Relief Valve Leak FAQs#2FAQs on leaks at temperature / pressure relief valves, set #2.
This article series describes the causes of leaks, drips, or discharges from pressure relief valves, temperature/pressure relief valves, or TP valves found on heating boilers, water heaters, or the simpler pressure relief valves found on water pressure tanks.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?
These questions & answers about temperature/pressure relief valve leaks were posted originally
at RELIEF VALVE LEAKS - home page for this topic. Be sure to review the diagnosis, repair, and safety advice given there.
Also see our index to all water heater questions and answers at RELIEF VALVE DIAGNOSTIC FAQs
Watch out: a dripping or frequently spilling T&P valve is dangerous because those very leaks can eventually cause the valve to clog and then to fail to open when it should.
...
Tip: If the temperature/pressure relief valve is new, is the proper type for your heater, and if you think that the heater temperature and pressure are well below the opening temperature and pressure listed on the relief valve data tag, then take a look at these external causes of TPR valve leaking: thermal expansion leaks and water hammer leaks - detailed
THERMAL EXPANSION TPR VALVE LEAKS
and
New water heater new expansion tank and 2nd new relieve valve why is the valve still opening to release pressure? On 2016-10-24 by Anonymous
by (mod) - what to check first
Anon:
Check the starting water pressure to be sure it's not abnormally high - say over 60 or 70 psi.
Check that the heater temperature is not set abnormally high - safe is to 120F or less unless you also have an anti-scald valve or system installed.
Check that the correct type of pressure relief valve was installed: read the label on your relief valve.
The relief valve's opening pressure has to be correct for the type of heater: a heating boiler TPR valve opens at about 30 psi, a water heater TPR valve opens at about 150 psi, and a steam boiler relief valve opens at just about 5 psi.
Other causes of TPR leaks are described
by (mod) releif valve has been replaced was ok for couple months and now has started leaking again
Ron,
Over at RELIEF VALVE LEAKS we list the common causes of leaks at these safety devices.When a new valve that's probably intact is leaking I suspect over-pressure or water hammer.
then look further into this possible solution:
HOT WATER EXPANSION TANKS
and at this other cause of relief valve drips:
WATER HAMMER NOISE as if there is a banging sound when you close a hot water faucet that force could be triggering the TPR valve leaks.
Watch out: leaky pressure/temperature relief valves are a safety concern
I have problem of my apartment have 2 Ariston 40ltr water heater.b ut I got problem my only one water heater pressure relief valve water dripping.
my plumber change 2 times of pressure relief valve but still same problem when I on my water heater it's dropping after few minutes. How I solve this problem? On 2020-02-13 by Sallu
by (mod) - review the causes of TPR valve leaks
Sallu
Step through the diagnostics at RELIEF VALVE LEAK CAUSES
And let me know what you find.
Hi. I replaced the following.
Water heater.
Expansion vessel
and pressure release valve .
Yet water is still dripping from the pressure release valve. What can I do to stop it? On 2018-09-04 by Ian
by (mod) - other causes of relief valve spilling
Even with all new everything, a pressure/temperature relief valve may drip or release water if pressure or temperature are too high, or if there is an external problem such as water hammer.
I'm assuming (oops?) that you have not set the water heater to an abnormally high (boiling) water temperature. So
let's start by checking the building water pressure to see if it's abnormally high.
Help doing that is at WATER PRESSURE MEASUREMENT
The other thing you might check is for a water hammer problem.
So also check WATER HAMMER NOISE DIAGNOSE & CURE
Another possibiity is that your heating boiler expansion tank is waterlogged or has a failed internal bladder.
A similar problem occurs with domestic hot water heaters (geysers, calorifiers) if that heater uses a hot water expansion tank.
See our diagnosis and explanation
Then check the causes of leaky TP valves given at
Watch out this is an unsafe condition. The cause of the dripping TP valve needs to be found and fixed and the valve should probably be replaced too.
I just replaced my water heater (electric) and it is was very cold in the attic about 44 degrees.
Water fill was very cold as well. No leaks at fill up and run to get air out of the tank / lines.
Applied the electric and in a few minutes as the tank heated I got some leaks through the T&P valve.
I opened and closed the valve a couple of times. After about 30 to 45 minutes it no longer seems to be leaking.
Is this normal on a brand new water heater? (Dec 5, 2016) Scott
Reply:
Not normal, no, that is, as long as your building water pressure was at normal limits. Perhaps the valve was not properly seated. For safety I'd prefer to replace the valve as I'm not sure what it might do in the future.
But first see THERMAL EXPANSION TPR VALVE LEAKS
Great info here, but I have an ongoing problem.
On a fairly new electric hot water heater tank (2 years) I replaced the relief valve because it was leaking and occasionally discharging. However the new relief valve did not correct the problem, still leaks constantly.
So, I replaced both thermostats thinking one or the other was not shutting off the heating elements and it was over heating and discharging. Still, it drips out the relief line.
There is a new expansion tank on cold line.
I could replace heating elements but I do not think that is the problem.
After reading here it seems maybe it is a water pressure problem. But I would have thought the expansion tank would have solved that.
Any ideas? -
Richard Stafford On 2020-06-23
by (mod) - undersized expansion tank, water hammer, or one of these other causes
If water pressure is high the expansion tank may be too small,
Or
There may be another cause such as water hammer or wrong TPR valveStep through the diagnostics at RELIEF VALVE LEAK CAUSES
We have well water, we have very little water pressure.
We came home to a t&P valve violently discharging, called Rheem they advised to buy new valve and replace--gave us no instructions-- We just slapped a new one on turned the cold water back on and then immediately followed turning back on the hot water heater the new valve discharged a gushing stream.
Called Rheem again and they said oh no there are steps that must be followed, so we drained the hot water heater and started "Fresh" and followed the steps to a "T".
Now the T&P valve leaks horribly.
Is it possible that all that monkeying around the first time ruined a brand new valve? (Jan 10, 2015) Anonymous
Reply:
I'm not sure what might have happened to the valve - it could have been damaged or improperly installed.
But make a check of the system water pressure to see its level is abnormally high - if water pressure is above the TP valve pressure (or if you bought the wrong type of TP valve) that could be the trouble.
(don't confuse poor or slow flow with low pressure)Water hammer an also cause a TP valve to leak but that leakage is not usually continuous.
...
I have a pressure relief problem on my Burnham boiler. At first, we found a flooded floor and the plumber noticed a leaky air-vent valve.
I replaced that part and all was well for a week.
Today, I went downstairs and noticed water again; caused by the overflow from a bucket I have under the Pressure Relief Valve.
So, I looked at the boiler pressure and it reads about 18 PSI, which is fine. However, the boiler temperature was 188 degrees and headed higher. So, I shut off the Emergency switch.
I recently had the boiler serviced, the Relief Valve looks fine, so I am not sure what's causing the temperature build-up and what to do about it?
As it is I have to replace one-room of carpeting that initially got wet, I sure don't want to install new carpet and have this reoccur. Please advise. On 2018-02-16 by Vince
by (mod) - check heater temperature, then look for other causes
Vince
You can check the specifications on your temperature/pressure relief valve by reading its data tag. Typically you'll see that the valve will open at 30 psi or at temperatures above 200F. f
So at 188F and 18 PSI the valve should not be opening. Of course the gauges could be off but it'd be unusual for both temperature and pressure gauges to be so far off.
In this case I'd replace the TPR valve. The fact that you had a bucket under it could be a hint that it's been a chronic leaker. Such valves are unsafe.
A simple external visual inspection of the valve is not sufficient.
There are other causes of TPR leaks such as water hammer.See details at WATER HAMMER NOISE DIAGNOSE & CURE
If replacing the valve doesn't cure the problem let me know and we'll proceed from there.
See our catalog of all of the causes of TPR leaks
I have a 31-yeay oil boiler (tankless water heater), which had small water dripping from the pressure relief.
The pressure and temperature was 20 psi and 180 degree.
The boiler does not ignite frequently now because of the beginning of summer season. Water dripping from the pressure relief significantly increased when the boiler was tested to heat the house, and the pressure reading went up quickly to 30 psi.
The water released from the pressure relief contained a lot of yellow residue.
Greatly appreciate if you have any thoughts. (June 1, 2014) Frank 06/01/2014
Reply:
Diagnose dripping TP valves on a heating boiler
If the TP valve is leaking and the heating boiler temperature is BELOW the 200degF limit I suspect either overpressure in the boiler or a defective valve.
The fact that leaks increase when the boiler is heated up is consistent with either of those conditions.
Pressures close to or over 30 PSI will spill the valve.
If your boiler has a tankless coil the coil could be leaking water into the boiler raising its pressure.
With the boiler OFF and cooled down to room temperature, remove water to drop pressure to 12 psi (or slightly higher if your home is more than 3 floors tall).
Leave the boiler off and watch for a pressure increase - that'd indicate a leak into the boiler or a faulty water feed valve.
Diagnose dripping TPR valves on a water heater
Open a faucet anywhere in the building. If the dripping stops, most likely the cause is thermal expansion of hot water.
...
Tip: See THERMAL EXPANSION TPR VALVE LEAKS - why the water heater, cylinder, or calorifier relief valve leaks when heating water
and see HOT WATER EXPANSION TANKS for the solution to this problem.
After installing 100 ft of 3/4" Pex sub floor heating , replacing 24 ft of 3/4' copper base board.
I am experiencing frequent T&P valve reliefs. I have replace the the auto feed and the T&P valve, and purged all the air. Utilty water is high 90 psi. Do need to increase the size of the expansion tank. Or do ypu suspect a different problem? (Nov 28, 2014) Anonymous said:
Reply:
Anon
At 90 PSI incoming water pressure your heating boiler's pressure-reducer / water feeder valve may need replacement OR you may need to install two of them in series as is often done in high pressure locations.
Anonymous said: boiler expansion tank bladder blown during boiler refill at high pressure
Thanks Dan Joe. Your suggestion is something I need do. As it turns out the Expansion Tank bladder had failed, probably due to the 90 psi when refilling the system.
Reply:
Thanks for the feedback anon -that will help other readers. DF
A water logged expansion tank either on a heating boiler or on a domestic hot water supply system (HOT WATER EXPANSION TANKS) can indeed cause the heater's relief valve to drip or leak.
Helpful diagnosis and repair advice that applies both to expansion tanks and to water pressure tanks is found
at WATER TANK BLADDER BURST or LEAKY
...
...
Continue reading at RELIEF VALVE LEAKS - topic home, or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see these
RELIEF VALVE LEAK FAQs-2 at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Or see
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.
Search the InspectApedia website
Note: appearance of your Comment below may be delayed: if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.
Only one image can be added per comment but you can post as many comments, and therefore images, as you like.
You will not receive a notification when a response to your question has been posted.
Please bookmark this page to make it easy for you to check back for our response.
IF above you see "Comment Form is loading comments..." then COMMENT BOX - countable.ca / bawkbox.com IS NOT WORKING.
In any case you are welcome to send an email directly to us at InspectApedia.com at editor@inspectApedia.com
We'll reply to you directly. Please help us help you by noting, in your email, the URL of the InspectApedia page where you wanted to comment.
In addition to any citations in the article above, a full list is available on request.