Building Inspection, Diagnosis & Repair Info

Septic tank being pumped (C) Daniel Friedman at InspectApedia How to Measure Septic Tank Bottom Sludge Thickness Level

  • POST a QUESTION or COMMENT about the septic tank sludge layer: measurement, thickness, diagnostics, guidance for septic tank cleanout interval.

Septic tank bottom sludge:

This article explains how to measure the thickness of the layer of sludge on the bottom of a septic tank - a step in deciding if a septic tank needs to be pumped out and cleaned.Septic tank pumping pumping frequency guidance is provided in a table at our website (seelinks listed at the ARTICLE INDEX the bottom of this article .)

When the septic tank is pumped, measurements of the scum layer and sludge layer tell you the condition of the system.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?





ADVERTISEMENT





How to Measure the Bottom Sludge Layer Thickness in the Septic Tank: measuring the thickness of the settled sludge layer

Septic tank sludge measaurement method - USDA DJF

Septic tank scum layer thickness measurements are given in detail at HOW TO MEASURE SEPTIC SCUM LAYER


and septic tank bottom sludge layer thickness measurements are detailed on this page.

These measurements can be made or at least roughly estimated by the septic pumping contractor at the time that a septic tank is pumped.

This nformation permits the home owner to know

  1. Whether or not the septic tank is being pumped often enough
  2. Whether or not there is evidence that the septic fields have been damaged by having not pumped the tank soon enough.

At SEPTIC TANK LEVELS of SEWAGE we explain how to interpret the meaning of high or low sewage levels in the septic tank as well as thick or thin scum or sludge levels.

Readers of this document should be sure to review our table of septic tank pumping frequency.

The same pole can be used for this purpose by removing the flapper, or a separate pole can be constructed. To re-use the scum pole, just pull the hinge pin which will drop the flapper assembly, leaving half the hinge still bolted to the pole end for next use. A simple septic tank sludge measuring pole and towel shown at left (courtesy USDA).

  1. A towel, preferably a light color, is wrapped around the end of the pole and secured thoroughly.

    The towel does not need to be a big bulge at the end of the pole but rather should be screwed or taped so that it simply wraps around the pole for about three feet from the bottom of the pole up. (A sheet metal screw through the towel into the pole makes sure you won't leave the towel behind in the bottom of the septic tank.
  2. Probe the septic tank to the bottom, just behind (not through) the outlet baffle, and keep the probe there for a minute or longer.
  3. Pull the probe back up from the tank bottom and observe the total height of sludge marked on the towel.
  4. Compare the sludge height from the tank bottom with the distance from the outlet baffle to the tank bottom.
  5. Watch out: Sludge within 12 in. of the bottom edge of the septic tank baffle or Tee or septic tank sludge closer than 18 in. to the actual point of effluent outlet from the tank (the horizontal outlet pipe) means that the tank needs to be pumped.

Also see TUBE for MEASURING SCUM & SLUDGE for a tool that can make both scum and sludge thickness measurements with a single device.

For deep or hard to access or commercial septic tanks that may need close monitoring, see ELECTRIC MONITOR for SCUM & SLUDGE and also take a look at Other Measures Scum / Sludge.

Where to Measure Septic Tank Scum & Sludge Levels

Septic tank scum sludge measuring routine - USDA DJF

Because of the typical sludge settlement pattern, & possibly also scum formation pattern, measure the septic tank sludge and scum layers near the septic tank outlet for a single-chamber septic tank, or at the outlet of the first chamber in a two or more chambered septic tank.

The USDA sketch (left) shows where sludge measurements are being made in a two-chamber septic tank. Make sure your septic tank access is over the outlet, not the inlet, when you are making these tests.

Here is a sketch of measuring the scum & sludge levels in a single-chamber septic tank.

When to Measure Septic Tank Scum & Sludge Levels

An optimum septic tank / soil absorption maintenance plan includes opening, inspecting, and measuring the sludge and scum levels annually. If your inspections never find baffle damage, evidence of tank flooding, tank leaks, tank backups, nor thick sludge or scum layers, you can try extending this interval to alternate years or longer.

What is the settled sludge layer in a septic tank

The sludge layer on the bottom of a septic tank includes various solids which are not dissolved in the septic effluent and which are dense enough to fall to the bottom of the tank.

The septic tank bottom sludge is comprised of "settleable solids" and that portion of "suspended solids" which will, given enough time, also settle out. These accumulate at the bottom of the septic tank until they are removed by a septic tank cleanout procedure.

Normally a septic tank should be pumped when the bottom layer of sludge is within 18 inches of the tank outlet.

Other measures of scum layer and sludge layer indicate when to pump the septic tank

The following example was provided to us by Effluent Services, Ltd., an experienced septic service company in New Zealand. In New Zealand septic tank sizes range from 2000-6000 liters (500 gallons to 1,500 gallons U.S.) with the average being 3100 liters (about 800 U.S. gallons and below the minimum septic tank size permitted in most U.S. jurisdictions).

"Generally at a two year interval for septic tank pumping service the average septic tank in these size ranges will have a 400 mm scum layer with about a 200 mm sludge layer.  With an average depth of 1600 mm, the solids content is about 600 mm thereby reducing the settling time by nearly 40%.   

Similar rules of thumb offered by USDA on how much sludge or scum mean the septic tank needs cleaning include:

or

or

This is very sound reasoning. Homeowners should use the scum and sludge layers found when their septic tanks are pumped as a way to determine whether or not the tank is being pumped often enough. In areas where most septic tanks are on the comparatively "small' side, a two year regular pumping schedule is reasonable for light-usage.

In our experience, a 500-gallon septic tank in a home with a family of four is going to need very frequent pumping if the drainfield, leach beds, or soakaway system is to be protected. Multiple times a year. This is so costly that it makes sense to install a much larger septic tank.

When to Pump the Septic Tank based on thickness of the septic tank sludge and scum layers

The following is an excerpt from What Scum Sludge Thickness = Pump Needed.

"Generally at a two year interval for septic tank pumping service the average septic tank in these size ranges will have a 400 mm scum layer with about a 200 mm sludge layer.  With an average depth of 1600 mm, the solids content is about 600 mm thereby reducing the settling time by nearly 40%.   

Don't wait too long before removing septic scum and sludge People who wait until their septic system stops working due to a clogged or over-filled (with sludge and scum) septic tank have waited too long.

As the bottom sludge layer increases in thickness, and as the top septic scum layer increases as well, the remaining "net free area" or "effective septic tank volume" of effluent in the tank is reduced in volume.

When a septic tank is operating with a low volume of "net free area" of septic effluent, the system lacks adequate volume to provide adequate settlement time - time needed for sludge to settle to the tank bottom and scum to coagulate at the tank top. In this circumstance, although drains in the building seem to be just fine, the septic tank effluent is remaining in a constant state of stirred-agitation. In turn, that means that the system is pushing floating debris into the leach field or other absorption system.

Pushing grease, scum, and small solid debris out of the septic tank and into the leach field reduces the future life of that expensive component of a septic system.

Beginning at SEPTIC TANK PUMPING PROCEDURE are the Steps in Septic Tank Cleaning Procedure in the order that they should be performed

...





ADVERTISEMENT





...

Continue reading  at SEPTIC TANK BACK FLOODING or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.

Or see these

Recommended Articles

Suggested citation for this web page

HOW TO MEASURE SEPTIC SLUDGE LAYER at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

Or see this

INDEX to RELATED ARTICLES: ARTICLE INDEX to SEPTIC SYSTEMS

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Ask a Question or Search InspectApedia

Share this article:

Search the InspectApedia website

Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.

Citations & Reviewers

In addition to any citations in the article above, a full list is available on request.

  • SEPTIC TANK/SOIL-ABSORPTION SYSTEMS: HOW TO OPERATE & MAINTAIN [PDF] - , Equipment Tips, U.S. Department of Agriculture, 8271 1302, 7100 Engineering, 2300 Recreation, September 1982, web search 08/28/2010, original source: http://www.fs.fed.us/t-d/pubs/pdfimage/82711302.pdf.
  • Thanks to Richard at Effluent Services, Ltd., Cambridge 3434 NZ for the suggestions regarding the significance of the septic tank floating scum layer and settled sludge layer. New Zealand readers can contact this septic system service company at 07 827 0436 or Waikato Wide: 0800 EFFLUENT.
  • Thanks to reader Robert Shirley, Calgary, for discussing alternative ways to measure septic tank sludge, including the relatively low cost electronic system on the market from Worldstone Inc. (SepticWatch) - a system to monitor sludge and scum and grease levels in grease traps or septic tanks - 04/20/2010
  • Worldstone, http://www.worldstoneinc.com/ electronic monitors, including via internet, for grease traps, septic tanks, oil tanks - manufactured by F.O.G. Solutions,  1348 Delta Drive, Saginaw, MI 48638, 866 279-2824, 989-928-1806, Fax 480-247-4983. The Company also makes an oil tank level monitor.
    "Worldstone Inc. is a Braintree Massachusetts based company that specializes in separation tank monitoring. Using established ultrasonic technologies, Worldstone’s GREASEwatch,

    SEPTICwatch and OILwatch monitors capture critical tank information and transfers data to city officials, end users or service providers creating a safer, cost effective solution to manual inspections. Data from monitors can help establish appropriate service intervals, and document maintenance for regulatory compliance. Alarm features can help detect abnormal conditions and prevent costly backups.

    Worldstone monitors are currently assisting over 200 major restaurants, hospitals, prisons, casinos and city officials across the United States."

    Septic Tank Monitoring:


    "The SEPTICwatch monitor provides continuous monitoring of the sludge, scum, temperature and liquid levels [in a septic tank]. ... real-time information on actual changes as a percentage of permissible floating solids, bottom solids and total solids. It also provides the immediate status of the liquid level within the tank in inches. Using the monitor's programmable Control Unit, the tank's optimum level for pumping is set, so the tank can be pumped when it's actually needed. The [septic tank] monitor's Control Unit can also be programmed to warn of dangerously high solid levels and lower than normal/higher than normal liquid levels - emergency conditions that could indicate system failure."

    Grease Trap Monitoring:

    "...GREASEwatch monitor uses ultrasonic transducers and an embedded microprocessor to continuously monitor the sludge, scum, liquid levels and temperature in your grease trap. ... get real-time information on incremental changes in the levels of floating solids, bottom solids and total solids at the touch of a button. ... the immediate status of the liquid level in the trap in inches. The Control Unit can be programmed to indicate how full the tank should be before pumping, so there's no more guessing when it's time for service. The GREASEwatch monitor lets you plan a pumping level that meets your needs and protects your investment.
    "


ADVERTISEMENT