Building Inspection, Diagnosis & Repair Info

Photograph of Photograph of a water pump pressure control switch with the cover offRelay Switch & Contactor FAQs

  • POST a QUESTION or COMMENT about contactor switch or relay switch noises in mechanical systems used in buildings or building air conditioners, heat pumps, water pumps or other equipment

Control relay switch chattering noise diagnosis and repair Q&A.

This article series discusses control relay switch chattering or rapid, repeated clicking noises, their cause, meaning, and repair.

Relay switches are widely used to control equipment found in or on buildings including air conditioning system or heat pump compressor/condenser unit compressor motors, fans, and in an air handler the blower fan used in forced air heating and air conditioning systems.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?





ADVERTISEMENT





Clicking or chattering electrical relay switch FAQs

White Rodgers ran relay switch (C) InspectApedia.com These questions and answers about clicking or chattering electrical control relays were posted originally

at RELAY CONTROL SWITCHES - be sure to see the diagnosis and repair advice given there.

On 2018-05-07 by Compressor

I just installed a new compressor on a heat pump. The compressor was working fine then it stopped and won't turn on. About every 30 seconds it tries to turn on for a sec then nothing for 30 secs then tries again.

On 2018-05-07 by (mod) - every 30 seconds it tries to turn on

Sounds like excessive head pressure, maybe a stuck TEV

How can I manually override the contactor relay on my boiler's aquastat?

I have a hot water boiler for radiators and the circulator pump only runs when the burner is on.

I want to be able to manually over-ride the contactor/relay with an external switch to have the ciruclator run continuously during very cold outside temps.

Can I simply add a typical single-pole light switch between the L1 L2 line in and the C1 C2 circulator control? If not, how else to do this? On 2018-01-04 by Paul

Circulator relay trouble in Minnesota

@Paul,
I've got the same issue up here in northern Minnesota. What image of the control system are you referring to in regard to the L1 L2 line and C1 C2 control? - On 2018-01-10 by Mike C -

Reply by (mod) - A chattering relay is most likely failed or failing; replace it, don't bypass it with an external switch.

Mike

A chattering relay is most likely failed or failing; in an emergency a short term repair is, with power off, to try to clean the contacts but it's difficult. SOME techs can replace a relay; most replace the whole control.

This illustration https://inspectapedia.com/heat/Honeywell_R8182D_Internals.jpg shows the two relays in a typical aquastat, one for the burner and one for the circulator.

The L1 L2 are the power or LINE-IN terminals

The C1 C2 are the wires that control the circulator

Those are shown in the lower right of the illustration found at this article:

That image is discussed a tAQUASTAT CONTROLS

That article includes links to PDF files that describe the installation and use of the aquastat.

Bottom line: you probably need a new relay or a new control.

Water pump relay won't turn on the pump

My water pump leaked for along time where the pressure gauge is and then my water pressure just stopped period no water at all. I'm getting power but no water, wires are everywhere relay switch isn't connecting to turn pump on ethier. HELP. On 2017-12-03 by Ronald Williams

Reply by (mod) - replace wet relays

Watch out: FOR safety turn off electrical power to the pump, then ask your electrician to replace the wet switch. And of coirse, fix the leak.

When the air turns on I hear a continuous non stop clicking sound

That's doesn't sound normal to me. I would ask for an investigation in repair by the service technician

An air conditioner repair man replaced the relay switch for a 24 VAC coil in the heating unit. Now whenever the air turns on I hear a continuous non stop clicking sound from the part. Is this normal or does it need to be fixed?
Thanks.On 2017-11-12 by Katherine

Reply by (mod) -

Katherine, also see our discussion of clicking relays in the page bottom COMMENTS about clicking aquastats at AQUASTAT CONTROLS inspectapedia.com/heat/Aquastats.php

...

Continue reading at RELAY CONTROL SWITCHES - topic home, or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.

Or see these

Recommended Articles

Suggested citation for this web page

RELAY CONTROL SWITCH FAQs at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

Or see this

INDEX to RELATED ARTICLES: ARTICLE INDEX to AIR CONDITIONING & HEAT PUMPS

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Or see

INDEX to RELATED ARTICLES: ARTICLE INDEX to BUILDING NOISE DIAGNOSIS

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Or see

INDEX to RELATED ARTICLES: ARTICLE INDEX to WATER SUPPLY, PUMPS TANKS WELLS

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Ask a Question or Search InspectApedia

Share this article:

Search the InspectApedia website

Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.

Citations & References

In addition to any citations in the article above, a full list is available on request.



ADVERTISEMENT