White Rodgers or Emerson Thermostat wiring reference chart - simplest case two-wire thermostat (C) Daniel Friedman Q&A on How Wire an Emerson or White Rodgers Room Thermostat

Q&A on making the right thermostat wiring connections for the White Rodgers brand of room thermostats.

This article series includes a table showing the proper wire connections nearly all types of White Rodgers room thermostats, new and old, used to control heating or air conditioning equipment, including the White Rodgers F90 2-wire and 3-wire thermostat installations.

Photo at page top: a vintage White Rodgers 1F56-444 room thermostat.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?





ADVERTISEMENT





White Rodgers Thermostat Wiring Guide FAQs

Emerson White Rodgers 1F80 series thermostats typical wiring diagrams at Inspectapedia.com cited in detail in this article

These questions & answers about wiring a White Rodgers thermostat (often spelled White Rogers thermostat) were posted originally

at THERMOSTAT WIRING WHITE RODGERS - you will want to check out the WR thermostat wiring tables and connections described there.

Where to find a rodgers thermostat wiring diagram

I need a white rodgers thermostat wiring diagram 1h11g 101 On 2018-05-15 by Ahmed

by (mod) - white rodgers thermostat wiring diagram 1h11g 101

Ahmed

Please attach a photo to a comment giving us an image of your White Rodgers 1H series thermostat and additional photos of any labels or markings on the thermostat including inside its cover.

While we have no trouble finding White Rodgers 1E series and 1F series and other thermostat models - all shown at THERMOSTAT WIRING WHITE RODGERS - I've not found the one you cited.

 

How do I Fix a White Rodgers 1E30-910 thermostat that won't turn off

1E30-910 (discontinued) turned off thermostat but cool air has been blowing constantly past 3 days.... New thermostat? How to stop it? Please help!

0-910 thermostat but cool air has been blowing constantly past 3 days On 2018-05-09 by Anisa logan

Moderator reply: here are the repair steps to follow

Anisa

Please see the step by step repair instructions at


To see the common causes and repairs that you might need.

Also check for shorted thermostat wires.

Below is a link to the installation & wiring instructions for the White Rodgers F56N-444 thermostat that replaces your White Rodgers 1F35-910 as the wiring instructions there might help you out.

White-Rodgers-F56N-444-Installation-Manual [PDF]

How do I connect a White Rodgers 1F35-910 thermostat to a Honeywell Thermostat?

Trying to connect a White Rodgers 1F35-910 (Red wire (W4), white wire (R5) and Green Wire (Y6) to a Honeywell Pro 3000. I connected the Red to W, White to R/Rc (jumper) and Green to G. Hot water boiler system.

The boiler furnace stays on for 15 secs, then shuts off. Does this repeatedly. But doesn't with the mercury. Is there something else I need to do? On 2018-01-23 by Shawn

by (mod) - Don't confuse wiring for thermostats with wiring for heating zone valves

Shawn

The Honeywell Pro 3000 is a non-probrammable wall thermostat.

The White Rodgers 1F35-910 is a (now discontinued) wall thermostat designed for three-wire zone valves.

I don't understand why you would be trying to connect one thermostat to another. So I suspect I don't have the right understanding of your question.

Zone valve wiring instructions for pretty much all types of zone valves begin at

ZONE VALVE MANUALS & WIRING INDEX

The manual for your Honeywell Pro 3000 thermostat gives the proper wiring connections and is at

https://customer.honeywell.com/resources/techlit/TechLitDocuments/69-0000s/69-1929EFS.pdf

Below is an example of a simple 3-wire Flair zone valve illustration widely found across the web at sites that I see have lifted the illustration from our original work.

Flair zone valve wiring diagram shows thermostat wire connections (C) InspectApedia.com

Audible alarm on a white Rodgers 1f94-371 ?

which wire controls the audible alarm on my white Rodgers 1f94-371 On 2015-05-06 by dj

by (mod) - white Rodgers 1f94-371 doesn't show an alarm feature

DJ I looked at two copies of the owners and installation manual for the White Rodgers 1F94-371 control and could not find mention of an alarm feature.


How do I Replace a round Honeywell T87 with a Digital Honeywell Thermostat

Hello - I am replacing a round Honeywell thermostat with a non-programmable digital Honeywell unit. I have a hot water system with multiple zones and with no air conditioning.

There are three wires at the thermostat. On the old round unit the red wire went to the R terminal, the white wire went to the w terminal and a green wire went to B terminal. I hooked up the new stat the same way but it would not work.

If I selected "fan on" instead of "fan auto" the zone would heat up but would not shut off (hot water kept flowing even if I selected a temp below room temp). Appreciate your help. - Patrick - 1/20/12

Reply:

Patrick, typically the three wire thermostat hookups would be exactly the same for the old and new thermostats.

For details of wiring a typical and simple digital Honeywell thermostat,

see Honeywell 5-2 Day Programmable Thermostat - RTH2300B1012.

For help in understanding the wiring of your old thermostat,

see Three-Wire Honeywell Wall T87-F type Thermostat wiring and also

see Generic HVAC Thermostat Control Wiring Points

 

Steps in Replacing a mercury thermostat with a digital unit

I am replacing an old mercury thermostat with a digital. my system is a heat pump. my neighbor gave me the digital, no instructions, no box. I'm trying to decide if this is even a heat pump compatible thermostat. on the therm it has c, g, rc, rh (which are linked by a black wire.)

w, y, b, and o. coming out of my wall is, white connected on old therm w2, yellow connected to y, green conn g, black conn e, red to r, blue to b and bro to x. any help would be great. - Kurt 6/4/12

Reply:

Kurt, as you see in the examples at For help in understanding the wiring of your old thermostat,

see Three-Wire Honeywell Wall T87-F type Thermostat wiring and also

see Generic HVAC Thermostat Control Wiring Points.

Many thermostat wiring setups are straightforward or "cookbook" but why not find the brand name on your thermostat and then you can obtain the installation instructions right from the manufacturer?

Also, Honeywell's thermostat replacement advice (and most likely that of all thermostat manufacturers) warns:

Watch out: MERCURY NOTICE: Do not put your old thermostat in the trash if it contains mercury in a sealed tube. Contact your local waste management authority for instructions regarding recycling and proper disposal.[5]

 

Wiring for 2-wire Lennox thermostat conversion to White Rodgers Thermostat

I have a old lennox 2wire red and white wires from the old thermostat I bought a white rodgers up400c thermostat where do I install the red and white wires to my new thermostat (Nov 22, 2014) Dale

Reply:

Dale that's tricky since you describe 4 wires, 2 red and 2 white we don't know which does what without doing some testing.

See in the ARTICLE INDEX

THERMOSTAT WIRE FUNCTIONS

and

THERMOSTAT WIRING TIPS & COLOR CODES - where you will find a discussion titled SHORTING THERMOSTAT WIRES to ID R W B

...

Continue reading at THERMOSTAT WIRING WHITE RODGERS - topic home, or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.

Or see

Suggested citation for this web page

THERMOSTAT WIRING WHITE RODGERS FAQs at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

Or see this

INDEX to RELATED ARTICLES: ARTICLE INDEX to HVAC THERMOSTATS

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Ask a Question or Search InspectApedia

Share this article:

Search the InspectApedia website

Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.