Exhaust Fan Ventilation System GuideHow to diagnose & fix exhaust fan problems: this article explains using exhaust fan ventilation systems to improve indoor air quality in homes.
We include exhaust vent system troubleshooting checks: Here we provide air handler unit or blower assembly troubleshooting by expanded annotated information from the US EPA [5]who provided suggestions for investigating the air handling unit during an indoor air quality investigation.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?
This article includes excerpts or adaptations from Best Practices Guide to Residential Construction (Steve Bliss, J Wiley & Sons) , by Steven Bliss, courtesy of Wiley & Sons. [Click to enlarge any image]
As detailed in Best Practices Guide to Residential Construction (Steve Bliss, J Wiley & Sons) :
Exhaust-only ventilation is the most common approach, due to its simplicity and use of familiar components such as bathroom fans. However, unless houses are built very tight, there is little control over where fresh air enters the building.
Also, building depressurization can be a problem, particularly with high-capacity fans. In addition to the increased potential for backdrafting, a depressurized house tends to draw more soil gases, including radon if it is present. And in hot, humid climates, moist air infiltrating through exterior walls can condense on interior finishes such as the back face of vinyl wallpaper that is chilled by air conditioning.
Below we discuss three exaust-only ventilation approaches, followed by a discussion of Supply Only Ventilation
and
then VENTILATION, BALANCED.
The simplest and least expensive central ventilation system consists of an automatic timer wired to one centrally located bathroom or laundry fan so it cycles on and off for a portion of every hour or for the 8 to 12 hours per day when most people are home, typically mornings and evenings.
See the figure at left (click the image for details) about a single port exhaust house ventilation system.
The simplest ventilation system uses a single, centrally located exhaust fan that runs on a timer or continuously at a low speed. The fan may also serve as a bathroom or laundry fan, but a dedicated fan is optimal.
Passive air inlets are sometimes installed but will only work properly in very tight homes.
Illustration Source: Recommended Ventilation Strategies for Energy-Efficient Production Homes, 1998, by Judy A. Roberson, et al., Lawrence Berkeley National Laboratory, appearing in the text cited above.
Exhaust fan control switch: Since the house ventilation exhaust fan is doing double duty as a bath or laundry fan, it must have a manual override switch for intermittent use. In larger homes, two fans at separate locations can be used. Another upgrade is to use a dedicated fan in a central location, such as a hallway ceiling, which will provide better distribution of both exhaust and supply air.
Exhaust fan noise: For the house ventilation system to work well, it is important to use a quiet exhaust fan of one sone or less and choose a central location. Also, the door to the bathroom with the exhaust fan must be undercut by 3/4 to 1inch, along with doors to all 4 bedrooms and other rooms that require ventilation. An alternative is to connect the rooms with through-the-wall transfer grilles.
The biggest drawback to exhaust-only ventilation is that there is little control over distribution of the incoming air. Makeup air will come via the path of least resistance. In a leaky house, this might be a window or drop ceiling in the bathroom with the exhaust fan, leaving the rest of the house un served by the ventilation system. For this reason, single-port exhaust-only ventilation works well only in relatively small, tight houses.
This type of system uses a more powerful exhaust fan that is remotely mounted, typically in the attic or basement. See the figure at left for details of a multi-port whole house exhaust fan vent system).
A multiport exhaust system improves air distribution by picking up air from bathrooms and main living areas. These are often used in conjunction with passive air inlets.
Exhaust-only systems are best used in homes with electric heating or sealed-combustion appliances where backdrafting is not a concern.
Illustration Source: Recommended Ventilation Strategies for Energy-Efficient Production Homes, 1998, by Judy A. Roberson, et al., Lawrence Berkeley National Laboratory, appearing in the text cited above.
The multiport house exhaust fan system is ducted to exhaust grilles in bathrooms, laundries, and other wet areas, and sometimes to a centrally located pickup point in the main living space. A room with no outside walls would also benefit from a pickup point.
Systems typically run on a low background speed with timer switches in bathrooms for higher-powered spot ventilation. If installed correctly, these systems are very quiet and provide good distribution of ventilation.
Multiport exhaust systems may incorporate passive air inlets (see description above) that install either in windows or through the wall, providing some control over supply air. The inlets, typically three or four for a small house, go in bedrooms, main living areas, and other occupied rooms, such as dens or home offices. Inlets should be placed high on the wall away from beds, chairs, or other places where drafts might cause discomfort. Placement near a window is preferred.
Because these systems use more powerful fans that depressurize the house, they should not be used in houses with fireplaces or atmospherically vented combustion appliances. They are also not recommended in hot climates, since hot, moist exterior air may be drawn into walls and condense behind interior surfaces chilled from air conditioning.
Packaged multiport house exhaust venting systems are available from American Aldes, Fantech, and a few other few manufacturers (see Resources, page 297 in Best Practices Guide to Residential Construction (Steve Bliss, J Wiley & Sons) )
This variation on exhaust-only ventilation passes the exhaust air through a heat-pump water heater, reclaiming heat from the outgoing air stream. Some systems can be reversed in summer, functioning as a supply ventilation system while cooling and dehumidifying the incoming air. A packaged heat-pump ventilating system is available from Therma-Stor.
-- Adapted with permission from Best Practices Guide to Residential Construction (Steve Bliss, J Wiley & Sons) .
...
Below you will find questions and answers previously posted on this page at its page bottom reader comment box.
(June 3, 2011) bobby said:
Can u connect a kitchen exhaust fan pipe to a vent pipe in the attic to exhaust out?
Kitchen exhaust vent routing:
Sure a kitchen vent fan can be routed via metal ductwork up through a building attic and out through a roof surface or out through a soffit. Of course the vent and routing need to be fire-safe, air tight (we don't want to blow grease into the attic nor feed a fire), and accessible for cleaning.
If you were asking if a kitchen exhaust fan can be connected to a plumbing vent pipe, the answer is no.
(Aug 30, 2011) Ed said:
I just installed a new range hood venting out to the roof. Problem is it is on an inside wall. Vibration noise comes through the wall into the other room, kitchen noise is normal for the range hood. Anything I can place behind the hood to lessen the vibration noise coming into the living room?
Ed, you can use rubber or foam as a vibration dampener.
But
Watch out: for fire hazards: you will want to review the range hood and duct installation instructions to be sure that you are respecting any necessary fire safety clearances. You may be able to reduce those clearances by using fire proof materials or even fire-rated drywall.
...
Continue reading at VENTILATION, SUPPLY-ONLY or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see these
VENTILATION, EXHAUST ONLY at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Search the InspectApedia website
Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.
In addition to any citations in the article above, a full list is available on request.