Q&A on how to repair an electrical box that is damaged, loose, or has stripped screw openings.
This article series describes how to repair the mounting screw or screw opening at an electrical box used to mount a receptacle, switch, or other device.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
- Daniel Friedman, Editor/Publisher - See WHO ARE WE?
This Q&A were posted originally at ELECTRICAL BOX SCREW REPAIR - you may also want to review that article.
On 2018-11-08 by Steve - exterior brick veneer wall - porch light damaged during a storm
I have a porch light that was damaged during a storm - see photo at page top.
[Click to enlarge any image]
Fortunately the light was undamaged, but the junction box that's in the brick broke in half where the screw holes are.
To me, it looks as if I need to replace the junction box. My question is, "How"? The box has mortar all around it and obviously won't just pull out. Just not sure how to go about doing this myself. Any input would be appreciated.
On 2018-11-08 by (mod) - options for repairing a damaged electrical box in a brick, block, or concrete exterior wall
Steve I can't quite make out what is the situation in your exterior wall electrical box photo of damage.
Is the box itself broken or just the screw connector tab?
Is the box metal or plastic?
In your photo it looks to me as if the only damage is the lower box cover mounting screw tab or receiver - which looks cracked; perhaps a tree limb smashed your porch light and broke it away from the wall.
If just one of the screw tabs in the existing electrical box is broken you can easily repair the situation by using a Tapcon screw - saving hours of fooling around trying to replace the whole electrical box.
Here are the repair steps if you can use a Tapcon screw:
If you have a lot of Tapcon screw repairs I recommend buying the company's repair kit and an appropriate assortment of screws. Mine are shown below.
Watch out: While driving a Tapcon or any other repair screw into an existing electrical box, ytou don't want to pierce an electrical wire in the box - see ELECTRICAL PANEL COVER SCREWS for an example of what can go wrong.
If the break is just the connector screw-tab, an alternative repair to using a Tapcon screw and one that you might need if the wall is a masonry veneer over wood frame is to use a repair clip like the several models (including the G-clip shown above).
If the break is just the connector screw-tab, I suspect it's possible to use a repair clip like the ones discussed in that article - simply chip out enough enough concrete at the box edge to insert the replacement repair clip, break off and remove the broken screw connector, then install the repair connector.
Simply chip out enough enough concrete at the box edge to insert the replacement repair clip, break off and remove the broken screw connector, then install the repair connector shown below and described in detail
at ELECTRICAL BOX SCREW REPAIR
If the whole box is broken it may be possible to seal it against water entry using a fire-rated sealant.
In the worst case you'd indeed need to use a small cold chisel to remove the box after first straightening its entering wires. That's a larger job that I agree is best avoided if possible, but certainly do-able.
When facing a problem like this it's helpful to tell yourself that others have surely faced this problem before and that almost certainly there are specialty repair tools or parts for the job.
The electrical box mender screw clip is an example.
Watch out: work only with power off, and if you're not familiar with safe electrical wiring have the work done by a professional: a mistake can kill you or burn down the house.
For a badly-damaged electrical box installed in an exterior masonry brick or block wall, the typical repair procedure used by many electricians involves the following steps:
Watch out: don't over-foam or you'll have a lot of cleanout to perform, as you can see in my photo below.
You want the weather-proof electrical box to actually be weatherproof if you're working in an exterior wall. So take care to buy the proper outdoor-use round electrical box to fit the existing opening.
A round 4" weatherproof exterior use electrical box like the one shown above can be used.
To insert that box flush into the wall so that its outer edge is just above the wall surface (so that its cover will also seal weather-tight) you'll need to break off the surface-mount ears (red arrows in the photo) and you will probably need to enlarge the hole in the wall slightly to get the wires into the box and the box into the wall.
Then you can mount this box into the masonry wall as I described previously.
...
Continue reading at METAL ELECTRICAL BOX SCREW REPAIR, METAL BOX MENDER or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see these
EXTERIOR ELECTRICAL BOX REPAIR at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Questions & answers or comments about ways to replace an electrical outlet or switch mounting screw when threads are stripped on the screw or in the mounting box.
Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.
Search the InspectApedia website
Note: appearance of your Comment below may be delayed: if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.
Only one image can be added per comment but you can post as many comments, and therefore images, as you like.
You will not receive a notification when a response to your question has been posted.
Please bookmark this page to make it easy for you to check back for our response.
Our Comment Box is provided by Countable Web Productions countable.ca
In addition to any citations in the article above, a full list is available on request.