InspectAPedia.com InspectAPedia®
Google
InspectAPedia
 

Free Encyclopedia of Building & Environmental Inspection, Testing, Diagnosis, Repair

Ask a Question or Search InspectAPedia

  • HOME
  • AIR CONDITIONING
  • DAMAGE ASSESSMENT
  • ELECTRICAL
  • EXTERIORS
  • HEATING
  • HOME INSPECTION
  • INTERIORS
  • PLUMBING
  • ROOFING
  • SEPTIC SYSTEMS
  • STRUCTURE
  • WATER SUPPLY
  • ENERGY SAVINGS
  • ENVIRONMENT
  • INDOOR AIR IAQ
  • INSULATION
  • MOLD INSPECT TEST REMOVE
  • NOISE
  • ODORS
  • SOLAR ENERGY
  • VENTILATION
  • EXPERTS DIRECTORY
  • CONTACT US



InspectAPedia ® Home

HEATING SYSTEMS

AFUE DEFINITION, RATINGS
AGE of AIR CONDITIONERS & HEAT PUMPS
AGE of HEATERS, BOILERS, FURNACES
AIR CONDITIONING & HEAT PUMP SYSTEMS
AIR FILTERS for HVAC SYSTEMS
AIR HANDLER / BLOWER UNITS
AIRBOUND HEAT SYSTEM REPAIRS
ANIMAL ALLERGENS / PET DANDER
ANIMAL ENTRY POINTS in buildings
ANIMAL ODORS IN buildings
ANTI SCALD VALVES
ANTIFREEZE for BOILERS
ANODES & DIP TUBES on WATER HEATERS
APPLIANCE EFFICIENCY RATINGS
ASBESTOS IDENTIFICATION IN buildings

BACKDRAFTING HEATING EQUIPMENT
BACKFLOW PREVENTER VALVE, HEATING SYS
BACKFLOW PREVENTER, HEATER WATER FEEDER
BACKUP HEAT for HEAT PUMPS
BANGING HEATING PIPES RADIATORS
BAROMETRIC DAMPERS
BIOGAS PRODUCTION & USE
BLEVE EXPLOSIONS
BLOWER DOORS & AIR INFILTRATION
BLOWER FAN CONTINUOUS OPERATION
BLOWER FAN OPERATION & TESTING
BLUE vs YELLOW COMBUSTION FLAMES
BLUERAY Recall

BOILERS, HEATING
BOILER CHEMICAL TREATMENTS
BOILER COMPONENTS & PARTS
BOILER CONTROLS & SWITCHES
BOILER LEAKS CORROSION STAINS
BOILER LEAKS, HOW TO LOCATE
BOILER NOISE SMOKE ODORS
BOILER OPERATING PROBLEMS
BOILER OPERATION DETAILS
BOILER PRESSURE & TEMPERATURE SETTINGS
BOOKSTORE - InspectAPedia
BTU USAGE MONITORS
BUILDING SAFETY HAZARDS GUIDE

CAPACITORS for HARD STARTING MOTORS
CARBON DIOXIDE - CO2
CARBON MONOXIDE - CO
CHEMICAL TREATMENTS for BOILERS
CHIMNEY INSPECTION DIAGNOSIS REPAIR
CHIMNEYS & Flues - Asbestos Transite Pipe
CHINESE DRYWALL HAZARDS
CIRCULATOR PUMPS & RELAYS
COOL OFF HEAT, Thermostat Switch
COMBUSTION AIR
COMBUSTION AIR for TIGHT buildings
COMBUSTION GASES & PARTICLE HAZARDS
COMBUSTION PRODUCTS & IAQ
COMPLETE COMBUSTION, Stoichiometric
CREOSOTE FIRE HAZARDS
Curved Brick Chimneys - Sulphation
CONDENSING BOILERS/FURNACES
CONDENSING BOILERS/FURNACES DAMAGE
CONVECTOR HEATERS - HYDRONIC COILS

DEFINITION of Heating & Cooling Terms
DIAGNOSE & FIX AIR CONDITIONER / HEAT PUMP
DIAGNOSE & FIX HEATING PROBLEMS-BOILER
DIAGNOSE & FIX HEATING PROBLEMS-FURNACE
DIRECT VENTS / SIDE WALL VENTS
DIRECTORY of OIL TANK EXPERTS
DRAFT HOODS - gas fired
DRAFT MEASUREMENT, CHIMNEYS & FLUES
DRAFT REGULATORS, DAMPERS, BOOSTERS
DUCT SYSTEM & DUCT DEFECTS
DUST, HVAC CONTAMINATION STUDY
DUST SAMPLING PROCEDURE

ELECTRIC HEAT, DIAGNOSIS, REPAIR
ELECTRIC MOTOR DIAGNOSTIC GUIDE
ELECTRIC MOTOR OVERLOAD RESET SWITCH
ELECTRICAL POWER SWITCH FOR HEAT
EVAPORATIVE COOLING SYSTEMS

FAN, AIR HANDLER BLOWER UNIT
FAN AUTO ON Thermostat Switch
FAN, COMPRESSOR/CONDENSER UNIT
FAN CONVECTOR HEATERS - HYDRONIC COILS
FAN LIMIT SWITCH
FAN NOISES
FILTERS, AIR for HVAC SYSTEMS
FILTERS, OIL on HEATING EQUIPMENT
FIRE SAFETY CONTROLS
FIREPLACES & HEARTHS
FLAME COLOR, BLUE vs YELLOW COMBUSTION
FLOODED HEATING EQUIPMENT REPAIR
FLOODED WATER HEATER REPAIR
FLUE VENT CONNECTORS
FREEZE-PROOF A BUILDING
FUEL OIL TYPES & CHARACTERISTICS
FUEL UNIT, HEATING OIL PUMPS
FURNACES, HEATING
FURNACE CONTROLS & SWITCHES
FURNACE EFFICIENCY, HIGH vs MID
FURNACE HEAT EXCHANGER LEAKS
FURNACE OPERATION DETAILS
FURNACE OPERATING TEMPERATURES

GALVANIC SCALE & METAL CORROSION
GAS BURNER Flame & Noise Defects
GAS FIRED WATER HEATERS
GAS PIPING, VALVES, CONTROLS
GAUGES ON HEATING EQUIPMENT
GEOTHERMAL HEATING SYSTEMS

HEAT EXCHANGER LEAK TEST
HEAT LOSS in BUILDINGS
HEAT LOSS DETECTION TOOLS
HEAT LOSS INDICATORS
HEAT LOSS PREVENTION PRIORITIES
HEAT LOSS R U & K VALUE CALCULATION
HEAT PUMPS, DIAGNOSIS, REPAIR
HEAT TAPES & CABLES on Roofs for Ice Dams
HEATING COST FUEL & BTU Cost Table
HEATING COST SAVINGS METHODS
HEATING LOSS DIAGNOSIS-BOILERS
HEATING LOSS DIAGNOSIS-FURNACES
HEATING OIL CLOUD WAX GEL POINT
HEATING OIL EXPOSURE HAZARDS, LIMITS
HEATING OIL - OLD, USEABLE?
HEATING OIL PIPING TROUBLES
HEATING OIL SHELF LIFE
HEATING OIL SLUDGE
HEATING OIL USAGE RATE
HEATING SYSTEM INSPECTION GUIDE
HEATING SYSTEM NOISES
HIGH EFFICIENCY BOILERS/FURNACES
HOT WATER HEATERS
HOT WATER IMPROVEMENT

INSULATION INSPECTION & IMPROVEMENT

LOW VOLTAGE BUILDING WIRING
LOW VOLTAGE TRANSFORMER TEST
LP & Natural Gas Safety Hazards

MANUALS & PARTS GUIDES - HVAC
MIXING / ANTI-SCALD VALVES
MOTOR OVERLOAD RESET SWITCH

Natural Gas Combustion Products
NO HEAT - BOILER
NO HEAT - FURNACE
NOISE / SOUND DIAGNOSIS & CURE
NOISE AIR CONDITIONER / HEAT PUMP
NOISE, DUCT VIBRATION DAMPENERS
NOISE, HEATING SYSTEMS
NOISE, PLUMBING
NOISE, WATER HEATER

ODORS GASES SMELLS, DIAGNOSIS & CURE
ODORS FROM HEATING SYSTEMS
OIL BURNERS
OIL BURNER FUEL UNIT
OIL BURNER INSPECTION & REPAIR
OIL BURNER NOISE SMOKE ODORS
OIL BURNER NOZZLE & ELECTRODES
OIL BURNERS, RETENTION HEAD
OIL BURNER SOOT & PUFFBACKS
OIL FILTERS on HEATING EQUIPMENT
OIL FILTER MISSING
OIL FUEL TYPES & CHARACTERISTICS
OIL HEAT FIRE SAFETY CONTROLS
OIL LINE CLOGGING FIX
OIL LINE QUICK STOP VALVES
OIL LINE SAFETY VALVES
OIL ODORS, LEAKY OIL TANK PIPING
OIL PUMP FUEL UNIT
OIL SPILL CLEANUP / PREVENTION
OIL TANKS

PLASTIC HEATER VENT
PULSE COMBUSTION HEATERS
PASCAL CALCULATIONS
PRESSURE REDUCING VALVES
PRESSURE REGULATOR, WATER
PUFFBACKS, OIL BURNER
PUMPS, PONY PUMPS

RADIANT BARRIERS
RADIANT HEAT
RADIANT HEAT Floor Mistakes to Avoid
RADIANT HEAT TEMPERATURES
RADIANT SLAB FLOORING CHOICES
RADIANT SLAB TUBING & FLUID CHOICES

RADIATORS
RELIEF VALVE LEAKS
RELIEF VALVES - TP Valves on Boilers
RELIEF VALVES - STEAM TP VALVES
RELIEF VALVES - Water Heaters
RELIEF VALVES - Water Tanks

Reset Switch - Heater Primary Control
Reset Switch Broken - Quick Repair
RESET SWITCH - ELECTRIC MOTOR
Reset Switch - Stack Relays

SAFETY HAZARDS & INSPECTIONS
SAFETY HAZARDS GUIDE
SAFETY, HEATING INSPECTION
SAFETY RECALLS, Chimneys, Vents, Heaters
SOOT on OIL FIRED HEATING EQUIPMENT
SPILL SWITCHES - Flue Gas Detection
SPLIT SYSTEM AIR CONDITIONERS & HEAT PUMPS
STACK RELAY SWITCHES
STEAM HEATING SYSTEMS
  AQUASTAT CONTROL Functions
  BACKDRAFTING HEATING EQUIPMENT
  BACKFLOW PREVENTER VALVE, HEATING SYS
  BANGING HEATING PIPES RADIATORS
  CAD CELL RELAY SWITCH
  CHECK VALVES, HEATING SYSTEM
  CHEMICAL TREATMENTS, Boiler
  Circulator Pumps & Relays
  COMBUSTION GASES & PARTICLE HAZARDS
  CONDENSATE RETURN PIPES, PUMPS, STEAM
  DIAGNOSE & FIX BOILER
  DRAFT HOODS - gas fired
  DRAFT MEASUREMENT, CHIMNEYS & FLUES
  DRAFT REGULATORS, DAMPERS, BOOSTERS
  ELECTRIC MOTOR OVERLOAD RESET SWITCH
  ELECTRICAL POWER SWITCH FOR HEAT
  EXPANSION TANKS
  FIRE SAFETY CONTROLS
  GAUGES, HEATING EQUIP.
  LIMIT SWITCH, BOILER
  LOW WATER CUTOFF VALVE
  MIXING / ANTI-SCALD VALVES
  PRESSURE, TEMPERTURE SETTINGS, CONTROLS
  PRESSURE SWITCH, STEAM BOILER
  RELIEF VALVES - STEAM TP VALVES
  SIGHT GLASS, STEAM BOILER
  SPILL SWITCHES
  STACK RELAY SWITCH
  STEAM PRESSURE GAUGE
  STEAM TRAPS
  STEAM VENTS
  THERMOSTATS, HEATING / COOLING
  WATER FEEDER Valves, Steam

TANKLESS COILS
Thermal Expansion Cracking of Brick
THERMAL EXPANSION of HOT WATER
THERMAL EXPANSION of MATERIALS
THERMAL IMAGING, THERMOGRAPHY
THERMAL IMAGING MOLD SCANS
THERMAL MASS in BUILDINGS
THERMAL TRACKING & HEAT LOSS
THERMOSTATS, HEATING / COOLING
THERMOSTATS, WATER HEATER
THERMOSTATIC EXPANSION VALVES
Transite Pipe Chimneys & Flues

VIDEO GUIDES: Heating System Videos
VIDEO GUIDES - InspectAPedia.com

WATER HEATERS
WATER HEATER SAFETY
WATER HEATERS for HOME HEATING USE?
WATER HEATER NOISES
WATER HEATER SCALE - De-Liming Procedure
WATER HEATER SCALE PREVENTION
WINTERIZE A BUILDING
WOOD, COAL STOVES & FIREPLACES
WOOD STOVE SAFETY

ZONE DAMPERS
ZONE VALVES

More Information

Condensate return sysem on steam heat (C) D FriedmanSteam Heat Condensate Piping, Pumps, Return LInes
InspectAPedia®  -    

  • Condensate Return Pumps & Condensate Systems on Residential Steam Heating Systems - how to identify & troubleshoot steam condensate return piping
  • Sources of Trouble in the Steam Condensate System
  • Corrosion on Steam Piping & Corrosion Control by Chemical Treatment of Condensate or Water
  • Leaks in steam condensate return piping
  • Problems with condensate return reservoirs & pumps
  • Questions & Answers about the causes & cures of trouble with steam condensate piping, pumps, reservoirs
  • References

Click to Show or Hide Related Topics

  • STEAM HEATING SYSTEMS & Controls - home
  • AQUASTAT CONTROL Functions
  • BANGING HEATING PIPES RADIATORS
  • CAD CELL RELAY SWITCH
  • CHECK VALVES, HEATING SYSTEM
  • CHEMICAL TREATMENTS, Boiler
  • CONDENSATE RETURN PIPES, PUMPS, STEAM
  • DEFECTS LIST - HEAT STEAM
  • DIAGNOSE & FIX BOILER
  • DRAFT HOODS - gas fired
  • DRAFT MEASUREMENT, CHIMNEYS & FLUES
  • DRAFT REGULATORS, DAMPERS, BOOSTERS
  • ELECTRIC MOTOR OVERLOAD RESET SWITCH
  • ELECTRICAL POWER SWITCH FOR HEAT
  • EXPANSION TANKS
  • FIRE SAFETY CONTROLS
  • GAUGES, HEATING EQUIP
  • LIMIT SWITCH, BOILER
  • LOW WATER CUTOFF VALVE
  • MIXING / ANTI-SCALD VALVES
  • PRESSURE, TEMPERTURE SETTINGS, CONTROLS
  • PRESSURE SWITCH, STEAM BOILER
  • RADIATORS
  • RELIEF VALVES - STEAM TP VALVES
  • SIGHT GLASS, STEAM BOILER
  • SPILL SWITCHES
  • STEAM HEAT DEFECTS LIST - curriculum
  • STACK RELAY SWITCH
  • STEAM PRESSURE GAUGE
  • STEAM TRAPS
  • STEAM VENTS & STEAM VENTS, AUTOMATIC
  • THERMOSTATS, HEATING / COOLING
  • WATER FEEDER Valves, Steam
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

Steam heating system condensate pumps & piping: this article describes and illustrates steam condensate return piping, condensate return pumps and steam condensate return reservoirs. We also discuss leaks in steam condensate piping lines and chemical treatment of steam condensate.

Green links show where you are. © Copyright 2013 InspectAPedia.com, All Rights Reserved. Author Daniel Friedman.

Guide to Condensate Return Pumps & Condensate Systems on Residential Steam Heating Systems

Steam condensate return pump system (C) D Friedman

If you don't know what kind of heat your building uses, we explain how to figure out the answer at HEATING SYSTEM TYPES. If your heating system is not working properly, see NO HEAT - BOILER or NO HEAT - FURNACE.

Our photo at left illustrates a steam condensate return pump system in a New York home.

Where condensate is unable to flow by gravity back to the steam boiler, a reservoir tank (under our client's hand at left) receives condensate from a low point in the building.

A float control and small pump moves condensate back to the steam boiler.

 

This steam system includes a plastic tank and injector pump used for chemical treatment of the steam condensate. When the float in the condensate return tank activates the condensate return pump, that same circuit activates the small chemical injector pump mounted on top of the plastic reservoir at the right in our photograph.

Some Sources of Trouble in the Steam Condensate System

Condensate return line leak (C) D FriedmanWatch out: problems such as blockages or leaks in steam condensate return systems can have various causes and can originate in many areas including at least these:

  • Improperly sloped or routed condensate return piping
  • A steam trap that is not working properly - see STEAM TRAPS
  • A wiring error or electrical failure that causes the condensate pump to run backwards
  • A system operating problem (such as bad steam vents) or other events (a leak) or conditions (water chemistry or poor maintenance) that causes too-frequent in-feed of water to the boiler, leading to corrosion and leaks in the condensate piping or in the boiler itself
  • Improperly set or damaged boiler water feeder or water level controls
  • Condensate reservoir leaks
  • Condensate pump motor troubles: motor not running, won't start, won't stop running, noisy
    • See ELECTRIC MOTOR DIAGNOSTIC GUIDE for condensate pump motor problems
    • Check for a dirty or clogged strainer blocking condensate flow in the reservoir or at the pump
    • If the pump wont' stop running check for a leaky failed steam trap (s) or a valve that has been left partly closed or is debris-clogged in the condensate discharge line; also check for a broken or debris-clogged pump impeller.
  • Dirt or debris blockages at steam traps, or anywhere in the condensate return system piping, including at the Hartford Loop

Corrosion on Steam Piping & Corrosion Control by Chemical Treatment of Condensate or Water

Steam condensate return pump system (C) D Friedman

Our second steam condensate return system (left) shows the reservoir and condensate pump motor (grey pump and new piping on the right side of the condensate reservoir at the left in that picture).

Steam condensate may be corrosive due to an improper pH level of the building water supply, or condensate water may be particularly corrosive to steam piping or to the boiler itself due to the formation of carbonic acid in the condensate liquid.

Carbonic acid itself forms because of the combination of high levels of carbon dioxide CO2 and oxygen in the steam piping system. Steam piping that is made of copper is also vulnerable to a combination of ammonia and oxygen in the steam condensate.

Chemical treatment of steam condensate is typically done to reduce corrosion in the steam piping.

Other chemical treatments of water in steam boilers may be performed at the boiler itself to adjust the pH of the water or to control levels of corrosive carbonic acid using neutralizing amines or to control oxygen levels. [1]

A second approach to controlling steam system corrosion used particularly in steam systems that use a high volume of make-up water is the use of filming inhibitors or filming amines.

In a third approach to controlling steam system corrosion, water entering steam boilers may also be "de-aerated" by a feed water heater that removes excess oxygen mechanically.

Where do corrosion and leaks most often appear in steam piping?

Corrosion in steam piping is most likely to appear in the sections of steam condensate piping that remain filled with condensate. Those piping sections are found near the steam boiler itself or at steam condensate return reservoirs and pumps.

To control or reduce the corrosion and leaks caused by corrosive steam condensate the steam boiler water may be pre-treated or the condensate may itself be treated as we illustrate in our photo above.

Leaks in Steam Condensate Return Piping

Steam condensate return leaks (C) D Friedman

Our photograph at left shows a leaky steam condensate return line close to the steam boiler.

This steam condensate line leak has been dripping for more than a decade. Unlike a hydronic heating boiler system, because the pressure in the steam condensate return line is low, the leak was not noticed by the homeowner and it was ignored by the heating service technician.

Our opinion was that the piping in this steam condensate line section all should be replaced, but it was reasonable to wait until the end of the heating season rather than having to shut down the heater during freezing-cold weather.

Watch out: never pick at corrosion on a heating pipe: we warned the homeowner not to poke or pick at the corrosion on this piping. Disturbing the condensate return pipe was likely to result in a sudden and much larger leak that could leak badly, resulting in basement water problems and increased steam boiler water consumption.

Watch out: a leak in the condensate piping of a steam heating system can lead to very expensive damage including:

  • Leaks into the building causing rot, inviting insect damage, or leading to a costly mold cleanup job
  • Excessive water in-feed to the boiler, leading to increased rate of corrosion in the condensate piping or even the boiler itself, risking the development of additional leaks that can destroy the boiler

More details about steam condensate return pumps for residential properties are in process, photo contributions needed. CONTACT us.

...


Frequently Asked Questions (FAQs)

...

Ask a Question or Search InspectApedia

Questions & answers or comments about the causes & cures of trouble with steam condensate piping, pumps, reservoirs.

Ask a Question or Enter Search Terms in the InspectApedia search box just below.

Technical Reviewers & References

Related Topics, found near the top of this page suggest articles closely related to this one.

  • [1] Boiler Systems, Chemical Treatment, Association of Water Technologies, Technical Manual, web search 04/22/2011, original source: http://www.steamforum.com/pictures/water%20treat%20Boilers%281%29.pdf
  • [2] "Steam/Condensate Treatment, An Overview of Monitoring and Treatment", John J. Baum, Craft Products Co., Inc., White Paper prepared for P.C.I. Controls and Instrumentation, Seminar, August 1995, web search 04/23/2011, original source: http://www.craftprod.com/research/Steam%20-%20Condensate%20Treatment.pdf
  • "The Fight Against Corrosion - A Study of the Nature of Corrosion and its Problems in Water Services and Heating Systems", Daniel Davies, Research and Development Services, Stansted Mountfichet, Essex, England, World Plumbing Conference-IV, "Plumbing and the World Environment, Compendium of Workshop Papers, October 3-6, 1996, Hyatt Regency Chicago, Chicago, IL", [personal correspondence, DJF - Author, July 2011]

For details about the controls, components and switches commonly found on hot water heating systems see the articles listed below in which we explain how to identify, set, re-set, repair, replace, or avoid problems with the components of a hot water heating system..

  • Steam Boiler Inspection, Diagnosis, Repair books at the InspectAPedia bookstore - Amazon.com
  • The Steam Book, 1984, Training and Education Department, Fluid Handling Division, ITT [probably out of print, possibly available from several home inspection supply companies] Fuel Oil and Oil Heat Magazine, October 1990, offers an update, (see next item in this list). ITT Fluid Technology, 1133 Westchester Avenue
    White Plains, NY 10604, tel +1 914 304 1700 fax +1 914 696 2950 www.ittfluidbusiness.com
  • Principles of Steam Heating, $13.25 includes postage. Fuel oil & Oil Heat Magazine, 389 Passaic Ave., Fairfield, NJ 07004.
  • The Lost Art of Steam Heating, Dan Holohan, 516-579-3046 FAX
  • Principles of Steam Heating, Dan Holohan, technical editor of Fuel Oil and Oil Heat magazine, 389 Passaic Ave., Fairfield, NJ 07004 ($12.+1.25 postage/handling).
  • "Residential Steam Heating Systems", Instructional Technologies Institute, Inc., 145 "D" Grassy Plain St., Bethel, CT 06801 800/227-1663 [home inspection training material] 1987
  • The Heat Efficiency of Steam Boilers, Bryan Donkin
  • Steam Boiler Operation, Principles & Practice, James J. Jackson
  • Domestic and Commercial Oil Burners, Charles H. Burkhardt, McGraw Hill Book Company, New York 3rd Ed 1969.
  • National Fuel Gas Code (Z223.1) $16.00 and National Fuel Gas Code Handbook (Z223.2) $47.00 American Gas Association (A.G.A.), 1515 Wilson Boulevard, Arlington, VA 22209 also available from National Fire Protection Association, Batterymarch Park, Quincy, MA 02269. Fundamentals of Gas Appliance Venting and Ventilation, 1985, American Gas Association Laboratories, Engineering Services Department. American Gas Association, 1515 Wilson Boulevard, Arlington, VA 22209. Catalog #XHO585. Reprinted 1989.
  • The Steam Book, 1984, Training and Education Department, Fluid Handling Division, ITT [probably out of print, possibly available from several home inspection supply companies] Fuel Oil and Oil Heat Magazine, October 1990, offers an update,
  • Principles of Steam Heating, $13.25 includes postage. Fuel oil & Oil Heat Magazine, 389 Passaic Ave., Fairfield, NJ 07004.
  • The Lost Art of Steam Heating, Dan Holohan, 516-579-3046 FAX
  • Principles of Steam Heating, Dan Holohan, technical editor of Fuel Oil and Oil Heat magazine, 389 Passaic Ave., Fairfield, NJ 07004 ($12.+1.25 postage/handling).
  • "Residential Steam Heating Systems", Instructional Technologies Institute, Inc., 145 "D" Grassy Plain St., Bethel, CT 06801 800/227-1663 [home inspection training material] 1987
  • "Residential Hydronic (circulating hot water) Heating Systems", Instructional Technologies Institute, Inc., 145 "D" Grassy Plain St., Bethel, CT 06801 800/227-1663 [home inspection training material] 1987
  • "Warm Air Heating Systems". Instructional Technologies Institute, Inc., 145 "D" Grassy Plain St., Bethel, CT 06801 800/227-1663 [home inspection training material] 1987
  • Heating, Ventilating, and Air Conditioning Volume I, Heating Fundamentals,
  • Boilers, Boiler Conversions, James E. Brumbaugh, ISBN 0-672-23389-4 (v. 1) Volume II, Oil, Gas, and Coal Burners, Controls, Ducts, Piping, Valves, James E. Brumbaugh, ISBN 0-672-23390-7 (v. 2) Volume III, Radiant Heating, Water Heaters, Ventilation, Air Conditioning, Heat Pumps, Air Cleaners, James E. Brumbaugh, ISBN 0-672-23383-5 (v. 3) or ISBN 0-672-23380-0 (set) Special Sales Director, Macmillan Publishing Co., 866 Third Ave., New York, NY 10022. Macmillan Publishing Co., NY
  • Installation Guide for Residential Hydronic Heating Systems
  • Installation Guide #200, The Hydronics Institute, 35 Russo Place, Berkeley Heights, NJ 07922
  • The ABC's of Retention Head Oil Burners, National Association of Oil Heat Service Managers, TM 115, National Old Timers' Association of the Energy Industry, PO Box 168, Mineola, NY 11501. (Excellent tips on spotting problems on oil-fired heating equipment. Booklet.)
  • Links to our list of additional information on heating system inspection, repair, maintenance

Books & Articles on Building & Environmental Inspection, Testing, Diagnosis, & Repair

  • Our recommended books about building & mechanical systems design, inspection, problem diagnosis, and repair, and about indoor environment and IAQ testing, diagnosis, and cleanup are at the InspectAPedia Bookstore. Also see our Book Reviews - InspectAPedia.
  • Home Reference Book - Carson DunlopThe Home Reference Book - the Encyclopedia of Homes, Carson Dunlop & Associates, Toronto, Ontario, 25th Ed., 2012, is a bound volume of more than 450 illustrated pages that assist home inspectors and home owners in the inspection and detection of problems on buildings. The text is intended as a reference guide to help building owners operate and maintain their home effectively. Field inspection worksheets are included at the back of the volume. Special Offer: For a 10% discount on any number of copies of the Home Reference Book purchased as a single order. Enter INSPECTAHRB in the order payment page "Promo/Redemption" space. InspectAPedia.com editor Daniel Friedman is a contributing author.

    Or choose the The Home Reference eBook for PCs, Macs, Kindle, iPad, iPhone, or Android Smart Phones. Special Offer: For a 5% discount on any number of copies of the Home Reference eBook purchased as a single order. Enter INSPECTAEHRB in the order payment page "Promo/Redemption" space.

  • GO TO Carson Dunlop's Home Study Course Information - How to Become a Home Inspector: Carson Dunlop's nationally recognized Home Study Course, selected by ASHI the American Society of Home Inspectors and other professionals and associations. This website author is a contributor to this course.
  • GO TO Carson Dunlop's Home Study Course Information - How to Become a Home Inspector: Carson Dunlop's nationally recognized Home Study Course, selected by ASHI the American Society of Home Inspectors and other professionals and associations. This website author is a contributor to this course.
  • GO TO Carson Dunlop's Home Study Course Information - How to Become a Home Inspector: Carson Dunlop's nationally recognized Home Study Course, selected by ASHI the American Society of Home Inspectors and other professionals and associations. This website author is a contributor to this course.
    Building inspection education & report writing systems from Carson, Dunlop & Associates Ltd
  • Carson Dunlop, Associates, Toronto, have provided us with (and we recommend) Carson Dunlop Weldon & Associates' Technical Reference Guide to manufacturer's model and serial number information for heating and cooling equipment
    Special Offer
    : Carson Dunlop Associates offers InspectAPedia readers in the U.S.A. a 5% discount on any number of copies of the Technical Reference Guide purchased as a single order. Just enter INSPECTATRG in the order payment page "Promo/Redemption" space.

  • ...

HOME ABOUT CONTACT COPYING DESCRIPTION POLICIES PRINTING PRIVACY © 2013 Copyright InspectAPedia.com