Building Inspection, Diagnosis & Repair Info

Parts explosion of a B&G pressure reducing valve - at Inspectapedia.comPressure Reducing Valve Disassembly

Heating boiler water feeder valve disassembly.

Page to sketch: parts list for a typical B&G pressure reducing valve.

[Click to enlarge the page top image]

This article series explains the operation and repair of hot water boiler (hydronic heat) pressure reducing valves and types of manual and automatic water feeder valves used on hot water heating boilers, including when and how to add makeup water to a boiler.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?





ADVERTISEMENT





Take Apart a Hydronic (hot water) Heating Boiler Pressure Reduce Valve

Clogged pressure reducer valve won't feed water to the boiler B&G B-8 (C) Daniel Friedman at InspectApedia.com

Here we illustrate complete dis-assembly of an older B&G B-8 pressure reducing valve.

We found this valve on a hot water heating system in a Two Harbors Minnesota home built in the 1960s.

This was an original pressure reducer that had served more-or-less for over fifty years.

I say more-or-less because nobody knows just when this valve stopped feeding water to the boiler.

On a heating service call, working with the local heating repair technician, we had observed some loss of water in the heating system.

After draining the boiler to remove pressure so that we could replace air bleeder valves and a bad TP relief valve on the boiler, we turned water back on to the boiler.

Nothing happened: no water entered the boiler.

While the B&B pressure reducer shown here can be cleaned or repaired in the field, the technician declined to do so.

Instead we bought and installed a new pressure reducing valve.

Later back in our Poughkeepsie workshop we decided to dis-assemble the valve completely in order to examine conditions in a 50+ year old B&G pressure regulator.

My first discovery was that the technician was much smarter than I was.

Steps in Complete Disassembly of a B&G Pressure Reducer

Loosen the lock nut on the pressure reducing valve adjustment screw (C) Daniel Friedman at InspectApedia.com

Above: loosening the lock nut on the pressure reducer adjustment screw. To access this screw you may have to remove a plastic cap on the valve top.

Watch out: loosening or even removing this nut will NOT permit dis-assembly of the valve. This adjustment screw is turned clockwise (in) to increase the feed pressure to the boiler, or counter-clockwise (out) to reduce the water feed pressure to the boiler.

Pressure reducer lock nut loosened (C) Daniel Friedman at InspectApedia.com

Normally the pressure reducing valve is preset at the factory to feed water to a boiler when boiler pressure drops below 12 psi

If you need to adjust the pressure of your boiler's pressure reducer ("water feeder") see

WATER PRESSURE SETTING FOR A PRESSURE-REDUCING VALVE OR WATER FEEDER ON A HOT WATER HEATING SYSTEM

Watch out: I do NOT recommend that you try complete dis-assembly of a pressure reducing or water feed valve.

The photos and notes included here are for educational purposes to show novices the internal workings of a typical and normally rock-solid pressure reducer made by B&G. But if you rip apart a valve as I do here you may not get it back together to work safely.

Starting

at PRESSURE REDUCING VALVE (BOILER) CLOG REPAIR I show removing the pressure reducer strainer nut to remove and clean the strainer.

If replacing or cleaning the pressure reducer strainer doesn't get the valve working again I suspect its internal valve is jammed, as I will illustrate.

In that case it's best to repalce the entire valve - and less time and cost in labor and materials.

Below I begin actual dis-assembly of the B&G Pressure Reducer.

B&G pressure reducing valve disassembly - NOT recommended (C) Daniel Friedman at InspectApedia.com

All of the valve body screws are removed and set aside.

Below, with the body screws removed I am prying the valve upper and lower body halves apart.

Prying the pressure reducer body apart (C) Daniel Friedman at Inspectapedia.com

Below I'm pulling the pressure reducer apart.

In the photo left you can see the heavy spring that, adjusted by the screw shown above and apressure plate I'll show next the pressure on the diaphraghm at the valve centr is adjusted.

That diaphraghm in turn will permt the water flow valve assembly (shown later) to open or close.

Pressure reducer valve internal parts dis-assembly (C) Daniel Friedman at Inspectapedia.com

Below from left to right you can see the pressure reducer valve spring cap and inside it the point of the screw that is turned up or down to press on the round pressure plate that in turn presses a spring that in turn presses on a metal plate affixed to the center of the pressure reducer rubber diaphraghm.

Pressure managing components of a pressure reducing valve (C) Daniel Friedman at InspectApedia.com

Water pressure on the supply side (under the valve, connected to building water piping) wants to press the diaphraghm up to open the valve.

Spring pressure on the upper side of the diaphraghm presses the diaphraghm down to close the valve.

Below: to expose the actual water valve that is operated by the diaphraghm I had to loosen the lock screw shown below and later un-screw the water valve from the valve body (shown later).

Pressure reducer valve internal parts dis-assembly (C) Daniel Friedman at Inspectapedia.com

Below, with the pressure plate of the diaphraghm removed we see the centter of the valve and the upper side of the actual water control valve.

Pressure reducer valve internal parts dis-assembly (C) Daniel Friedman at Inspectapedia.com

Below I've removed the rubber cover to show both the water control valve (center) and the water flow opening in the valve's body.

When the water valve is pushed up by water pressure (against spring pressure), water can pass through the water valve (shown below) and the valve body opening to enter the boiler.

Pressure reducer valve internal parts dis-assembly (C) Daniel Friedman at Inspectapedia.com

Below my screwdriver points to the actual water flow valve that is controlled by the pressure reducer diaphraghm.

Pressure reducer valve internal parts dis-assembly (C) Daniel Friedman at Inspectapedia.com

Below, after much fighting, I've managed to un-screw and remove the actual water flow valve of the pressure reducing valvfe.

Pressure reducer valve internal parts dis-assembly (C) Daniel Friedman at Inspectapedia.com

Below: I show the valve main water flow openings in the valve center (controlled by the water valve detailed later) and the oval opening in the side of the valve body.

Pressure reducer valve internal parts dis-assembly (C) Daniel Friedman at Inspectapedia.com

Below is the pressure reducer water flow valve in its open position.

Pressure reducer valve internal parts dis-assembly (C) Daniel Friedman at Inspectapedia.com

Above: water can flow under the valve's under-side stopper and through the valve outlet disc on its upper side.

In this position spring pressure is greater than water pressure so water can pass through the valve into the boiler.

Below I show the pressure reducer's water flow control valve in its "closed" position.

Pressure reducer valve internal parts dis-assembly (C) Daniel Friedman at Inspectapedia.com

In this position the valve's stopper head on its under-side (right side in the photo) is closed against the valve body screw and its disc has moved upwards against spring pressure. Water pressure is greater than spring pressure in this position.

This valve would not move freely between open and closed when I first dis-assembled it. I had to pry and wiggle to get the parts moving to make these photos.

That would explain why even if we had replaced the clogged strainer on this pressure reducing valve it would still not have worked.

The service tech, in insisting on simply replacing the valve, was dead right.

Pressure Reducer & Flow Control Valve Manuals


...

Continue reading at PRESSURE REDUCER / WATER FEED VALVE, BOILER - topic home, or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.

Or see these

Recommended Articles

Suggested citation for this web page

PRESSURE REDUCING VALVE DISASSEMBLY at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

Or see this

INDEX to RELATED ARTICLES: ARTICLE INDEX to HEATING SYSTEMS

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Ask a Question or Search InspectApedia

Share this article:

Search the InspectApedia website

Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.

Citations & References

In addition to any citations in the article above, a full list is available on request.



ADVERTISEMENT