy-Link or Multi-Link System. | T-H2-OS, T-H3-DV/OS, T-H3J-DV/OS, T-H3S-DV/OS T-D2, T-M32, T-M50 |
| 941 | Abnormal exhaust temperature Watch out: this is an unsafe condition risking CO hazards. |
T-H2-OS, T-H3-DV/OS, T-H3J-DV/OS, T-H3S-DV/OS |
| 991 | Improper gas combustion. Abnormal combudstion. Watch out: this is an unsafe condition risking CO hazards. Check for blocked exhaust flue or under-sized exhaust flue. Check for debris clogging the gas burner or for a failed or blocked fan. |
T-H2-OS, T-H3-DV/OS, T-H3J-DV/OS, T-H3S-DV/OS T-D2, T-M32, T-M50 |
Watch out: some water heater defects represent dangerous conditions, risking fire, explosion, or carbon monoxide poisoning or scalding hazards. Work on these heaters must be by a qualifed service professional.
All units are self diagnostic for safety and convenience when trouble shooting.
Error codes may be displayed in different locations, The 3‐digit 7‐Seg LED displays error code, or the TM‐RE30 (if installed) displays the 3‐digit error code, or for Easy-Link System units, The 7‐Seg LED of the individual unit with the error in question displays the whole 3‐digit error code.
The TM‐RE30 (if installed) displays a 3‐digit number which signifies which unit has the error, and what the error code is.
If there is a problem with the installation or the unit, it will display a numerical error code on
the Remote Controller (if installed), on the 7‐Seg LED on the computer board (510 (T‐D2)), or
the flashing red LED (110 (T‐KJr2), 310 (T‐K4)) to communicate the source of the problem.
Consult the chart for the cause of each error code.
If no your water heater model is not listed in the right-hand column then the error code on this table row may not apply.
See the water heater manual or troubleshooting manual for your specific water heater model for expanded detail about the meaning and the corrective steps for each of these error codes.
Also see AO SMITH WATER HEATER AGE & MANUALS where A.O. Smith water heater error codes are given.
Also see A.O. Smith CONDENSING WATER HEATER TROUBLESHOOTING GUIDE [PDF], (2011) A.O. Smith Water Products Company 500 Tennessee Waltz Parkway Ashland City, TN 37015 Toll Free: 1‐877‐737‐2840
...
Below you will find questions and answers previously posted on this page at its page bottom reader comment box.
On 2019-06-23 by (mod) -
I've been surprised how quickly it's been necessary to clean some tankless water heaters. It's a good idea to flush it out make sure that the coil is not clogged and then reset the unit.
On 2019-06-23 by Barb
My Takagi has always worked great. Today it is in STANDBY mode. There is no hot water. It is 5 yrs old & I have not cleaned it every yr as instructed.
Should I do that first...and then reset it?
Thanks
On 2019-03-09 by Anonymous
Thank you
On 2019-03-08 by (mod) -
You can see #39 in the Takagi water heater error code table above
39 Air-Fuel Ratio Rod Failure
Sounds like a burner or combustion air adjustment issue
It's time for help from a Takagi-trained service technician on-site, for both function and for your safety.
On 2019-03-07 by Anonymous
Now I am getting error code 39 when the downstairs is tuned on while the upstairs was on and working.
On 2019-03-05 by (mod) -
Brad
Am I right that this is a variable flame capacity water heater? There may be an effect of flow rate demand on the heater that in turn controls flame height that in turn is not working properly.
For example with a Bosch variable flame water heater with which I've been experimenting across several models, with some models if the flow rate through the heater is insufficient the flame will go out.
Try a faster flow rate shower head in that downstairs shower and let me know if that fixes the trouble.
It's not literally pressure (though that's the word people commonly use) that is critical, it's water flow rate in gpm or lpm.
On 2019-03-05 by Brad
Thanks for the reply. If I turn the unit off and then on again, I can get the flame to stay lit. This seems to only be a problem when the downstairs shower is turned on. When the upstairs, or dishwasher are used, the flame stays lit.
Pressure issue with the water?
I have cleaned the filter and am now going to clean the rods.
On 2019-03-03 by (mod) -
Brad
As you saw in the Takagi water heater error codes in the table in this article, error 12 = a flame loss. That can be a problem with fuel, igniter, fuel valve, piping, burner adjustment, cleaning, combustion air supply etc.
Start with the troubleshooting advice in your Takagi manual,
also see GAS BURNER FLAME & NOISE DEFECTS https://inspectapedia.com/plumbing/Gas_Flame_Noise_Defects.php
keep me posted.
On 2019-03-03 by Brad
I get error code 12 on my TK-4 IN. I have cleaned the filter and it is still happening. Any thoughts?
On 2019-02-23 by (mod) -
Perhaps there is a scale clogging problem.
On 2019-02-23 by Marty Prevosto
My Takagi is inside the house when we go to use the shower an turn on the hot it rumbling an goes hot to cold hot to cold
...
Continue reading at WATER HEATER LIFE or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see these
TAKAGI WATER HEATER MANUALS, AGE, ERROR CODES at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Questions & answers or comments about how to find out the age of a heating appliance: water heater, heating boiler, heating furnace.
Search the InspectApedia website
Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.
In addition to any citations in the article above, a full list is available on request.