Here we provide an actual data collection checklist for stair and railing inspection.
While no checklist is ever technically exhaustive, the list serves as an aid in learning how to inspect stairs, steps, landings, railings, balconies for safety and proper construction
InspectAPedia tolerates no conflicts of Interest. We have no relationship with advertisers, products, or services discussed at this website.
- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?
Our page top photo shows unsafe exterior stairs at a New York City home entrance. Below we provide a stair inspection checklist that outlines information to collect during a field investigation of the condition of an interior or exterior stairway for safety defects.
Having investigated cases of severe injury related to falls and railing collapses I (DJF) developed this field data collection checklist. We also include references to key documents on building codes and stair and railing safety.
Stair Inspection Notes and Observations |
||
Client: | . | |
RE Case: | . | |
Location: | . | |
Inspection Date & Conditions: | . | |
Inspector: | . | |
Item | Measurement | Comments |
Total Stairway Rise | . | . |
Total Stairway Run | . | . |
Landing top dimensions | . | . |
ht. vs. int. floor | . | . |
Entry door swing in/out | . | . |
Landing intermediate dims. | . | . |
Landing bottom dimensions | . | . |
Tread width = stair width | . | . |
Tread depth (horizontal) | . | . |
Individual Tread Conditions | ||
1 Tread, riser ht./condition | . | . |
2 Tread, riser ht./condition | . | . |
3 Tread, riser ht./condition | . | . |
4 Tread, riser ht./condition | . | . |
5 Tread, riser ht./condition | . | . |
6 Tread, riser ht./condition | . | . |
7 Tread, riser ht./condition | . | . |
8 Tread, riser ht./condition | . | . |
9 Tread, riser ht./condition | . | . |
10 Tread, riser ht./condition | . | . |
11 Tread, riser ht./condition | . | . |
12 Tread, riser ht./condition | . | . |
Tread nose (indic. variation) | . | . |
Tread level F-R (indic var) | . | . |
Tread level L-R (indic var) | . | . |
. | . | . |
Railing Conditions | ||
Railing height @ | . | . |
Railing height @ | . | . |
Railing height @ | . | . |
Railing security | . | . |
Railing cross section/Shape | . | |
Baluster Conditions | ||
Baluster spacing | . | . |
2nd Railing height @ | . | . |
2nd Railing height @ | . | . |
2nd Railing height @ | . | . |
Lighting Conditions | ||
Lighting/Switch at/watts/condition | . | . |
Other Observations: | ||
. |
Also see Building Safety Hazards Guide.
...
Below you will find questions and answers previously posted on this page at it's page bottom reader comment box.
On 2020-05-31 by Joy - Should I spend inspection money on a home when I can already see that there are problems
I went to look at homes and found a home I really liked.
However, the basement stairs were leaning. leaning to the right of the wall.
How hard is it to repair this problem. Does this mean that there is a foundation problem with the home?
Should I spend inspection money on a home when I can already see that there are problems with the home.
On 2020-05-31 - by (mod) - yes, a professional will always see more than you
Joy
I can't answer the question without seeing more of the building, but that's certainly a reasonable structural damage question to ask your home inspector prior to purchase.If the foundation wall is not cracked, bulged, leaning, Bode, Etc then more likely the problem is the stair structure itself that needs to be repaired or replaced.
On 2016-12-13 by Connor - Are commercial buildings required to have stairs that access all floors?
My grandfather has had claustrophobia since WWII and can't take elevators. Are commercial buildings required to have stairs that access all floors? I've taken him to several medical appointments. We climb the stairs only to find all of the floors have locked doors so we can't access the floor. Cheers and thanks.
On 2016-12-13 by (mod)
No. Many buildings will lock the stairwell side of doors that open to restricted areas.
However none of the building's doors that OPEN from a floor to the stairwell should ever be locked if that stairwell forms part of the building's emergency exit passage.
On 2016-01-05 by Dee - drywall split along stairs: is this a structural problem?
I have a large split in the drywall (vertical) where two stair sets are joined. stairs are 180 degrees apart. is this a sign of normal settling? or could it be more structural?
On 2016-01-05 - by (mod) -
Dee
To make a reliable assessment of structural movement an on-site expert is needed; it'd be betting your money and safety without enough information to guess from a one line e-text; there are quite a few on-site observations that go into deciding why a crack has appeared in a building - search InspectApedia.com for FOUNDATION CRACK DIAGNOSIS for some good examples.Also see
Goldstein, Matthew, Jessica Silver-Greenberg, "A New Spin on Funding Slip-and-Fall Lawsuits", The New York Times, 12 May 2018 p. b1-2
A federal indictment ... portrays a complex scheme, a sort of insurance fraud on steroids that lasted for five years and cost insurers and property owners $32 million. A group of five men orchestrated the fraud, recruiting poeple to stage so-called slip-and-fall accidents, and then organizing the legal and medical appointments that followed, the indictment says. Along the way, the group enlisted doctors, lawyers, and finance companies.
...
The indictment offers insight into the unregulated and opaque world of the litigation-finance business. Such finance firms ... typically bankroll defendants' alawsuits with large cash advances. The goal is to profit on the advances, some of which come with interest rates as high as 100 percent, from the proceeds of jury verdicts.
...
The primary litigation-finance firm involved in the scheme was Fast Trak Legal Funding ...
On 2015-07-21 by Ruth - how far out over the curb should a stair rail extend?
should a stairway with 2 steps have a railing to the edge of bottom step or should it extend out over curb
On 2015-07-21 - by (mod) -
The handrail extends at least to the nose of the bottom step, and for accessible (handicapped) stairways it needs to extend further horizontally as we discuss at accessible stairs and handrails.
I'm not sure of the details of your installation nor the problems that might arise with "over the curb" extension.
(May 22, 2014) Chris said:
Good evening,
What is the minimum tread depth with?
Thank you.
Reply:
Chris,
Please see STAIR TREAD DIMENSIONS
where we give full details
(July 23, 2014) Terrie said:
Hi I would like to install the new Cable System Stairway and baluster railing and I would like to know is it a safety hazard to have 5 wires that a toddler could possible step on to? Please advise
Reply:
IN my opinion, yes.
at CONTINUE READING - the links above - in the article series beginning at
you'll see photos of youngsters climbing horizontal cables in a public guardrailing. The climbing temptation is great.
(Sept 20, 2014) Anonymous said:
can first step riser very in heigth to second riser off concrete slab
Reply:
Not by much. +/- 0.375 inches - See the details at STAIR RISER SPECIFICATIONS
...
Continue reading at STAIRS, RAILINGS, LANDINGS, RAMPS - INSPECTIONS, CODES or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see these
CHECKLIST for STAIR INSPECTIONS at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.
Search the InspectApedia website
Note: appearance of your Comment below may be delayed: if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.
Only one image can be added per comment but you can post as many comments, and therefore images, as you like.
You will not receive a notification when a response to your question has been posted.
Please bookmark this page to make it easy for you to check back for our response.
IF above you see " Comment Form is loading comments..." then COMMENT BOX - countable.ca / bawkbox.com IS NOT WORKING.
In any case you are welcome to send an email directly to us at InspectApedia.com at editor@inspectApedia.com
We'll reply to you directly. Please help us help you by noting, in your email, the URL of the InspectApedia page where you wanted to comment.
In addition to any citations in the article above, a full list is available on request.
OSHA estimates that there are 24,882 injuries and as many as 36 fatalities per year due to falls from stairways and ladders used in construction. Nearly half of these injuries are serious enough to require time off the job--11,570 lost workday injuries and 13,312 non-lost workday injuries occur annually due to falls from stairways and ladders used in construction. These data demonstrate that work on and around ladders and stairways is hazardous. More importantly, they show that compliance with OSHA's requirements for the safe use of ladders and stairways could have prevented many of these injuries. - osha.gov/doc/outreachtraining/htmlfiles/stairlad.html