Building Inspection, Diagnosis & Repair Info

IMC metal conduit in a New York home (C) Daniel FriedmanElectrical Conduit Pull Boxes

Electrical Conduit pull boxes provide access to successfully pull wires through metallic or non-metallic conduit & raceways.

This article describes the requirements for pull-boxes including sizing & spacing or distances between pull boxes & their locations. We define pull boxes, junction boxes, and terminal boxes and we explain the differences in how these electrical components are used.

This article series describes both metallic electrical conduit and plastic or non-metallic electrical conduit products, and answers basic questions about installing electrical conduit. Electrical conduit is metal or plastic rigid or flexible tubing used to route electrical wires in a building.

The page top photo showing a pull box used to route wires thorugh conduit from a main electrical panel up to a raceway (not shown) that crosses a building to connect in a second, remote electrical panel located in an attached garage.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?





ADVERTISEMENT





Electrical Conduit Pull-Box Requirements

Calbrite™ Brand stainless steel C Condulet at InspectApedia.com contact information for Calbrite is in the article where this image appearsA pull box is an electrical box placed at key locations in electrical conduit wiring systems in order to provide access in order to pull electrical wires through conduit during wiring installation.

Illustration: a small pull box or junction box used with EMT or electrical metallic tubing - conduit.

[Click to enlarge any image]

Is a junction box the same as a pull box?

Although the same physical electrical box might be used as either an electrical junction box or a pull-box, their uses are different:

Really? While technically a junction box only joins either wires or conduits (raceways), according to some sources that we reviewed, an electrical box might be used as as both a pull box and a splice box.

For example the Crouse-Hinds PTB or PTC pull box enclosures are designed to serve both purposes, allowing the initial pulling of electrical wires during installation and the future access to the wires for changes or additions to the circuits involved.

Pull Box Types

Pull boxes may be described by how the pulled-wires enter and exit the box.

Straight Pull Boxes are those in which the conduit carrying wires is attached to opposite sides of the box to permit a straight-pull of wires through the conduit. These boxes may be installed at intervals along a long straight wire pull to make pulling easier.

Angle Pull Boxes are those in which wires enter the box at a side at right-angles to the side through which they exit the box (angle pulls)

U-Pull Boxes are those in which the wires exit and enter the box through the same side (U-Pulls).

Pull Box Location

The pull box location depends on the number and location of bends in the conduit and in the wire and conduit sizes.

Pull boxes are placed where wires must be pulled through multiple bends in the conduit or raceway routing and where the number of bends exceeds four.

PVC pull box cited & discussed at InspectApedia.com

Illustration: a 6-inch PVC junction box produced by Carlon as listed by Home Depot in 2022, for use with Schedule 40 or Schedule 90 conduit. NEMA 6P and type 4/4X ratings and described in detail by citations found at the end of this article.

Pull Box Distances

In a straight run the distance between pull boxes is not limited by the electrical code. It may be limited by physical constraints in the building or even simply by the length of the electrician's fish-tape or pull tape - popular names ofr a pull wire inserted through conduit from a destination end and then used to connect and pull wires to that location from the source-end of the circuit.

In a conduit run that involves bends or changes in direction,

Pull Box Size

Electrical conduit pull boxes for wires that are No. 4AWG or greater are sized under U.S. NEC article 314.28 given in more-detail below.

The "conduit size" or diameter is interpreted to be the "trade size" or "metric designator" of the conduit, which may be slightly different than its actual physical dimension or diameter.

Watch Out:  Do not attempt to work on your electrical wiring, switches, or outlets unless you are properly trained and equipped to do so. Electrical components in a building can easily cause an electrical shock, burn, or even death.

...




ADVERTISEMENT





Reader Comments, Questions & Answers About The Article Above

Below you will find questions and answers previously posted on this page at its page bottom reader comment box.

Reader Q&A - also see RECOMMENDED ARTICLES & FAQs

what's the distance between pull boxes for straight conduit and where there are conduit bends?

What the Distance of Pull boxes in Straight conduiting and at how many bend Junction box Pull box recommended as per NEC NAFA. - Ak Kahn, 2022/05/23

This Q&A were posted originally

at ELECTRICAL CONDUIT, METALLIC

Moderator reply: permitted distance between pull boxes for electrical conduit

Thank you for a helpful question.

Bottom line:

The distance between electrical conduit pull boxes in a straight run is not limited by the electrical code.

The distance between electrical conduit pull boxes where there are bends depends on the location of the bends and *their* distances apart, since the NEC 300-13(a) says

“There shall be no more than the equivalent of four-quarter bends (360 total) between pull points.”

Details:

The distance between pull boxes will depend on the number of bends in the conduit between pull boxes (details below), conduit size and tpe, number of conductors & their size.

Key really is the number of bends; straight pulls are easy even over great length.

US NEC 300-13(a) - the maximum distance between pull boxes depends on the length of the conductors.

There shall be no more than the equivalent of four-quarter bends (360 total) between pull points.

The distance between electrical conduit raceway entries enclosing the same conductors must be at least six times the trade size (metric designator) of the larger raceway.

Elecctrical pull boxes for straight-pulls through conduit

2-inch raceways carrying the same conductors would have to be no less than (2 x 6 = 12) 12” apart.
3-inch raceways carrying the same conductors would have to be no less than (3 x 6 = 18) 18” apart.

Notice that these are minimum, not maximum distances. Long straight runs are not so difficult as would be runs incorporating bends.

Electrical conduit pull boxes where there are bends

It’s the US NEC reqiuerment that “there shall be no more than the equivalent of four quarter-bends (360 deg total) between pull points that governs the location and thus distance between those pull boxes.

Useful NEC sections for conduit pull boxes:

US NEC 300.14 - Boxes, conduit bodies, fittings & manholes, installation and use,
includes a descriptin of free conductors allowed within a conduit or box or device including pull boxes and junction boxes

US NEC 314 Electrical boxes, fill, sizing, etc.

US NEC 314 Part V describes Pull & Junction Boxes for systems greater than 600VAC

US NEC 34.15 Damp, Wet or Hazardous Locations

US NEC 314.16 Number of Conductors in Outlet, Device and Junction Boxes, and Conduit Bodies (18 - 6 AWG)

314.16(A) Box Volume Calculations

314.16(B) Box Fill Calculations

(The volume of the box calculated in part A must be equal or greater than the fill calculation given by part B)

US NEC 314.28 Pull and Junction Boxes and Conduit Bodies. Angle Pulls, U Pulls & Splices.

discusses the requirements for the size, dimensions, location and use of pull boxes. Specifically, see all of the requirements given in sections 314.28(A)(1)-(3). You’ll see requirements for dimensions of the boxes

— Electrical Code Excerpt for Electrical Conduit (Raceway) Pull Box Requirements -

(1) Straight Pulls

In straight pulls, the length of the box or conduit body shall not be less than eight times the metric designator (trade size) of the largest raceway.

(2) Angle or U Pulls, or Splices

Where splices or where angle or U pulls are made, the distance between each raceway entry inside the box or conduit body and the opposite wall of the box or conduit body shall not be less than six times the metric designator (trade size) of the largest raceway in a row.

This distance shall be increased for additional entries by the amount of the sum of the diameters of all other raceway entries in the same row on the same wall of the box. Each row shall be calculated individually, and the single row that provides the maximum distance shall be used.

Exception: Where a raceway or cable entry is in the wall of a box or conduit body opposite a removable cover, the distance from that wall to the cover shall be permitted to comply with the distance required for one wire per terminal in Table 312.6(A).

The distance between raceway entries enclosing the same conductor shall not be less than six times the metric designator (trade size) of the larger raceway.

When transposing cable size into raceway size in 314.28(A)(1) and (A)(2), the minimum metric designator (trade size) raceway required for the number and size of conductors in the cable shall be used.

(3) Smaller Dimensions

Listed boxes or listed conduit bodies of dimensions less than those required in 314.28(A)(1) and (A)(2) shall be permitted for installations of combinations of conductors that are less than the maximum conduit or tubing fill (of conduits or tubing being used) permitted by Table 1 of Chapter 9.

Listed conduit bodies of dimensions less than those required in 314.28(A)(2), and having a radius of the curve to the centerline not less than that indicated in Table 2 of Chapter 9 for one-shot and full-shoe benders, shall be permitted for installations of combinations of conductors permitted by Table 1 of Chapter 9. These conduit bodies shall be marked to show they have been specifically evaluated in accordance with this provision.

Where the permitted combinations of conductors for which the box or conduit body has been listed are less than the maximum conduit or tubing fill permitted by Table 1 of Chapter 9, the box or conduit body shall be permanently marked with the maximum number and maximum size of conductors permitted.

For other conductor sizes and combinations, the total cross-sectional area of the fill shall not exceed the crosssectional area of the conductors specified in the marking, based on the type of conductor identified as part of the product listing.

Research & Code Citations for Electrical Conduit Pull Boxes


...

Continue reading  at ELECTRICAL CONDUIT, NON-METALLIC or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.

Or see these

Recommended Articles

Suggested citation for this web page

ELECTRICAL CONDUIT PULL BOXES at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

Or see this

INDEX to RELATED ARTICLES: ARTICLE INDEX to ELECTRICAL INSPECTION & TESTING

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Ask a Question or Search InspectApedia

Share this article:

Search the InspectApedia website

Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.

Citations & References

In addition to any citations in the article above, a full list is available on request.



ADVERTISEMENT