Measure water flow rate: how to measure water quantity delivered per minute at building plumbing systems.
How to measure the water flow rate in gallons or liters per minute at building faucets & fixtures. Plumbing fixture flow rate data. Water flow rate vs pipe diameter & pressure. This article describes procedures for measuring the flow rate in gallons per minute or liters per minute at a building faucet or plumbing fixture.
We explain what fixture flow rate means and we warn that measuring water flow in or at a building may give quite misleading data about the condition of the building water supply whether it's from a private well or from a municipal water main.
Our page top photo shows typical flow rate at a kitchen faucet - around 3 gpm.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
Above: a digital flow meter from Savant.
[Click to enlarge any image]
One can purchase flow meters like the Savant digital flow meter above and that connect to various plumbing fixtures to make water usage measurements,
and there are "flow meters" sold to home inspectors that pretend to make such a measurement at a sink tap, but remember that we are measuring the flow rate at the particular fixture - that number that does not describe the water flow rate capability of the water supply system nor the capacity of water that could be delivered to the building.
Our photo shows water running into a five-gallon plastic bucket. If this is the only fixture running water in the building we can time the number of seconds or minutes needed to fill the bucket.
For example, if the time required to fill the five gallon bucket is one minute, then the water flow rate at this plumbing fixture is 5-gallons per minute or 5 gpm.
Watch out: measuring "flow rate" at any faucet or fixture served by a well pump system will be inaccurate and will reflect pump capacity, piping restrictions, fixture restrictions, and even actual well flow rate variations where pump protection tailpieces or similar devices are installed. Measuring flow rate at a fixture does not measure the well's true flue rate.
The measurement of water flow rate at a particular plumbing fixture does not accurately measure the true water flow rate of the plumbing system because:
On a pump and well system when we turned on water at just the kitchen sink (DYNAMIC WATER PRESSURE) the flow rate dropped slowly until the pump turned on. Then the water pressure rose slowly until the pump turned off. Water pressure varied between 38 psi (pump off) and 25 psi (pump on).
When we turned on water at a bath tub faucet (photo just above) water pressure dropped to about 28 psi and stayed there as the well pump ran continuously, delivering water to the building at that rate. Here is a photo of our PRESSURE GAUGE reading 28 psi [image]
Also see WATER PRESSURE REDUCER / REGULATOR for a discussion of how we reduce building water pressure to a safe level and how we assure uniform building water pressure and flow using a pressure reducing valve or pressure regulator.
Readers whose building is served by a private pump and well system should
see WATER PUMP PRESSURE CONTROL SWITCH.
If we actually measure the flow rate at various building fixtures and faucets we will see water flow, measured in gallons per minute or liters per minute in these ranges:
Typical Water Flow Rates in Residential Properties |
||
Plumbing fixture or measurement location | Water Flow Rate in GPM / LPM | Comments / notes |
Bath tub faucet with no flow restrictor installed | 3-5 gpm | [1] |
Bathroom sink faucet | 1-3 gpm | [1] |
Kitchen sink faucet | 2-4- gpm | [1] |
Outdoor hose bib | 3-6 gpm | [1] |
Shower head, no flow restrictor | 2-6 gpm | [1] |
Shower head with flow restriction device installed | 1.25 - 3.5 gpm | [1], average 2 gpm. |
Shower heads prior to 1980 | 5 gpm (19 lpm) | |
Shower heads, flow restrictors ca 1985 | 3.5 gpm | |
Shower heads, flow restrictors, ca 1989 | 3.0 gpm | |
Shower heads, flow restrictors, 1992 | 2.5 gpm (9.5 lpm) | US National Energy Policy Act 1992, requirement waived in 2010 |
Shower head with high flow restriction device | 1.8 gpm | |
Water pressure tank drain | 3-6 gpm | [1] |
[1] Typical field measurements by home inspectors
Typical incoming water pressure at residential properties ranges between 20 psi and 70 psi. At properties served by a private pump and well system the actual flow rate will vary continuously between the pump's cut-in rate and cut-out rate. All flow rates are also affected by pipe diameter, length, restrictions, and other factors including water turbulence and building height.
Aerating shower heads restrict water flow rate by adding air mixed in with flowing water to increase perceived water volume.
Atomizing shower heads restrict water flow rate by water turbulence to create very fine high velocity water droplets.
Shower head flow restrictors in simplest form consist of a disc insert with a small center hole to meter water flow.
Some non-restrictive and non-compliant shower heads may permit water flow rates as much as 10 gpm (38 lpm).
Below we show how to CALCULATE WATER FLOW RATES for PIPE DIAMETER, LENGTH, PRESSURE
But for a simple quick estimate of the nominal water flow rate range based on water pipe diameter, the table below gives nominal and maximum flows. Where there are two or more entries on a line in the table those data are from different sources. You'lls ee that there is a lot of variability in estimates of these pipe flow rates, as we explain below the table.
Nominal & Peak Water Pipe Flow Rates |
||
Pipe Diameter | Flow Rate in GPM | |
Nominal | Peak | |
1/2" | 14 2 | 21 2 |
3/4" | 23 2 | 36 2 |
1" | 16, 37 2 | 30 |
1 1/4" | 30, 62 2 | 35 |
1 1/2" | 40 | 70 |
2" | 65 | 120 |
2 1/2" | 80 | 170 |
3" | 120 | 270 |
4" | 250 | 500 |
6" | 500 | 1100 |
8" | 1000 | 2000 |
10" | 1500 | 3000 |
As a crude and very general approximation, you can guess at the theoretival flow rate by either of two calculations:
Nominal water pipe flow rate: Diameter2 x 20
Velocity of water inside a pipe V = 0.408 x (Q / D2)
Where to perform the calculation you need to know any two of the following three parameters
V = Velocity of water in a pipe given in feet per second
Q = Flow rate of water inside the pipe in gpm
D = Pipe inside diameter in inches
There are numerous online calculators that permit you to calcculate the volume or mass flow rate and velocity based on pipe diameters, such as
Pressure Loss Ploss = 4.53 x L x [(Q/C)1.852 / D4.857 ]
Where
Ploss = loss due to friction, expressed in psi
L = Length of the pipe in feet
Q = Water flow rate inside the pipe in gpm
C = Pipe Coefficient ( a friction loss figure) given as
C PVC = 150
C Alumin w/Couplers = 120
C Galvanized Steel or Asbestos-Cement = 140
C Cast Iron or Old Steel = 100
D = Inside Diameter of the pipe in inches
(Mar 15, 2013) Jim Mault said:
Hi, we have a 6" water line with a static pressure of 90 psi. We want to put in a 6" stand pipe for truck filling at 1500gpm & 20psi. will that work?
Whew!. OK so it depends ... that "static" pressure of 90 psi is not going to give us a true answer to the flow rate in gpm you'll be seeing, since we don't know the effects of line length, friction losses, and number of bends, valves, or obstructions in your water line.
[Click to enlarge any image]
Really this is a hydraulics question. The true figures for water movement through piping are interesting and complex. For example, the velocity of water moving through piping (measured in feet per second or fps) is not uniform across the diameter of the pipe.
Water moves fastest in the middle and slows down at the edges of the cylinder or pipe walls - which makes sense if we think the walls impart friction losses on the water.
OK so we'll skip that. Here are some basics:
The cool chart at left relating water flow rate in GPM to pressure in psi makes some assumptions stated in the table's note.
This data is from engineering work prepared by the University of Florida, Indian River Research & Education Facility. - Dr. Brian Boman, "Chapter 21, Hydraulics", retrieved 3/3/2014, original source: http://irrec.ifas.ufl.edu/citrusbmp/ Water%20and%20FL%20Citrus/21%20Chap21.pdf
The second chart shown at left relates pressure loss to length for 100 feet of hose of various diameters up to greater than the 6-inch you asked about.
This data is from Dultmeier Sales also cited atReferences or Citations .
Click the chart to enlarge it for a more readable copy and you'll see that a six-inch diameter "pipe" (we don't know the material of your pipe) at a flow rate of 1500 gpm has a pressure loss of 4 psi per 100 feet.
From there and considering I've got no other data about your system, you are on your own to calculate the approximate flow rate loss for your system and thus the net flow rate.
You could ask Dultmeier or Dr. Boman for an accurate detail but I'm reluctant to bother an educator with these individual questions. Extrapolate from the table or try some basic ballpark calculations, or just give your local hydraulics engineer a call. Boman lays out the data and basic equation as follows:
The equation of continuity states that flow rate can be calculated from the multiple of the velocity times the cross-sectional area of flow.
The volume flow rate Q, given by the equation below, is the volume of liquid that can pass through the cross-sectional area of a pipe over a given time interval.
The volume flow rate equation relates the cross-sectional area of the pipe (area of a circle of a given diameter if the pipe is round) and the time over which the flow occurs expressed usually as a velocity in feet per second.
Flow Rate Q = A x V or V = Q/A
or
Flow Rate Q = Volume / Time
where
Q = A x V for 1 meter per second through a 1-meter pipe
Shelly Weinberg, one of the greatest teaches I [DF] ever met, teaching at IBM's System Research Institute, was conducting a course in queuing theory. To demonstrate a service time optimization algorithm that looked daunting, Shelly asked us to pick any number and he would demonstrate how easy the calculation was.
The class sat mute, frozen.
"OK" Shelly said, "We'll pick ONE. ONE's a good number, right?"
In honor of Shelly Weinberg, let's set everything in the volume flow rate equation to 1 and see what happens.
A = 1 square meter cross sectional area of pipe
V = 1 meter per second flow rate
V = A x V or 1 x 1 = M3 / second
The flow of a fluid traveling at an average velocity of a 1 meter per second through a pipe with a 1 square meter cross-sectional area is 1 cubic meter per second - volumetric flow rate before considering fluid density.
Q = A x V for 1 foot per second through a 1-inch diameter pipe
A = π x D2/4
A = 3.1416 x 1 / 4
A = 3.1416
V = 1 ft. per second
Q = 3.1416 x 1
Q = 3.14 = ft3 / second or 3.14 cubic feet per second of volume flow rate
For building water supply systems and many other applications the above flow rate calculation is sufficient, but it is not accurate for all types of fluids of various densities.
If we need to add consideration of fluid density on flow rates, Omega (cited below) explains:
W = rho x Q
where
The flow rate will be 1 kilogram per second when 1 cubic meter per second of a fluid with a density of 1 kilogram per cubic meter is flowing.
As we've reported elsewhere under improving water flow in buildings or "perceived water pressure", doubling the pipe diameter increases the liquid carrying capacity of the pipe by a factor of 4.
FYI, friction losses for a 100 ft. length of 6" diameter PVC pipe are figured at 0.30 psi / 100 ft. of pipe. The friction loss data is different for different pipe materials, and is IMO always wrong for in-use systems where contaminants or usage have changed the surface properties of the piping to increase (roughing or wear or mineral deposits) or decrease (algae) friction losses.
Pressure Versus Flow is described eloquently by Boman. As I've struggled for years to explain this and to help people understand that what they call "water pressure" experienced at the kitchen sink or bath shower is better understood as flow rate, I'm quoting him here:
As water moves through any pipe, pressure is lost because of turbulence created by the moving water. The amount of pressure lost in a horizontal pipe is related to the velocity of the water, the inside diameter of the pipe, and the length of pipe through which the water flows. When velocity increases, the pressure loss increases.
For example, in a 1-inch Sch 40 PVC pipe with an 8-gpm flow rate, the velocity will be 2.97 fps with a pressure loss of 1.59 psi per 100 ft.
When the flow rate is increased to 18 gpm, the velocity will be 6.67 fps, and the pressure loss will increase to 7.12 psi per 100 ft of pipe.
Increasing the pressure in the system increases the flow rate. In Fig. 21-3, the flow rate in a 2-inch pipe increases by 100 gpm when the pressure is in- creased from 20 psi to 50 psi. Using a smaller pipe size does not increase the flow.
Note that the smaller pipe sizes have considerably less flow at any given pressure. Since decreasing the pipe size does not increase the pressure at the source, the result of decreased size is reduced flow.
Using a smaller pipe size does not increase pressure. In contrast, it will result in lower pressure because there will be greater pressure loss in the lines. In Fig. 21-3, a flow of 20 gpm would require about 9 psi pressure in a 1-inch pipe. In order to maintain a 20-gpm flow in a 1/2-inch pipe, over 50 psi would be required at the source. Smaller pipes result in greater pressure loss, not higher pressure. - Op. Cit.
Measurements of actual flow rate at a fixture (explained at MEASURE ACTUAL FLOW RATE) will not, without additional measurements, reflect variations due to changes in the source pressure such as the effects of a well pump and pressure tank or temporal variations in the water pressure delivered from a municipal source or variations in the behaviour of a pressure regulator.
If it takes 5 minutes to fill a 5 gallon joint compound bucket (that's what we used to use) at the bath tub, then we're seeing a water flow rate of one gallon per minute.
As we calculated at SUMP PUMPS, using an 18-inch diameter joint compound bucket (or sump pit of that size), one inch in the bucket equals 1.1 gallons of water. Therefore,
If our 5-gallon 18" diameter bucket is filled up 10 inches in one minute of running water, that gave us about 10 gallons (actually 11 gallons) of water "per minute" at that plumbing fixture.
What's wrong with measuring well flow rate in the building at the bath tub using a bucket and a stopwatch?
Watch out: This bucket in the house well flow test assumes that the water flow rate at the plumbing fixture somehow reflects the water in-flow into the well too. This is a big mistake. Those figures could be totally different.
For example we could have a well with a horrible in-flow rate of .5 gpm but a huge water reservoir tank or a huge static head in the well itself.
The well or water flow rate we can measure at or inside of a building reflects the conditions of the pump, pressure tank, building piping, valves, and fixture, not the actual well flow rate of water from the ground into the well.
Nevertheless, an at-building water "flow test" is a practical or functional test that might tell you something important. At countless building inspections we ran water in the building, pulling perhaps 200 gallons or so out during a septic loading and dye test.
And at countless inspections we ran out of water, discovering that the well and water supply system had a poor well flow rate combined with a small static head in the wall and a small in-building water tank. But when you see a poor water flow in the building, you have found a problem but you have not diagnosed the problem.
Omega, a provider of accurate flow metering equipment adds these technical details about measuring water flow:
The fluid and its given and its pressure, temperature, allowable pressure drop, density (or specific gravity), conductivity, viscosity (Newtonian or not?) and vapor pressure at maximum operating temperature are listed, together with an indication of how these properties might vary or interact.
... Expected minimum and maximum pressure and temperature values should be given in addition to the normal operating values when selecting flow meters....
Concerning the piping and the area where the flowmeters are to be located, consider:
For the piping, its direction (avoid downward flow in liquid applications), size, material, schedule, flange-pressure rating, accessibility, up or downstream turns, valves, regulators, and available straight-pipe run lengths.
The specifying engineer must know if vibration or magnetic fields are present or possible in the area, if electric or pneumatic power is available, if the area is classified for explosion hazards, or if there are other special requirements such as compliance with sanitary or clean-in-place (CIP) regulations. - Omega, retrieved 11 Aug 2015, original source: http://www.omega.com/prodinfo/flowmeters.html
7/25/14 kjsuryawanshi@bajajauto.co.in said:
We are looking some sort of 'Auto valve/Flow meter' which will allow us to restrict the supply of water to each residential flat to a specified limit e.g. 200-300 liters per day. After supply of specified limit of water, valve should automatically close & stop the further flow of water.
KJ
It is easy to measure the volume of water delivered to a specific residential flat provided that each flat receives all of its water from a single delivery pipe: install a water meter at each of those points. If however building hot water is provided from a central source though a separate piping network you may need two water meters to measure both hot and cold water use.
It is also easy to restrict water flow rate through piping using controls, valves, and low-flow plumbing fixtures.
But to restrict water usage to a specific quantity in cubic feet, gallons or liters is another matter. You'd need to combine a water metering device with an automatic shutoff valve. Or for a less costly approach you can install timers to control water supply valves, opening and closing the valves only during certain intervals - something that few of your residents will appreciate.
In our opinion best, is to control water usage by metering and charging individual water users by installing sub-meters. This approach encourages voluntary water conservation.
I suggest that before going to that considerable expense you invest in
Take a look at the Ista line of process and flow controllers as well as those made by other manufacturers listed below. Some of these flow meter producers such as Omega include flow control devices. See
BTU MONITORS & HEATING COST APPORTIONMENT for some examples.
The list of brands of flow metering equipment is long as you can see. Here are more flow metering manufacturers you can consult:
Aalborg, Alicat Scientific, AquaMetrix, AW Gear Meters, Badger Meter, Blancett, Dwyer Instruments, Dynasonics, Flocat, Flo-tech, Flowline, Fox Thermal Instruments, Fuji Electric, GE Panametrics, GE Rheonik, Gems Sensors & Controls, General Tools, Georg Fischer / GF Signet, GPI, Greyline Instruments, Hedland, KEP, King Instrument, Kobold, Krohne, Lake Monitors, Mace, Macnaught, Rosemount, Seametrics, Sondar, Teksco, Universal Flow Monitors, W.E. Anderson, Yokogawa
Watch out: Measurements like the
are all useful, but taken by themselves some of these numbers can give a false reading about the basic question of how much water is in the well?
Even calculations of theoretical flow rate through a pipe of given diameter, length, pressure, and bends
(explained at CALCULATE WATER FLOW RATES for PIPE DIAMETER, LENGTH, PRESSURE)
will not give the actual flow rate that will be experienced in most real-world situations where other details that affect flow rate have not been considered such as the effects of height, flow restricting fixtures, variations in the actual water source pressure, unidentified restrictions in piping such as mineral deposits or rust, etc.
Before assuming that a water pressure, flow, or quantity problem is due to the well itself,
see WATER PUMP REPAIR GUIDE for an example of diagnosis of the cause of loss of water pressure, loss of water supply, and analyzes the actual repair cost.
On 2020-10-07 - by (mod) -
James
Yes we've had this question before. This is a fluid mechanics problem referred to as the open pipe flow rate question.
Our answer came from a reliable source, the engineering stack exchange at
https://engineering.stackexchange.com/questions/27036/open-pipe-and-relation-between-pressure-and-flow-rate
There are two approaches, depending on whether or not you're considering the length of pipe through which water is flowing;
If you know the length L then you apply Poiseuille's Law,
Poiseuille's Law,
𝐹𝑙𝑜𝑤=π⋅𝑟4⋅(𝑃−𝑃𝑜)8⋅η⋅𝐿𝑐𝑚3/𝑠
Assuming you have a Pipe with the area 𝐴𝑐𝑚2
𝐹𝑙𝑜𝑤=𝐴𝑟2⋅(𝑃−𝑃𝑜)8⋅η⋅𝐿𝑐𝑚3/𝑠
-P = pressure at the entrance, Bar
-P0 = atmosphere pressure, Bar
-eta = viscosity at dyne second/cm2 for water at 20c it is 0.01
-L = length cm.
but if you ignore length you apply the Bernoulli equation 𝑝+𝜌∗(𝑐2/2)+𝜌∗𝑔∗𝑧=𝑐𝑜𝑛𝑠𝑡𝑎𝑛𝑡
PS: Good luck on your test.
On 2020-10-07 by James
Anyone know how to solve this problem?
A water flow test was done at Seneca College on July 31, 2017. The static pressure was
measured with no water flowing and was observed to be 75 pounds per square inch (psi). The
2.5" projected outlet was opened and water was allowed to flow at full capacity on the second
hydrant. The pitot reading was 50 psi. While the water was flowing, the flow pressure from the
first hydrant was observed to be 65 psi.
How much water was flowing from the second hydrant? Graph your answer in the space
provided.
On 2019-03-11 - by (mod) -
Chrissy
The pressure exerted by water when measured at the bottom of a column of water is not dependent on the diameter of a column only the height of the column.
In the ARTICLE INDEX found above in the article titled at WATER PRESSURE MEASUREMENT
We
explain how to calculate the pressure at the bottom of a column of water of Any Given height. Since you probably don't want to go look in the way that I've described you can also jump directly to this link
https://inspectapedia.com/water/Water_Pressure_Measure.php#Height
On 2019-03-11 by Chrissy
What would be the water pressure from a 1/2 inch opening at the bottom of a tank 5 feet in diameter and 10 feet high when full?
On 2018-07-17 - by (mod) -
Matt
You ask a perfectly good question, a great one, but one that is in my opinion very difficult to answer, because of the number of variables and the fact that no actual home will precisely fit any generic formula or answer.
The theoretical answer is given in the article above from which I will excerpt:
The equation of continuity states that flow rate can be calculated from the multiple of the velocity times the cross-sectional area of flow.
Q = A x V or V = Q/A
where
Q = flow rate in ft3 / second
A = cross sectional area flow in sq. ft. of the pipe
(A = π x D2/4 and of course pi or π = 3.1416)
V = velocity in ft/sec - for systems where V varies use the average fluid velocity in the pipe
The flow of a fluid traveling at an average velocity of a 1 meter per second through a pipe with a 1 square meter cross-sectional area is 1 cubic meter per second - volumetric flow rate before considering fluid density. .
For building water supply systems and many other applications the above flow rate calculation is sufficient, but it is not accurate for all types of fluids of various densities.
But for an actual home there are practical considerations that argue that the theoretical answer is likely to be wrong.
Even starting at a water pressure regulator, that device will pass more water volume (at the same pressure) as more faucets are opened in your home.
If we had just a single open pipe pouring water into a home, say at a bath tub, we could calculate the flow rate using an engineering approach that considers pressure and pipe diameter, but that's not the case in a normal home: you have many pipes with elbows, lengths variations in diameter, and constrictions at fixtures. Even the constrictions are not fixed over time
In addition, the pressure of water delivery from the municipal supply - if it is a municipal supply in your case (you don't say) - in many communities varies from hour to hour and day to day.
If your water supply is from a private pump and well system, the delivery pressure is not fixed, by cycles from a low CUT IN pressure to a higher CUT OUT pressure, and worse, the cycle time will vary widely depending on how many fixtures are being run simultaneously, unless and until you are running so much water that the pump simply runs continuously.
In that case you've reached the delivery limit for the private pump and well.
So what's to be done to guesstimate how much water could possibly be delivered:
You could calculate the potential flow rate at your entering water main at your building by assuming a fixed pressure and diameter and by removing the pipes at the incoming main, say just past the shutoff valve. Then you'd open the valve and measure the pipe diameter and the dimensions of the arc of the stream of water. There are engineering procedures to translate that arc and the other measurements into a fair estimate of flow rate.
Or you could read your water meter over some period of time to see your actual, not your theoretical maximum water usage rate.
Or you could run water at every fixture in your home at once, emptying the flow into a measured container - say a 5 gallon bucket - and time the minutes to fill each bucket. Those flow rates would be additive and would guess at what your house flow rate sum could be for the fixtures you test. It'll be incomplete as you'll find doing that with a washing machine or toilet or dishwasher is just too much trouble.
On 2018-07-16 by Matt
How do you calculate the amount of water that could possibly be distributed to a home per day. Im not sure if I worded that correctly.
...
Continue reading at WATER PRESSURE VARIATION CAUSES or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see WATER FLOW RATE FAQs - questions & answers on how to measure or calculate the flow rate of water from a well or through a pipe
Or see these
WATER FLOW RATE CALCULATE or MEASURE at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.
Search the InspectApedia website
Note: appearance of your Comment below may be delayed: if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.
Only one image can be added per comment but you can post as many comments, and therefore images, as you like.
You will not receive a notification when a response to your question has been posted.
Please bookmark this page to make it easy for you to check back for our response.
Our Comment Box is provided by Countable Web Productions countable.ca
In addition to any citations in the article above, a full list is available on request.