Main fuse or main circuit breaker in an electrical panel:
This article summarizes inspection of the main electrical switch - the main switch at buildings and also outlines other electrical panel and switch defects that can be found by visual inspection.
We include information about How many main disconnect switches are allowed, other main disconnect switch hazards.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?
This article and others in the series discusses procedures for safe and effective visual inspection of residential electrical systems including electrical panels and other components, when the inspection is conducted by trained building inspection professionals, home inspectors, electrical inspectors, and electricians.\
[Click to enlarge any image]
The Implications: electrical shock or fire. Look for these electrical panel hazards when inspecting the main circuit breaker:
Recently I inspected a ITE Pushmatic main panel box. At the top of each buss line there was a main breaker. What is the current policy regarding this type of main panel box wiring configuration? Is there need for further evaluation by a licensed electrician? - D.B. 1/22/2014
[Click to enlarge any image]
The short answer is that we are allowed up to two main switches to turn off power in the main electrical panel.
A sub panel containing 6 circuits or less can omit a separate main breaker and may be switched by the breaker on its input feed circuit.
That situation is called the "rule of six" - meaning that if there are six breakers or less in a panel then that panel does not have to also have a main switch.
But there are other issues with Pushmatics that argue for viewing this equipment with caution. I'm not confident that the advice "have the panel examined by an electrician" is at all an adequate warning, since there are surely electricians living by rigid code interpretation who will deem safe electrical panels known to have safety defects but that have not been subject to a government-ordered recall.
Clear examples are FPE Stab-Lok equipment, and two more possible examples are the Bulldog-Pushmatic panel and also Zinsco panels.
Where we have independent, unbiased testing and field reports of comparatively high levels of field failures, an astute home inspector, electrical inspector, or electrician ought to call out those hazards - even where they may call for a costly panel replacement. (The last man in to touch the equipment will be blamed if/when there is a fire or catastrophe).
Details and an expanded discussion of these hazards can be found
at PUSHMATIC - BULLDOG PANELS.
If I understand your photo, you are pointing (your dangerously close bare fingers made me nervous) to a pair of split-main breakers, an arrangement that lacks a common internal trip or external trip tie. This design would allow one side of the panel to be switched off while leaving the other side "on".
For main disconnects, (using 2002 NEC as an example)
(A) Lighting and Appliance Branch-Circuit Panelboard Individually Protected.
Each lighting and appliance branch-circuit panelboard shall be individually protected on the supply side by not more than two main circuit breakers or two sets of fuses having a combined rating not greater than that of the panelboard.
Exception No. 1: Individual protection for a lighting and appliance panelboard shall not be required if the panelboard feeder has overcurrent protection not greater than the rating of the panelboard.
[This means that no main is required in the panel if the feeder wires to the panel are protected ahead of the panel itself - that is, in effect there is a separate main breaker ahead of the panel, but there are then separation distance constraints between these switches.]
Your photo shows an electrical panel that uses two main breakers so by my understanding, on this point it would be acceptable. Further, this particular Pushmatic main breaker design is not visually ambiguous - that is, switching off one side of the panel would not make it look as if both are off.
Some experts (http://ecmweb.com) aptly point out that even if a circuit breaker pair could be connected by a common handle (not possible in this Pushmatic case) the level of protection is not the same as that provided by two-pole or double-pole circuit breakers with a common internal trip tie mechanism.
A handle-only connection in some designs may leave one breaker "on" and the other "off" - a dangerous condition because of the chance of fooling the electrician or homeowner into thinking that all electrical power is off when it is not.
Common internal trip ties would be required by NEC 240.20(B) for example on a multiwire branch circuit because that code paragraph requires that "... the circuit breaker shall open all ungrounded conductors of the circuit." Tandem circuit breakers (two breakers powering two circuits fit into a single original breaker slot in a panel) also trip together.
Details are at CIRCUIT BREAKER HANDLE TIES
Separately, NEC also permits a maximum of six disconnects to turn off all power in an electrical panel. We encounter this condition usually in sub-panels or branch panels. If the sub panel contains more than 6 breakers (and is remote from the main switch) it needs to have its own main switch.
(A) General. The service disconnecting means for each service permitted by 230.2, or for each set of service-entrance conductors permitted by 230.40, Exception Nos. 1, 3, 4, or 5, shall consist of not more than six switches or sets of circuit breakers, or a combination of not more than six switches and sets of circuit breakers, mounted in a single enclosure, in a group of separate enclosures, or in or on a switchboard.
There shall be no more than six sets of disconnects per service grouped in any one location.
For the purpose of this section, disconnecting means used solely for power monitoring equipment, or the control circuit of the ground-fault protection system or power-operable service disconnecting means, installed as part of the listed equipment, shall not be considered a service disconnecting means.
Thank you for your in-depth review and explanation of the issues encountered at this panel box.
[...] and I will revisit these issues with this client. Your comments also prompted me to read other related issues on main panel boxes that were posted on your website. - D.B. 1/24/2014
About your finger near that Pushmatic breaker, I know you were smart enough not to electrocute yourself.
As a publisher/editor I have to worry about risks to a casual reader, a careless homeowner, or someone who just lacks respect for electricity. The chance that someone else will fail to understand that they need to be careful when inspecting electrical panels is a worry that leads me take opportunity to point out shock hazards where I can see them.
Even though at home inspections I habitually stood blocking my inspection client from direct access to the electrical panel as I examined that component, I once had a client reach right over my shoulder and stick his finger right into a live fuse socket while asking "What the heck is this!" The results were exciting.
Watch out: at a home inspection training seminar we had an electrician tell newbie home inspectors how to inspect the electrical panel by saying "Well the first thing you wanna do is grab a-holt of each of the entry main wires just above where they come into the main breaker - and give them a good shake!"
I could just imagine that with that fool statement he had probably killed one or two of the fellows in the room, sending 240 volts right through their hearts.
Information in this electrical inspection article series was presented by Daniel Friedman - InspectApedia.com, and discussed by the Hudson Valley chapter of the American Society of Home Inspectors - HVASHI Seminar 12 Sept 2002, Updated April 2006, April 2009, January 2014, July 2017, March 2019
...
Below you will find questions and answers previously posted on this page at its page bottom reader comment box.
On 2021-03-12 - by (mod) -
@John, yes either in the panel or next to it
On 2021-03-12 by John
The main 200 amp breaker is on the north side of my house. The panel is on the south side. It has more than six circuits. Does it require a master breaker as well?
On 2020-11-15 - by (mod) -
John
It's a perfectly fair question - why did I lose power on one leg of an electrical system - but not one that we can reliably answer from a brief text message as there are lots of possiblities.
The more-important point is that the electrical system might be not just missing power but unsafe, depending on just why power was dropped.
A poor connection in a meter box can drop power but an example of a different cause is a cut wire or a post driven through a buried wire - a condition that is dangerous, risking fatal electric shock.
Get your electrician to examine the system and do tell me what she found.
On 2020-11-10 by John mjnks
I would like to know why I would have lost one leg of 220 after the maintenance guy changed out the 3 wire disconnect next to the meter the 3 wires go underground and come up under my home out of the ground as 4 wires where could they have changed over maybe there is a short there as I have 229 at disconnect and 120 one only one if the hot lines coming into the house
On 2020-09-25 - by (mod) -
Yes
On 2020-09-25 by Daniel E Griffin
Does the six disconnects apply to condos and high rises also?
On 2020-08-18 by (mod) - keep elecrical panel location obvious and access easy
Joe
You can of course add a level of drywall over the ecisting wall, but you will need to leave working space to remove the panel cover.
And if you are going to build an exterior access cover or door it needs to be obvious that it's the electrical panel. Otherwise in an fire or shock emergency someone may not be able to find the main disconnect switch.
Watch out: do not cover the electrical panel in a way that makes its location hidden or in any way not-obvious, as in the event of an emergency any building occupant needs to be able to find the panel and to reach it to turn off the main or other switches.
Also, for the same reason, review the required safe access and clearance distances to the panel before thinking about installing a gas fireplace in that same corner. Discuss the question with your building inspector too.
On 2020-08-17 1 by Joe
Am I able to drywall over the main service shutoff as long as I install a door to access the switch?
I'd like to install a direct vent gas fireplace in my basement corner. The main shut off unfortunately is also located in the corner. Once the framing and drywall is complete, the shut off would be covered. I was thinking of installing an access door, then putting a paint over it. Is there any codes/guidelines for accessibility? Thanks!
On 2020-07-03 - by (mod) -
Sure, Robin,
The main disconnect for a 200 A service can be located outside at an electric meter or pole, using, of course, a proper weatherproof box.
However if the electrical panel indoors has more than 6 circuits installed, it, too, requires a main shutoff switch.
On 2020-07-03 by Robin
Can a 200amp main disconnect be placed directly below the meter on a meter pole?
On 2019-03-25 by (mod) - How many disconnects are allowed on a residential home to turn off
A common rule of thumb is 6 breakers max to be switched off to cut all power to a home; more than 6 you need a separate main switch.
In a typical main panel, up to 2 main switches are allowed as main disconnect for the panel.
On 2019-03-25 by Anonymous
How many disconnects are allowed on a residential home to turn off
...
Continue reading at MAIN DISCONNECT AMPACITY or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see MAIN ELECTRICAL DISCONNECT FAQs - questions & answers about the main electrical disconnect switch(es) posted originally on this page
Or see these
MAIN ELECTRICAL DISCONNECT at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.
Search the InspectApedia website
Note: appearance of your Comment below may be delayed: if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.
Only one image can be added per comment but you can post as many comments, and therefore images, as you like.
You will not receive a notification when a response to your question has been posted.
Please bookmark this page to make it easy for you to check back for our response.
Our Comment Box is provided by Countable Web Productions countable.ca
In addition to any citations in the article above, a full list is available on request.