Q&A on clicking chattering relay switches in Air Conditioners, Heat Pumps, Water Pumps, & other controls
POST a QUESTION or COMMENT about contactor switch or relay switch noises in mechanical systems used in buildings or building air conditioners, heat pumps, water pumps or other equipment
Control relay switch chattering noise diagnosis and repair Q&A.
This article series discusses control relay switch chattering or rapid, repeated clicking noises, their cause, meaning, and repair.
Relay switches are widely used to control equipment found in or on buildings including air conditioning system or heat pump compressor/condenser unit compressor motors, fans, and in an air handler the blower fan used in forced air heating and air conditioning systems.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?
Clicking or chattering electrical relay switch FAQs
These questions and answers about clicking or chattering electrical control relays were posted originally
I just installed a new compressor on a heat pump. The compressor was working fine then it stopped and won't turn on. About every 30 seconds it tries to turn on for a sec then nothing for 30 secs then tries again.
On 2018-05-07 by (mod) - every 30 seconds it tries to turn on
Sounds like excessive head pressure, maybe a stuck TEV
How can I manually override the contactor relay on my boiler's aquastat?
I have a hot water boiler for radiators and the circulator pump only runs when the burner is on.
I want to be able to manually over-ride the contactor/relay with an external switch to have the ciruclator run continuously during very cold outside temps.
Can I simply add a typical single-pole light switch between the L1 L2 line in and the C1 C2 circulator control? If not, how else to do this? On 2018-01-04 by Paul
Circulator relay trouble in Minnesota
@Paul,
I've got the same issue up here in northern Minnesota. What image of the control system are you referring to in regard to the L1 L2 line and C1 C2 control? - On 2018-01-10 by Mike C
-
Reply by (mod) - A chattering relay is most likely failed or failing; replace it, don't bypass it with an external switch.
Mike
A chattering relay is most likely failed or failing; in an emergency a short term repair is, with power off, to try to clean the contacts but it's difficult. SOME techs can replace a relay; most replace the whole control.
This illustration https://inspectapedia.com/heat/Honeywell_R8182D_Internals.jpg shows the two relays in a typical aquastat, one for the burner and one for the circulator.
The L1 L2 are the power or LINE-IN terminals
The C1 C2 are the wires that control the circulator
Those are shown in the lower right of the illustration found at this article:
That article includes links to PDF files that describe the installation and use of the aquastat.
Bottom line: you probably need a new relay or a new control.
Water pump relay won't turn on the pump
My water pump leaked for along time where the pressure gauge is and then my water pressure just stopped period no water at all. I'm getting power but no water, wires are everywhere relay switch isn't connecting to turn pump on ethier. HELP. On 2017-12-03 by Ronald Williams
Reply by (mod) - replace wet relays
Watch out: FOR safety turn off electrical power to the pump, then ask your electrician to replace the wet switch. And of coirse, fix the leak.
When the air turns on I hear a continuous non stop clicking sound
That's doesn't sound normal to me. I would ask for an investigation in repair by the service technician
An air conditioner repair man replaced the relay switch for a 24 VAC coil in the heating unit. Now whenever the air turns on I hear a continuous non stop clicking sound from the part. Is this normal or does it need to be fixed?
Thanks.On 2017-11-12 by Katherine
Reply by (mod) -
Katherine, also see our discussion of clicking relays in the page bottom COMMENTS about clicking aquastats at AQUASTAT CONTROLS inspectapedia.com/heat/Aquastats.php
...
Continue reading at RELAY CONTROL SWITCHES - topic home, or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Ask a Question or Search InspectApedia
Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.
Search the InspectApedia website
Note: appearance of your Comment below may be delayed:if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.
Only one image can be added per comment but you can post as many comments, and therefore images, as you like.
You will not receive a notification when a response to your question has been posted. Please bookmark this page to make it easy for you to check back for our response.
Our Comment Box is provided by Countable Web Productions countable.ca
In addition to any citations in the article above, a full list is available on request.
"Solid State Relays Common Precautions" [PDF], Omron Management Center of America
2895 Greenspoint Parkway, Suite 100, Hoffman Estates, IL 60169
TEL: 1-224-520-7650 FAX: 1-224-520-7680,
OMRON Electronics LLC (Omron Automation - Americas)
2895 Greenspoint Parkway, Suite 200, Hoffman Estates, IL 60169
TEL: 1-847-843-7900 FAX: 1-847-843-8568/7787
Omron Corporation has offices world wide, retrieved 2016/.08/03, original source: https://www.omron.com/ecb/products/pdf/precautions_ssr.pdf
Barrett, P. G., and P. A. Collins. "Troubleshooting low voltage controls." In Pulp and Paper Industry Technical Conference, 1992., Conference Record of 1992 Annual, pp. 103-107. IEEE, 1992.
Abstract: Control components are a vital aspect of any industrial process. It is argued that costly shutdowns can be minimized or eliminated through a complete understanding of the control devices along with a conscientious maintenance program and troubleshooting procedure. The electromechanical design of various types of starters, contactors, and overload relays are analyzed in terms of operation, application maintenance and troubleshooting. Specific suggestions for troubleshooting procedures are offered for various problem scenarios.
Carfagno, S. P., and G. Erich Heberlein. "A Study of the Effect of Aging on the Operation of Switching Devices." IEEE Transactions on Power Apparatus and Systems 6 (1980): 2272-2280.
Abstract: An experimental study was conducted to determine whether equipment aging affects the vulnerability of electric switching devices to malfunction caused by vibratory stresses in the range of seismic frequencies and acceleration amplitudes. The study included a vibration test before and after a program of accelerated aging designed to simulate forty years of service in areas outside the containment of a nuclear power generating station. Gamma irradiation, thermal aging, electrical/mechanical cycling and simulation of operating basis earth- quakes were included in the program of accelerated aging. Malfunction was defined as spurious opening or closing of contacts for times in excess of 1 ms during the vibration tests.
Elphick, Sean, Vic Smith, Vic Gosbell, Gerrard Drury, and Sarath Perera. "Voltage sag susceptibility of 230 V equipment." IET Generation, Transmission & Distribution 7, no. 6 (2013): 576-583.
Feldbauer, B. "The design of contactors with regard to their industrial application." Electrical Engineers-Part II: Power Engineering, Journal of the Institution of 95, no. 46 (1948): 439-448.
Abstract: Modern contactor design is reviewed and reference is made to the influence which various applications of contactor type control gear have had on design and development. After a general survey the special considerations appertaining to motor-control duty are examined in detail, having due regard to the extreme cases which frequently occur in practice. Arc control and contact developments are mentioned, and a short discussion of the oil-immersed contactor follows with particular reference to its use in chemical plants and for high voltage. Some special contactor designs are discussed, as well as the problems arising in connection with the control of electric furnaces. A short summary of the desirable features of contactor auxiliary switches concludes the paper.
Haines, Roger W., and Douglas C. Hittle. "Electric and Electronic Control Devices." In Control Systems for Heating, Ventilating, and Air Conditioning, pp. 42-67. Springer US, 1993.
Herman, Stephen. Electric motor control. Cengage Learning, 2014.
Knights, D. S. "Relays & Contacts." In Component Reliability, pp. 45-56. Macmillan Education UK, 1971.
Kreveld, Phil. "Relays and Contractors: From Little Things Big Things Grow." Electrical Connection Winter Quarter 2008 (2008): 28.
Lee, Yim-Shu, Hon-Chee So, and Martin HL Chow. "Design of AC voltage sag compensators." In Power Electronics and Motion Control Conference, 2009. IPEMC'09. IEEE 6th International, pp. 2587-2590. IEEE, 2009.
Abstract: AC operated electronic equipment are vulnerable to momentary losses of AC voltage, which are known as voltage sags. Voltage sags are commonly caused by lightning, accidental short circuit, loose connection, starting of large motors (or air-conditioners) or abnormal use of the AC mains. In sensitive and critical applications, such as semiconductor material processing and medical operation, voltage sags may result in serious problems. In order to tackle this problem, the Semiconductor Equipment and Materials International (SEMI) defined, in 1996, a voltage sag immunity standard, known as SEMI F47-0200, for semiconductor processing equipment manufacturers to conform to. Equipment compliant to this standard must have the specified immunity characteristics against voltage sags without the use of batteries. Based on the experience learned, the standard was redefined, in 2006, as SEMI F47-0706. It is expected that new semiconductor processing equipment will be designed to be compliant to the new standard. It is also likely that the SEMI F47-0706 requirement will be extended to other application areas. This paper describes the design of voltage sag compensators which can be operated in conjunction with a piece of equipment for SEMI F47 compliance. The voltage sag compensators described can provide sine-wave AC backup power to enable electronic equipment to meet the SEMI F47-0706 standard and to tolerate 100% momentary loss of AC mains voltage.
National Electrical Code (NEC) for the U.S., Article 430 Air Conditioning and Refrigerating Equipment
National Electrical Code (NEC) for the U.S., Article 440 Air Conditioning and Refrigerating Equipment
Taylor, Carson W. "Concepts of undervoltage load shedding for voltage stability." IEEE Transactions on Power Delivery 7, no. 2 (1992): 480-488.
Our recommended books about building & mechanical systems design, inspection, problem diagnosis, and repair, and about indoor environment and IAQ testing, diagnosis, and cleanup are at the InspectAPedia Bookstore. Also see our Book Reviews - InspectAPedia.
In addition to citations & references found in this article, see the research citations given at the end of the related articles found at our suggested
Carson, Dunlop & Associates Ltd., 120 Carlton Street Suite 407, Toronto ON M5A 4K2. Tel: (416) 964-9415 1-800-268-7070 Email: info@carsondunlop.com. Alan Carson is a past president of ASHI, the American Society of Home Inspectors.
Carson Dunlop Associates provides extensive home inspection education and report writing material. In gratitude we provide links to tsome Carson Dunlop Associates products and services.