FREE Encyclopedia of Building & Environmental Construction, Diagnosis, Maintenance & Repair The accuracy & trustworthiness of every article or Q&A is researched by human experts. See WHO ARE WE?
POST a QUESTION or COMMENT about how to buy, install, use & maintain a whole house ventilation system & ventilation system impacts on indoor air quality
Whole house ventilation systems:
This article explains how to design, buy, and use a whole house ventilation system to improve indoor air quality in homes.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
- Daniel Friedman, Editor/Publisher - See WHO ARE WE?
Whole House Ventilation Strategies for Improving Indoor Air Quality
There are a number of strategies for providing whole-house
ventilation, which vary in cost, complexity, and effectiveness.
All strategies, however, can be categorized as either exhaust-only, supply-only, or balanced.
The Venmar HRV heat recovery ventilator shown here is discussed in detail at VENTILATION, BALANCED[Click to enlarge any image]
Guide to Sizing House Ventilation Systems - How Many CFM of Vent Fan Capacity are Needed?
As detailed in Best Practices Guide to Residential Construction (Steve Bliss, J Wiley & Sons) :
ASHRAE Standard 62-1989 recommends a minimum ventilation
rate in houses of 15 cfm per person, or .35 air changes per hour (ACH), whichever is greater. Based on
the ACH method, a three-bedroom house of 1,500 sq ft
with 8 ft ceilings would require:
(1,500 x 8) x .85 x .35 / 60 = 60 cfm
Multiplying the volume by .85 accounts for partitions and
exterior wall thickness.
Using the per person method and assuming two people
in the master bedroom and one in each other bedroom,
the rate is also 60 cfm.
The revised ASHRAE standard 62.2, released in 2003,
uses the formula of 7.5 cfm per person (based on the number
of bedrooms plus one) plus an factor of .01 cfm for each square foot of house area. For example, based on
the new ASHRAE standard, the same three-bedroom,
1,500-square-foot house would require:
(7.5 x 4) / (1,500 x .01) = 45 cfm.
As these calculations show, a low ventilation rate is
adequate if run on a continuous basis. A higher continuous
rate would be advisable for a home with higher-than-average
moisture levels or pollutant sources such as smoking.
Intermittent ventilation can also work as long as the total
daily ventilation rate is equivalent, but is most effective
when the system is timed to operate when people are home
breathing air and generating pollutants.
A two-speed or
variable-speed fan provides flexibility, allowing the ventilation
rate to be raised when needed, for example when
painting a room or during a party. More important than
the precise number of cubic feet per minute, however, is
a well-designed system that is quiet, reliable, and low-
maintenance, ensuring it will actually be used.
[Click to enlarge any image]
TABLE 7-1 Whole House Ventilation Strategies
[Click to enlarge any image]
Installation Tips for Whole House Ventilation Systems
Whole-house ventilation systems should be installed by
people familiar with the equipment. Since they normally
operate at 100 to 200 cfm rather than the much larger fans
found in air handlers, they are less forgiving of errors.
Numerous field studies have found heat-recovery ventilators
performing poorly due to installation errors and poor
maintenance.
Guidelines for good performance of whole-house
ventilation systems
Illustration: a small-diameter high-velocity in-home ventilation system, excerpted from U.S. DOE Whole House Ventilation Basics cited below.
[Click to enlarge any image]
Size the whole house ventilation system correctly. Oversizing will increase
heating and cooling costs.
Choose quiet, efficient fans in the house ventilation equipment
Keep HVAC or ventilation duct runs as short and straight as possible.
Locate fresh air intakes away from pollution sources
such as cars, pesticides, and outlets from HVAC equipment
or exhaust fans.
Seal all ducts and insulate where required. Examples:
Insulate intake ducts that run though a hot attic or exhaust
ducts that pass through a cold, unheated space.
Integrate spot ventilation in bathrooms or provide
separately.
Use separate spot ventilation in kitchens due to grease.
Place supply registers high on walls and away from
beds, sofas, chairs, and other places likely to cause
occupant discomfort.
Keep controls as simple and automatic as possible.
Educate homeowners about the system and
maintenance requirements.
U.S. DOE, WHOLE HOUSE VENTILATION BASICS [PDF] U.S. Department of Energy, Office of
Energy Saver
Office of Energy Efficiency & Renewable Energy
Forrestal Building
1000 Independence Avenue, SW
Washington, DC 20585 USA, retrieved 2021/05/26, original source: https://www.energy.gov/energysaver/weatherize/ventilation/whole-house-ventilation - illustrated above.
Watch out: many indoor contaminants are simply too small to see, or are not particles at all but rather gases or chemicals.
- - Adapted, expanded, modified from the original with permission from Best Practices Guide to Residential Construction (Steve Bliss, J Wiley & Sons) .
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Ask a Question or Search InspectApedia
Questions & answers or comments about how to buy, install, use & maintain a whole house ventilation system & ventilation system impacts on indoor air quality.
Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.
Search the InspectApedia website
Note: appearance of your Comment below may be delayed:if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.
Only one image can be added per comment but you can post as many comments, and therefore images, as you like.
You will not receive a notification when a response to your question has been posted. Please bookmark this page to make it easy for you to check back for our response.
Our Comment Box is provided by Countable Web Productions countable.ca
In addition to any citations in the article above, a full list is available on request.
Steve Bliss's Building Advisor at buildingadvisor.com helps homeowners & contractors plan & complete successful building & remodeling projects: buying land, site work, building design, cost estimating, materials & components, & project management through complete construction. Email: info@buildingadvisor.com Steven Bliss served as editorial director and co-publisher of The Journal of Light Construction for 16 years and previously as building technology editor for Progressive Builder and Solar Age magazines. He worked in the building trades as a carpenter and design/build contractor for more than ten years and holds a masters degree from the Harvard Graduate School of Education.
Excerpts from his recent book, Best Practices Guide to Residential Construction, Wiley (November 18, 2005) ISBN-10: 0471648361, ISBN-13: 978-0471648369, appear throughout this website, with permission and courtesy of Wiley & Sons. Best Practices Guide is available from the publisher, J. Wiley & Sons, and also at Amazon.com
Our recommended books about building & mechanical systems design, inspection, problem diagnosis, and repair, and about indoor environment and IAQ testing, diagnosis, and cleanup are at the InspectAPedia Bookstore. Also see our Book Reviews - InspectAPedia.
Decks and Porches, the JLC Guide to, Best Practices for Outdoor Spaces, Steve Bliss (Editor), The Journal of Light Construction, Williston VT, 2010 ISBN 10: 1-928580-42-4, ISBN 13: 978-1-928580-42-3, available from Amazon.com
Historic Preservation Technology: A Primer, Robert A. Young, Wiley (March 21, 2008)
ISBN-10: 0471788368 ISBN-13: 978-0471788362
Air Leaks, Moisture Problems, Vapor Barriers & Ventilation in buildings - References, Products
Building Pathology, Deterioration, Diagnostics, and Intervention, Samuel Y. Harris, P.E., AIA, Esq., ISBN 0-471-33172-4, John Wiley & Sons, 2001 [General building science-DF] ISBN-10: 0471331724
ISBN-13: 978-0471331728
Building Pathology: Principles and Practice, David Watt, Wiley-Blackwell; 2 edition (March 7, 2008) ISBN-10: 1405161035 ISBN-13: 978-1405161039
In addition to citations & references found in this article, see the research citations given at the end of the related articles found at our suggested
Carson, Dunlop & Associates Ltd., 120 Carlton Street Suite 407, Toronto ON M5A 4K2. Tel: (416) 964-9415 1-800-268-7070 Email: info@carsondunlop.com. Alan Carson is a past president of ASHI, the American Society of Home Inspectors.
Carson Dunlop Associates provides extensive home inspection education and report writing material. In gratitude we provide links to tsome Carson Dunlop Associates products and services.