Flue Gas Spill Switch Installation & Wiring
Hookup procedures for flue gas spill switches to detect backdrafting at gas or oil fired heating equipment.
In this article series we explain the installation, function, & troubleshooting Flue Gas Spill Switches and we provide a Guide to inspecting Furnace or Boiler Flue Gas Spill Switches on gas fired equipment such as heating boilers, warm air furnaces, water heaters.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?
Watch out: thermal switches and flue spill detection switches are important safety devices that are intended to reduce the chances of fatal carbon monoxide poisoning in buildings where gas-fired heating equipment is installed.
If you are not trained to make a correct and safe installation of these devices hire a licensed plumber or heating equipment technician who is so qualified. Making a mistake could kill someone. Here is a typical warning from a boiler installation manual:
Failure to follow all instructions can result in flue gas spillage and carbon monoxide emissions, causing severe personal injury or death. - Williamson-Thermoflo GSA Installation Manual Part Number 550-110-738/0319
Watch out: Because most flue spillage sensors detect heat rather than the specific gases that might be emitted from the heating equipment the safety switch must be matched to the equipment.
Photo: I'm holding the wire connecting the flue spill detector (at the left end of the wire) to the water heater gas valve (not shown).
Field Controls, for example, offers such devices. The term usually used is "thermal switch" or "thermal switches for oil fired heating equipment".
These flue gas spillage devices sense heat, must be selected for the proper fuel and application (or else your system would be unsafe as it'd not be properly protected), and are sold in both manual reset and automatic reset spill switch sensor switch forms.
Flue gas spillage or thermal switches also vary by their response time. You may have trouble with a too-fast-acting switch if in normal operation there is a brief burst of heat from a barometric damper - as happens on some oil fired heating equipment.
Field Controls Thermal switch models include FTS-4, FTS-6, GSK250-M (for steam boilers), GSJ0160-M for draft-induced furnaces, and about eight other models. You'll see that it is essential to choose the proper thermals sensor switch.
Our reader asked:
Where do I tie in a spill switch for a gas hot water heater?
Somewhere on the gas valve? 2019/11/18 Anonymous
This Q&A were posted originally
at FLUE GAS SPILL SWITCH TRIPPING & RESET
Anon
Watch out: if you are not trained and qualified to work on gas heating equipment don't do it as you could cause a fire, explosion, or death.
Yes the flue gas spill switch mounts at the gas vent draft hood and on a water heater, its wires connect to a special connector installed at the gas valve. The installation kit will contain a connector that is installed between the existing themocouple end and its connection point on the gas valve.
Wires from the spill switch are then hooked up to terminals on that connector.
Below as a downloadble PDF are example details adapted from the Field Controls SSK-1 or SSK-2 thermal switch installation instructions.
Because water heaters are not operated by an external wall-mount thermostat sporting thermostat wires but instead are controlled by a thermostat built into the water heater body (with no external thermostat wires), to hook up a flue gas spill switch to a water heater a different approach is used.
On a water heater the thermocouple at the gas valve on the water heater is removed; then a special connector or "junction block adapter", also referred to as a "thermocouple circuit" or a "thermocouple adapter" (shown here) used with the spill switch installation kit, is installed at the thermocouple mount on the gas valve, the thermocouple is then connected to the connector, and the spill switch wires also are plugged into the same connector.
A bit above on this page is a sketch showing those details.
Just above is a photo of the Fields Control thermocouple "circut" or junction block adapter.
Watch out: you may not find this junction block adapter in the box with the spill switches you've purchased. It has to be ordered separately.
Some Flue Gas spill switches like the Field Controls switch SSK-shown below will remain OFF until manually reset.
Here is what Field says about installing this type of control
Kit form of GSK-3 or GSK-4 generally used on millivolt water heaters. Can also be used with 24 VAC gas furnaces or boilers.
Kit includes (2) GSK style Thermal Safety Switches, (1) 12-gauge Jumper Wire and (1) 6 ft. length 12-gauge lead wire. SSK-3 switches not supplied with switch enclosures. TCA-1 or TCA-2 Thermocouple Adapter required for 30 millivolt applications.
Before and after adding this safety control on existing appliances, an installation inspection in accordance with the National Fuel Gas Code 54, Z223.1 Appendix H should be performed and a combustion analysis is recommended to determine the operating condition of the appliance.
The actual connection of the flue gas spill switch wires can vary but a typical connection wires the switch in series with one of the thermostat wires that connect between the thermostat and terminals on the gas valve that in turn turns opens to provide fuel gas to the gas burner.
Also see FLUE GAS SPILL SWITCH SOURCES & MANUALS
...
Below you will find questions and answers previously posted on this page at its page bottom reader comment box.
The thermal couple adapter on the flue gas spill switch doesn’t fit my model. Is there another way to install a spill switch? The thermal couple adapter doesn’t fit my model. - 2020/04/29 Anthony
Illustration: a flue gas spill swithc installation kit distributed by Zoro, cited
at FLUE GAS SPILL SWITCH SOURCES & MANUALS
Thanks for a helpful question, Anthony. Apologies that I'm chicken to bet your life on a guessed-answer.
Let's start by identifying the brand and model of your gas fired heating appliance.
Then we can find the manufacturer's technical help support line and give them a call to get an authoritative answer.
FYI, yes, there are indeed add-on flue gas spillage safety switches, typically relying on wiring in to the electrical wires controlling the gas burner operation.
Click on any of the several Field Control flue gas safety switch installation guides given as downloadable PDF files at the end of the article above on this page.
Check with your manufacturer about approval.
Shown above next to your question is a typical flue gas installation switch kit.
...
Continue reading at FLUE GAS SPILL SWITCH SOURCES & MANUALS or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see these
FLUE GAS SWITCH INSTALLATION & WIRING at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Search the InspectApedia website
Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.
In addition to any citations in the article above, a full list is available on request.