Building Inspection, Diagnosis & Repair Info

Heating oil filter at the oil burner (C) Daniel Friedman How to Change the Oil Filter Cartridge on an Oil Burner

  • POST a QUESTION or COMMENT about installing, servicing, and repairing oil filters used on oil-fired heating equipment & water heaters

Heating oil filter change:

Step by Step Oil Filter Change Procedure. This article series describes the installation, use, maintenance, and repair of oil filters used on oil-fired boilers, furnaces, and water heaters.

We discuss tracking down air and oil leaks at or near the oil filter canister and we describe proper oil filter location and problems to check for during oil filter cartridge changes.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?





ADVERTISEMENT





How to Change a Heating Oil Filter:

General heating oil filter canister Model 1A-25B that uses the 1A-30 oil filter (C) InspectApedia.comThe oil filter cartridge should be changed during oil heating equipment annual cleaning, service, and tune-up.

You should not have to change oil filter cartridges more often. If the cartridge clogs and leads to service calls or heat loss between annual service calls then we suspect the oil tank is contaminated with water or sludge - problems that need to be corrected at the oil tank.

Illustration: the General 1A-25B heating oil filter canister, used on many domestic oil burners. This canister or "container" receives the General 1A-30 oil filter cartridge or an equivalent.

Article Contents

...

Step by Step Procedure for Servicing the Oil Burner Oil Filter Cartridge

The procedure for changing the oil filter cartridge is simple, but if it's performed improperly you could be left with no heat.

  1. Turn off electrical power to the heating appliance (boiler, furnace, water heater) whose oil filter is to be serviced
  2. Place a catch pan or basin below the canister to catch any oil spills or drips
  3. Turn off oil supply to the system by closing the fire safety valve that should be located between the oil filter and the oil feeder supply line from the oil tank.

    If, as it should be, the valve is a fire-safety-valve it includes a spring-loaded fusible link that closes the valve in case of fire.

    Turning the fire-safety-valve handle CLOCKWISE (to the right) will CLOSE the valve.

    Doing this, you'll see the round screw stem move downwards in the valve, as the valve gate is closing.


    These fire safety valves work differently from typical plumbing shutoff valves.

    Turning the round handle COUNTER-CLOCKWISE (to the left) OPENS the valve.

    When turning the valve to the left to open the valve you will feel some resistance as you're lifting the valve's internal core against spring pressure, and you'll see the valve stem rise up through the round handle.

    The reason the valve works this way is that in the open position the valve stem's compressed spring combined with a fusible link, will push the valve face "down" to "close" the valve in the event of a fire.

  4. Remove the oil filter canister base:

    For oil canisters with a center bolt such as the unit shown just above, loosen the bolt found in the center of the canister top and remove it.

    Take care not to lose the fiber washer that seals the canister bolt and take care not to lose or damage the O-ring that seals the canister base to the canister lid.

    Watch out: for oil filter canisters that are supported only by oil piping you'll be wise to support the canister lid or assembly whenever loosening parts.

    Otherwise you may twist, bend, and cause leaks in the oil supply piping. Use two wrenches to loosen or tighten the canister bolt: one on the bolt itself and one on the rectangular projection at the canister lid inlet or outlet side. Leaks here cause oil burner startup bang, puffbacks, loss of heat. Details are

    at OIL SUPPLY LINE PIPING LEAKS.

    Watch out: the canister bottom may simply fall off at this point - you will want to catch it to avoid unnecessary oil spillage. Other oil filter canisters may lack the bolt and may have to be opened by un-screwing the canister base from the top.
  5. Remove dirty oil filter cartridge and place it in a plastic bag for suitable disposal along with any waste oil and sludge collected during this process.
  6. Clean the oil filter canister: remove any oil sludge, dirt, debris from the bottom of the oil filter canister base.

    Check for water contamination in the oil tank when changing the oil filter cartridge.

    Water contamination in oil tanks can be detected by examining the bottom of the oil filter canister.

    If you see actual water, or more likely rusty red sludge, that may be good evidence that water from the oil storage tank has been trapped in and rested in the bottom of the oil filter canister.

    For details

    see OIL TANK WATER CONTAMINATION
  7. Heating oil filter cartridge & gaskets © D Friedman at InspectApedia.com
  8. Insert the new oil filter cartridge into the canister base.

    If your oil filter replacement package included a new O-ring for the canister base-to-lid seal, use it to replace the old O-ring that we told you to save in step 4.

    Our photo (left) shows a typical heating oil canister filter and the gaskets that are packaged with it.

    The General 1A-30 replacement oil filter cartridge shown at the left of our photo is in most canisters inserted with the screen up where it fits into a recess in the canister lid.

    This filter cartridge fits the General 1A-25B oil filter canister as well as some other manufacturer's brands of an equivalent size.

    That large round gasket is used to seal between the oil filter canister top and the base.

    Inside the large gasket we show two smaller ones. The smallest red gasket is used under the air bleed screw found on the top of the oil canister, and the larger red gasket is used under the mounting bolt that secures the oil filter canister base to its top.
  9. Heating oil filter canister reassembly:

    Carefully, keeping the filter cartridge centered in the canister base, place the canister base up under the canister lid in proper position.
  10. Replace the heating oil filter canister mounting bolt 

    (and a new fiber washer if one was provided in your oil filter cartridge kit) to secure the canister base to the lid, tightening the bolt securely but not so tight as to damage threads. If your canister does not use a center bolt the base usually assembles by screwing in in place into the lid.

    Watch out: as we warned above, for oil filter canisters that are supported only by oil piping you'll be wise to support the canister lid or assembly whenever tightening parts. Otherwise you may twist, bend, and cause leaks in the oil supply piping. Details are

    at OIL LINE LEAKS - Oil Line leaks found.
  11. Open the oil supply valve to allow oil to enter the oil filter canister and then
  12. Bleed air from the oil filter canister using the procedure we detail just below

    at OIL FILTER AIR BLEED STEPS. Use a new fiber washer for the air bleeder screw if one was provided in your heating oil filter kit. Remember to close the bleed screw at the end of this procedure.
  13. Turn on electrical power to the heating appliance and
  14. Allow the oil burner to run to assure that the system starts and runs properly.
  15. Leak check: Check the oil piping and the oil filter canister top, center bolt and air bleeder bolt and any nearby fittings for evidence of oil leaks.

    Details of just where leaks occur at or around heating oil filters are

    at OIL SUPPLY LINE PIPING LEAKS
    and

    at OIL FILTER LEAK POINTS.
  16. Dispose of heating oil: if you collected heating oil in your drip pan and see that the oil is clean you can simply pour it into your oil tank through the filler pipe. Don't pour sludge, dirt, debris into the tank however.

...

Bleed Air from the Heating Oil Filter Canister after an Oil Filter Cartridge Change

Oil canister air bleed screw (C) D Friedman & E.S. Once you have installed the new oil filter cartridge inside the canister you will need to bleed air out of the canister and filter before restoring the system to service.

If your heating oil tank is at a level higher than that of the filter itself this is an easy task as oil may flow from the tank through the filter without even having to run the oil burner.

But most heating service techs simply turn up the heat to cause the oil burner to turn on, bypassing the cad cell relay if necessary to keep the burner running even before actual flame ignition.

Watch out: do not try this burner-on method if you don't have the necessary training: pouring a dose of un-burned oil into the combustion chamber is dangerous and risks a puffback.

With your catch-basin below the oil filter canister, simply loosen or remove the air bleeder screw located on the canister top just before the canister outlet fitting (red arrow in our photo at left, courtesy of reader E.S.).

Then open the oil supply valve to permit oil to flow from the oil tank into the canister. You may hear or feel air escaping at the air bleeder opening.

Once you see a clear flow of heating oil at the bleeder opening you can replace the screw that closes that port.

Watch out: don't forget to include the fiber washer that seals the screw to the canister head or you may have oil or air leaks at the canister.

...

Tips for the Follow-Up Check for Oil Leaks After Oil Filter Cartridge Change

Heating oil filter at the oil burner (C) Daniel FriedmanAfter any service procedure that disturbs oil line, filter, or burner oil piping fittings we recommend checking for evidence of oil leaks again after the system has been in use for a day or so, because slow leaks and small leaks in the oil piping system may not show up immediately.

Clean the floor beneath and around the heating oil filter and oil piping. Check back in a day or two for fresh heating oil spots on the floor (below left).

If you leave a clean paper towel below the oil filter and connectors it can make spotting an oil drip easier.

Fix any oil leaks immediately. An air leak into the oil piping system leads to improper oil burner operation, risking a dangerous puff-back, or loss of heat in the building.

Spin-on / off heating oil filter maintenance

Our reader asked:

The furnace oil filter changing instructions are for canister and not the spin-on cartridge pictured.
Are there separate instructions for removing and replacing a spin-on fuel filter cartridge (Gar-ber, Granby, etc)? 10/30/2014 Anonymous

Reply:

Thanks Anon for pointing out the need for this clarification. For a spin-on type oil filter cartridge the basic steps are the same: shut off the equipment, shut off the oil supply, place a pan to catch drips, remove and replace the filter. The central difference is that there is no center bolt to remove to drop the filter (as is the case with General Filters).

The mounting hardware for this filter is (as with other brands) specific to the filter brand, size, type. Gar-Ber filters,for example, include a die-cast metal head to which the oil lines are connected and to the under-side of which the Gar-Ber spin on heating oil filter screws on and off. The Gar-Ber filter head includes a port for a vacuum gauge and it also includes an air bleeder screw that serves the same function as we describe in the article above.

Gar-Ber spin-on / off oil filters are distributed by General Filters - generalfilters.com

Granby spin-on / off oil filters (Granby EX200-999) are distributed by Granby Industries - granbyindustries.com and also provide mounting hardware that connects to heating oil lines and that also includes an air bleeder plug. Granby also sells a traditional center-bolt oil filter as well. Granby notes that their 10 micron spin-on oil filter works with all spin-on filter heads of the same type and fit the CGF-10, Kerr K10, Purolator Per-103 and Nozzle Guard NG1500-M oil filter mounts.

Granby's instructions include this helpful note that gives some heating oil line vacuum reference points

"SERVICE: Replace the filter element at the beginning of each heating season, or when running vacuum exceeds 6’’ Hg on one-pipe systems or 15’’Hg on two-pipe systems."

...




ADVERTISEMENT





Reader Comments, Questions & Answers About The Article Above

Below you will find questions and answers previously posted on this page at its page bottom reader comment box.

Reader Q&A - also see RECOMMENDED ARTICLES & FAQs

...

Using a vacuum gauge to determine when to change the oil filter what should the reading be?

What should the pressure gauge located after the oil filter read when everything is running correctly?

My gauge is at 6 or 7 should the filter be replace? Ty Joe d On 2019-11-17 by deutgrass86@gmail.com

by (mod) - 4" or less for your system

Deut

On a single oil line single stage oil fuel unit heating system you shouldn't see a vacuum reading over 4" so your gauge is telling you to replace the filter if that's your system set-up.

Generally if there is a vacuum gauge between the oil filter and the fuel unit (oil pump) for a single stage fuel unit on a two-line oil system will show 3-10 inches of vacuum when the unit is running. If the vacuum level gets much above that then the oil filter probably needs replacing, or there's a blockage or clog in the oil line between tank and oil burner fuel unit (pump).

The service tech uses vacuum measurement to see if there are air leaks in the oil line or a bad fuel unit or similar problems.

A gauge on the high pressure line (out of the oil pump or fuel unit and in to the oil burner nozzle assembly) will read 100 psi or higher depending on how the fuel unit has been adjusted.

Watch out: pressure gauges in any location on a heating oil line or high pressure line between pump and burner should not be left permanently in place unless there are fittings to shut off oil pressure in to the gauge - to isolate it from the piping; my concern is that a burst gauge could spew oil all over and start a building fire or a leak at a gauge on the suction side of the pump may leak air into the system causing unsafe burner operation.

PLEASE read the details at OIL LINE VACUUM & PRESSURE TESTS where we include HEATING OIL LINE VACUUM TEST READING STANDARDS - you'll see that the acceptable oil line vaccum reading between the oil filter and the oil burner's fuel pump depends on the type of system installed.

Then don't hesitate to ask further questions. Daniel F.

...

What is the right oil filter size for me to use?

How do you know which size oil filter cartridge to use? Mine is the canister type with the felt insert but I've seen the cartridges in sizes 1A25B and 1A-30. There doesn't seem to be a size identified on the canister. On 2021-03-24 by Gene

Answer by (mod) - guide to il filter canisters & filter cartridges by brand, model, size

@Gene,



You may have been confused by people mixing names for the oil filter canister - the metal container that holds the actual heating oil filter and the actual oil filter cartridge that is inserted into the canister and through which the heating oil is filtered.

In your question " I've seen the cartridges in sizes 1A25B and 1A-30. " actually the 1A25B is the name for the oil filter canister (container) manufactured by General, ,and the 1A-30 is the oil filter itself that is inserted into that canister.

General 1A-30 oil filter cartridge (C) Inspectapedia.com

Above: The General 1A-25A oil filter canister and its standard filter cartridge, the 1A-30. This is the most-common residential oil burner filter size, though equivalents are available from other manufacturers.

For residential oil burners most use an oil filter canister (the can that holds the filter) such as the General Filter Model 1A-25A.
That filter uses cartridge refills in size 1A-30.

There are also substitute oil filters that will fit in that canister like the F15-48 that are perfectly compatible
Also compatible is the A-315 filter. What's different is the material but the size and operation of all 3 fit into the 1A-25A canister.

Some residential oil burners and some commercial burners use a larger capacity oil filter canister such as the General Model 2A-700B.
This larger canister uses as actual filter cartridge refills the 2A-710BG, or the 2A-710, 101, or RF2 oil filter cartridges.

I'll add illustrations of these oil filter canisters and filter cartridges to clarify their use.

Thanks for asking.

......

Below: the F15-48 oil filter cartridge from Westwood, and the rather different-looking

F-15-48 oil filter canister compatible with the 1A-30 for the General 1A-25A canister (C) InspectApedia.com

and next below,a same size Fulflo F10-209 oil filter cartridge, both of which fit and work in the General 1A-25A oil filter canister shown above.

F10-209 oil filter cartridge at Inspectapedia.com

Below: the larger General 2A-700B oil filter canister,

General 2A-700B larger oil filter canister at InspectApedia.com

and the General 2A-710 oil filter cartridge that fits into this larger canister.

Genearl 2A-710 oil filter cartridge at InspectApedia.com

Other heating oil filter brands

Above: the Parker Carborundum Fulflo process liquid filter model B3A-1/4" BD (Bottom drain), and below,

the General Aire from General Filters, Model 2A-17A similar to the General l 2A-700B above.

General 2A-17A epoxy-coated oil filter canister cited at Inspectapedia.com

The 2A-17A oil filter can be used with No. 2, 4, 5, an No. 6 fuiel oil. It is also used for othe roil filtering applications.

Below: the Westood heating F65 oil filter canister, also using a cast-iron top and the company's Pure-Oil filter element - filter cartridge Nos. F30-24, F35-12, F35-24.

Westwood F 65 Oil Filter Canister that uses filter eleme3nts No. F30-24, F35-12, F35-24 - cited at Inspectapedia.com

See this

  • GENERAL FUEL OIL FILTER CATALOG [PDF] (2015) General Filters, Inc. 43800 Grand River Avenue, Novi, Michigan 48375 USA, Tel: (866) 476-5101 Email: customerservice@generalfilters.cofor a more-exhaustive list of models and features of various heating oil and fuel oil filter products.

    Canadian contact: Canadian General Filters, Ltd. 400 Midwest Rd. Toronto, ON M1P3A9 (888) 216-9184 sales@cgfproducts.com
  • WESTWOOD OIL FILTER CATALOG [PDF] (2013) Westwood Co., Tel: 1-800-442-1630

...

I can't get the heating oil filter canister off!

General 2A-700B larger oil filter canister at InspectApedia.comThis is on so tight that I can't get it off. Do they make these kinds of filters
any more.

How can I get it off? On 2018-12-1 by Denise

Solution by (mod) -

Denise

Almost all of these oil filter canisters are disassembled by unscrewing the center release bolt you see in the filter canister top - the silver bolt pointed to by the red line at the canister top shown in my photo using a General 2A-700B as an example.

That bolt actually screws into a threaded receiver that's in the bottom of the black canister cartridge.

Once that bolt is removed, if the canister doesn't simply drop straight down, pry gently between the canister top and the canister base using a flat bladed screwdriver.

Watch out: to avoid unnecessary oil spills, work with a bucket or catch pan under the oil filter when removing it.

For the much less common oil filter canister that actually screws diretly into a lid, by holding the upper body of the oil filter with a suitable wrench and using an oil filter canister wrench on the bottom you should be able to unscrew the filter from the present installation. If not you could replace the entire assembly with a new oil filter assembly such as that made by General and shown here.

Or show me a photo of your oil filter canister and I can advise you further. - Daniel F.

...

When should I replace the cartridge in a heating oil filter?

Awesome info- thanks so much! How often should I replace the cartridge in my filter? Is this like a once-a-year kind of thing? Thanks in advance. On 2018-04-09 by Kevin

by (mod) - once a year at the annual service of your oil burner

Kevin

I replace the filter at annual oil burner service. If you find that the filter is clogging and having to be replaced more-often than that there's a problem to be found and fixed at the oil tank - at the very least by increasing the filter capacity so as to make it to annual service.

 

Thank you to our readers for their generous comments

Thank you for your valuable instructions and also for your forward thinking warnings. Cheers, On 2016-08-17 by David

...

Continue reading at OIL FILTER LEAK POINTS or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.

Or see

Heating Oil Filter Articles

Suggested citation for this web page

OIL FILTER CHANGE STEPS at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

Or see this

INDEX to RELATED ARTICLES: ARTICLE INDEX to HEATING OIL, OIL BURNERS, OIL FIRED HEATERS, OIL TANKS

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Ask a Question or Search InspectApedia

Share this article:

Search the InspectApedia website

Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.

Citations & Reviewers

In addition to any citations in the article above, a full list is available on request.

  • Audels Oil Burner Guide, Installation, Servicing, Repairing, Frank D. Graham, 1940's edition (obsolete). Updated versions of this guide are available in various editions, 1947, 1950, 1955, 1958, 1959, 1962, 1965, 1967, and at prices from around $3.00 to nearly $70.00 - useful for simple, clear, but not current, explanation of how heating equipment works. The original retail price was $1.00.
  • Dave Ferris - M&S Environmental Systems, Dutchess County, New York. Mr. Ferris was an HVAC expert. Personal communication to DJF 1987. Remove the firematic or fusible oil supply line valve on return oil-line side - in case of fire if this one closes first the pump continues to run, blows its seal, and sprays oil all over the fire. Proper installation is to have a fusible link valve only on the supply side, and to install a check valve on the return line to prevent back-siphonage from the tank.
  • "HUD Regulation for Manufactured Homes; Requirement that Heat-Tape not include a GFCI [ copy on file as /plumbing/GFCI_Heat_Tapes_HUD_CPSC_Letter1994.pdf ] - ", Meeting Log, US CPSC, HUD, Dennis McCoskrie, ESEE, 2/14/1994
  • [1] LeakLok™ blue thread sealant compound is available from Argo, Inc., 2610 Commerce Way, Vista CA 92083, tel: 800-854-1015. Quoting from the company's product literature:
    Leak Lock Blue Joint Sealing Compound 1.3 oz. tube Soft setting joint compound that seals threaded joints, gasket surfaces and mating surfaces. Resin-based brushable paste which remains permanently flexible, internal surfaces and fills voids. Excellent for use on metal and plastic materials subject to extreme vibrations.
  • Our recommended books about building & mechanical systems design, inspection, problem diagnosis, and repair, and about indoor environment and IAQ testing, diagnosis, and cleanup are at the InspectAPedia Bookstore. Also see our Book Reviews - InspectAPedia.
  • In addition to citations & references found in this article, see the research citations given at the end of the related articles found at our suggested

    CONTINUE READING or RECOMMENDED ARTICLES.


ADVERTISEMENT