Tankless water heater (C) Daniel Friedman Pro PHCC BrandSizing Tankless Water Heaters

  • POST a QUESTION or COMMENT about how to determine the size or capacity of tankless water heater or instant water heater that you require

How to Calculate Tankless Water Heater Requirements - tankless water heater capacity sizing guidelines:

Here we explain how to calculate the size or capacity of tankless water heater you will need in a building.

We name all of the factors that you should consider when buying a tankless or demand or point of use type water heater, such as incoming water temperature, desired output water temperature, and the total hot water flow rate in gallons per minute.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?





ADVERTISEMENT





How to Calculate Tankless Water Heater Requirements

Tankless water heater (C) Carson Dunlop AssociatesYou can calculate the approximate tankless water heater capacity required for any application as follows: Sketch of a point of use tankless water heater courtesy of Carson Dunlop Associates, a Toronto home inspection, education & report writing tool company [ carsondunlop.com ].

[Click to enlarge any image]

T1 = incoming water temperature

T2 = desired output hot water temperature at the plumbing fixture (say a shower)

GPM = anticipated hot water flow rate or usage rate in gallons per minute.

Example:

If your incoming water temperature to the building is 40 deg.F. and you want to provide hot water at a bath shower at 100 deg. F., and if your shower fixture runs at 3 gpm, then

T1 = 40 deg.F., T2 = 100 deg.F.

T2 - T1 = 60 deg.F. - that's the temperature rise you need.

Rheem tankless water heater © D Friedman at InspectApedia.com Our photo (left) illustrates a Rheem EcoSense® tankless water heater. A wide range of sizes and capacities of demand type water heaters are available, so indeed it makes sense to look carefully at your requirements.

Your tankless water heater will need to be able to provide a 60 deg. temperature rise at 3 GPM.

Note 1: our example does not consider temperature losses in the piping between the water heater and the point of use nor the use of temperature limiting or anti-scald valves in the plumbing system, both of which reduce the actual hot water flow rate in gpm

While 100° may be a good shower temperature, this means that mixing valves at the shower will be delivering almost 100% hot water. This may make filling a bathtub slow or result in lower water pressure than anticipated. When we blend hot and cold water, we enjoy a higher flow rate and commensurately higher pressure at the shower.

Note 2: it's quickly apparent that if the hot water system is going to be asked to provide 100 deg.F. hot water to multiple fixtures simultaneously, the gpm heating rate of your tankless water heater is going to have to be big - and may be beyond the capacity of the equipment.

In this case see MULTIPLE GANGED TANKLESS WATER HEATERS.

Gas fired tankless water heaters can usually produce more hot water faster than an electric unit. Electric tankless water heaters are simplest to install and operate, requiring only wiring and water piping, no fuel piping, no venting or chimney.

If your building includes three or four bathrooms or even just two baths, and if the occupants are likely to want to run hot showers simultaneously at multiple fixtures, the performance of a single demand water heater or tankless water heater may be marginal unless the unit is quite large.

An Example of Sizing a tankless water heater: specifying hot water flow rate & temperature rise required

- Adapted & expanded from Tankless or Demand Type Water Heaters, & from Sizing a Water Heater, - U.S. DOE[15][17].

As we explain in detail at TANKLESS WATER HEATER CAPACITIES, since there is no reservoir of hot water in a demand type water heating system, instead, tankless or demand-type water heaters are rated by the maximum temperature rise possible at a given flow rate through the device. As DOE points out in their article, to size a demand water heater, you need to determine

  1. Hot water flow rate: calculate the maximum combined hot water flow rate that may be required in the building at any one time (say two people taking showers or one person showering while a dishwasher and clothes washer are filling), etc.
    1. List all plumbing fixtures that use hot water and that may be run simultaneously in the building
    2. Determine the maximum hot water flow rate at each of these fixtures
    3. Make a realistic assumption about the chances that two or more of these fixtures really can be expected to operate simultaneously
    4. Add the effects of flow restrictors or other changes you are willing to make in hot water delivery rates - like low flow shower heads & faucets - be honest since kidding yourself about what flow rates you will accept will risk installing a water heater that is inadequate
    5. Add all of the simultaneous flow rates = Total gallons per hour or TGPH
    6. Check that that total is at least equal to or greater than any individual appliance or device that you may have left out of the "simultaneous" group and use the larger of those two numbers
  2. The temperature rise required - that is, the difference between the incoming cold water (that may be as low as or even lower than 40 degF in some locations) and the hot water temperature that is required (say 120 degF).
    1. Determine the coldest expected incoming water temperature to the building. This can be as low as 40 degF in winter in cold climates in North America; If you don't know this number use 50 degF for cool or cold climates. In hot climates (Arizona, South Texas, etc.) you can use 65F. [16]
    2. Determine the maximum temperature to which you want to heat your hot water, keeping in mind that if you are not using a point-of-use demand heater, there may be heat losses as water travels through building piping, but also keeping in mind that you don't want to scald anyone.

      See ANTI SCALD VALVES for advice on maximum hot water temperatures and on scald protection devices.

      If you are not sure, you can use 120F as a maximum hot water temperature for washing and bathing; special applications such as dishwashers and commercial washing facilities may use higher temperatures.
  3. Compare the building hot water temperature & flow rate with the capacity of the demand type tankless hot water heater appliance being considered. The demand water heater you are planning to install must meet your building usage requirements and for economy, and presuming you are ignoring peak hot water demands that exceed your sample data, then you may not want the unit to significantly exceed your requirements.

DOE example: simultaneously the building occupants will run a hot water faucet with a flow rate of 0.75 gallons (2.84 liters) per minute and a shower head with a flow rate of 2.5 gallons (9.46 liters) per minute. No one else is bathing, no dishwasher nor washing machine operation. The flow rate through the demand water heater would need to be at least 3.25 gallons (12.3 liters) per minute. [15][16]

Typically, a 70ºF (39ºC) water temperature rise is possible at a flow rate of 5 gallons per minute through gas-fired demand water heaters and 2 gallons per minute through electric ones. [15][16][17]


...

Continue reading  at TANKLESS WATER HEATERS or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.

Or see these

Recommended Articles

Suggested citation for this web page

TANKLESS WATER HEATER SIZE REQUIREMENTS at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

Or see this

INDEX to RELATED ARTICLES: ARTICLE INDEX to WATER HEATERS

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Ask a Question or Search InspectApedia

Share this article:

Questions & answers or comments about how to determine the size of tankless or demand water heater needed.

Search the InspectApedia website

Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.