Building Inspection, Diagnosis & Repair Info

Clogged pressure reducer valve won't feed water to the boiler B&G B-8 (C) Daniel Friedman at InspectApedia.comClogged Pressure Reducing Valve Repair

Heating boiler water feeder valve clogged strainer replacement.

This article series illustrates how to diagnoes and fix hot water boiler (hydronic heat) pressure reducing valves and types of manual and automatic water feeder valves used on hot water heating boilers, including when and how to add makeup water to a boiler.

Page top photo: The data tag on this pressure reducer/water feeder valve identifies it as a B&G (Bell & Gossett) No. 8, a combination pressure reducer and water feeder valve model 110199LF for hydronic (hot water) heating boilers. Typically this valve comes factory set to provide water to the boiler at 12 psi.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?





ADVERTISEMENT





Hydronic (hot water) Heating Boiler Pressure Reducer Valve Repair

Use a 1 1/4" wrench to remove the pressure reducer strainer retaining nut (C) Daniel Friedman at Inspectapedia.com

Symptoms of a Clogged Strainer in the Boiler Water Feeder/Pressure-Reducer Valve

If you find that the pressure in a residential heating boiler (hydronic or "hot water" heat) falls below the typical 12 psi level it's possible that the culprit is simply a clogged strainer at the "automatic" water feeder/pressure-reducer valve that is found on the water supply line on most heating boilers.

Here we illustrate the replacement of a clogged strainer in the bottom of an older B&G B-8 pressure reducing valve.

We found this valve on a hot water heating system in a Two Harbors Minnesota home built in the 1960s.

This was an original pressure reducer that had served more-or-less for over fifty years.

How to Remove the Pressure Reducer Strainer Nut to Inspect the Strainer

On a typical B&G pressure reducing valve (aka "water feeder" to the dismay of the manufactuer) there is a strainer in the bottom of the valve. To remove it one needs to remove the strainer nut.

It was plain hell just trying to remove the pressure-reducer strainer retaining nut on this 50-year old valve.

Using an adjustable wrench, as carried by most service techs, is going to give a too-short wrench handle, not enough torque, and you'll probably round off the nut facets.

I used a longer 1 1/4" box wrench. In my photo above I've flipped over the wrench to connect the open-end to the strainer nut so that you can see the size markings. But using the closed-end of a box wrench is most-secure.

With the nut removed you can see the strainer inside the pressure reducer valve. Along with rust and crud.

Clogged pressure reducer valve won't feed water to the boiler B&G B-8 (C) Daniel Friedman at InspectApedia.com

I also had a devil of a time getting this clogged old strainer out of the valve - shown in more detail below.

Later when I disassembled the entire pressure reducer I also found that the valve inside the pressure reducer was frozen solid.

Even replacing the strainer wouldn't have fixed this valve.

Details of the jammed water valve in the pressure reducer are shown in this separate article:

PRESSURE REDUCING VALVE DISASSEMBLY - not something that I recommend.

Just below we show the location of the pressure reducer strainer and the steps in replacing it.

Unlike complete disassembly, strainer cleaning or replacement is a recommended service procedure for pressure reducing valves on boilers.

Steps in Replacing or Cleaning a Clogged Pressure Reducer Strainer

Clogged pressure reducer valve won't feed water to the boiler B&G B-8 (C) Daniel Friedman at InspectApedia.com

Photo: a very clogged strainer in a B&G B-8 pressure reducing valve.

How to Check for or Fix a Clogged Strainer in a Pressure Reducer/Feeder Valve

If the pressure reducer will not feed enough water into the boiler to reach the desired cold-pressure setting, before messing with re-adjusting the valve's feed pressure nut and screw, consider that the internal strainer in the valve may have become clogged.

  1. Turn off the cold water

     supply valve at the inlet side of the pressure reducing valveTurn off the heating boiler -

    set the electrical service switch to OFF to shut down the entire system.
  2. Remove all pressure and temperature

     from the heating system to allow safe work on the pressure reducing valve

    Watch out: water in the heating boiler may be at dangerous high pressure or high temperature.

    Before proceeding to work on the pressure reducer valve you must either reduce the heating system internal water pressure to zero, OR you must isolate the pressure reducing valve from the rest of the the heating system.

    Leave the system drain valve open and allow the heating system to cool to a safe temperature - below 100 °F. Otherwise you risk serious injury or death or property damage.
  3. Loosen and remove the strainer nut located

    on the bottom of the pressure reducing valve

Use a 1 1/4" wrench to remove the pressure reducer strainer retaining nut (C) Daniel Friedman at Inspectapedia.com

  1. Remove and clean or replace the strainer

    found in that opening

Clogged pressure reducer valve won't feed water to the boiler B&G B-8 (C) Daniel Friedman at InspectApedia.com

It was impossible to get the strainer out of the pressure reducer without destroying it.

Damaged pressure reducer strainer needs replacement (C) Daniel Friedman at InspectApedia.com

I had to pry it out with a screwdriver and pliers. In my photo above you can see the side of the strainer is a bit bent.

Also as I show below, the strainer was badly clogged with scale and rust. I could have perhaps cleaned it by soaking it in vinegar.

Damaged pressure reducer strainer needs replacement (C) Daniel Friedman at InspectApedia.com

But best would be to install a new strainer.

That's why B&G's PRESSURE REDUCER REPAIR KIT (described below) includes a new strainer and O-ring.

  1. Reinstall the strainer and nut with its O-ring

    (don't lose or damage the O-ring or the valve will leak) and tighten the nut to at least 10 inch-pounds of torque, and not more than 100 inch-pounds of torque.

    Watch out: don't use Teflon tape when installing the pressure reducer strainer nut and o-ring or the risk is that you will over-tighten and damage the equipment making it and the system unsafe, risking injury or damage.
  2. Close the heating boiler drain and re-fill the heating system

    with cold water.
  3. Vent any excess air from the heating system -

    as you may have introduced air during the drain and refill procedure. Remember to close the bypass valve or fill valve when the heating system has been filled to its cold starting pressure.
  4. Check the system for water leaks,

    especially where you have been working and disturbing parts
  5. Turn the boiler electrical service switch back on,

    make sure the room thermostat is calling for heat, allow the heating system to resume normal operation.
  6. Check a last time for leaks.

Watch out: The manufacturers of this type of automagic water feed valve recommend that additional manual control valves be included in the piping system, so in some installations you might also find that the automatic water feeder is not really so automatic.

... the manufacturer warns that the purpose of the pressure-reducing (and automagic water feeding) valve is to fill heating boilers after installation or servicing. The company says

"It is not a safety device and is not intended to be used as as a water feed valve to control boiler water at a safe operating level".

Complete Disassembly of a B&G Pressure Reducer

This information has moved

to PRESSURE REDUCING VALVE DISASSEMBLY

How to Use the Pressure Reducer Valve Repair Parts Kit

Clogged pressure reducer valve won't feed water to the boiler B&G B-8 (C) Daniel Friedman at InspectApedia.com

B&G provides a repair parts kit for this valve.

Pressure Reducer & Flow Control Valve Manuals

Bell & Gossett dual unit pressure-reducer/water feeder and pressure relief valve combo cited & discussed at Inspectapedia.com

Above: a dual unit pressure-reducer/water feeder combined with a pressure relief valve, from Bell & Gossett - manuals and instructions given below.

Also see this complete manual source:


...

Continue reading at PRESSURE REDUCER / WATER FEED VALVE, BOILER - topic home, or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.

Or see these

Recommended Articles

Suggested citation for this web page

PRESSURE REDUCING VALVE (BOILER) CLOG REPAIR at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

Or see this

INDEX to RELATED ARTICLES: ARTICLE INDEX to HEATING SYSTEMS

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Ask a Question or Search InspectApedia

Share this article:

Search the InspectApedia website

Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.

Citations & References

In addition to any citations in the article above, a full list is available on request.



ADVERTISEMENT