Building Inspection, Diagnosis & Repair Info

Electrical service entry masthead (C) Daniel Friedman Electrical Service Entry Cable Sizes for Long Wire Runs

Electrical service entry wire sizes are calculated for long wire runs in which the wire size must be increased to avoid an un-wanted voltage drop. We include links to wire size and voltage drop calculators.

This article series gives photos and tables of electrical service entry cable sizes, electrical branch circuit wire sizes, bell wire, telephone wire, thermostat wire, and ampacity or fuse/circuit breaker ratings.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?





ADVERTISEMENT





Tables of SEC Sizes for Long Wire Runs for Copper & Aluminum Cable

This page gives the necessary increase in electrical service entry wire size for long runs, for example between the electric meter and the main electrical panel.

If you need wire sizes for shorter service entry cables up to 200A or for both short and long branch circuit wires from 15 to 50A

see SE CABLE & BRANCH CIRCUIT WIRE SIZES vs AMPS

Summary Table of Service Entry Cable Sizes

(Detailed tables follow the table given just below)

Electrical Service Entry Wire Sizes Needed for Longer Run Lengths

Maximum Run Length in Ft. vs AWG Wire Size, @ <= 3% Voltage Drop, 120V per SEC Conductor

  25 ft. 50 ft. 100 ft. 150 ft. 200 ft. 300 ft. 400 ft.
Wire Material AMPS
Wire Size AWG
Copper 100A 4 4 1 2/0 3/0 300 kcmil 500 kcmil
Aluminum 100A 2 2 2/0 4/0 300 kcmil 600 kcmil 1000 kcmil
Copper 200A 1/0 1/0 3/0 300 kcmil 500 kcmil 1000 kcmil 500 kcmil3
Aluminum 200A 2/0 2/0 300 kcmil 600 kcmil 1000 kcmil 600 kcmil 3 1000 kcmil3

Notes to the table above

  1. Using two 120VAC conductors, <= 3% maximum drop in voltage
  2. 240V Service provided as two separate 120VAC cables; All of these services are single phase. Three phase power typically reduces the wire size to the next smaller.
  3. Requires 2 parallel cable sets
  4. Watch out: these are example wire or cable sizes vs. run or length for the specific parameters named here and entered in the wire size and length calculator. Your installation may differ. For safety and for code compliant electrical wiring, be sure to check with your local electrical code inspector and electrical code provisions.
  5. Adapted from two sources:
    • VOLTAGE DROP TABLE, [PDF], retrieved 2017/09/26, Cerrowire LLC, 1099 Thompson Road SE, Hartselle AL 35640, USA, Tel: 256-773-2522, original source: http://www.cerrowire.com/files/file/voltagedrop.pdf

    The 300 ft and 400 ft cable length data is from

    • Cable size recommended based on voltage drop calculations. Calculated by Online voltage drop calculator: 2019/07/23, Southwire, Tel: 1-800-444-1700 Website: www.southwire.com Email: CableTechSupport@southwire.com Web page: https://www.southwire.com/calculator-vdrop

Detailed Copper SEC Sizes for Longer Cable Distances

The table below shows Copper SEC wire sizes for various run lengths - be sure to see the additional assumptions in the table notes. The voltage drop is held to under 3% across the long distance wire runs in these tables.

Copper SEC Wire Size for Long Runs for 200A Service

Cable Size1

Distance 8

Ft. / M

Voltage
Drop %

Phase

3/0 AWG 200 - 2257 / 60 2.83 1
3/0 AWG 200 / 60 2.45 3
4/0 AWG 250 - 2607 / 75 2.89 1
4/0 AWG 250 / 75 2.58 3
250 kcmil 2907 / 88    
250 kcmil 2907 - 300 / 90 2.72 3
300 kcmil 300 - 3207 / 90 2.78 1
300 kcmil 350 / 100 2.82 3
350 kcmil 3507/ 100 2.92 1
350 kcmil 400 / 120 2.89 3
400 kcmil 450 / 135 2.97 3
500 kcmil 400 - 4307 / 120 2.67 1
600 kcmil 450 - 4757 / 135 2.74 1
500 kcmil 500 / 150 2.89 3
600 kcmil 475 / 145   1
750 kcmil 500 - 5357 / 150 2.72 1
1000 kcmil 6157 / 187   1

Notes to the table above:

  1. Cable size recommended based on voltage drop calculations. Calculated by Online voltage drop calculator: 2019/07/23, Southwire, Tel: 1-800-444-1700 Website: www.southwire.com Email: CableTechSupport@southwire.com Web page: https://www.southwire.com/calculator-vdrop
  2. Electrical Panel & Service Size: 200A 240VAC, Ending amps if voltage drop were 3% will be 194A
  3. Voltage: 240 VAC
  4. Maximum Voltage Drop: 3%
  5. Parallels (Sets) 1
  6. Conductor installation is direct-buried, in conduit, OR overhead, unless otherwise noted
  7. See this ELECTRIC WIRE AMPACITY CHART [PDF] from CerroWire, retrieved 2021/11/25 original source: https://www.cerrowire.com/wp-content/uploads/2021/04/Cerrowire_Ampacity_Chart_210405.pdf
  8. Maximum wire run distance changes by required temperature rating:

    The Amperage rating and distances shown are for 90°C (194°F) THWN-2, THHN, XHHW-2, USE-2 - copper wire;

    Watch out: Note that dropping to 60°C (140°F) NM-B, UF-B copper wire, the maximum run lengths will be substantially shorter.
  9. For smaller wire size ampacities & run lengths (#14 copper or #12 aluminum) up through typical residential SEC wire sizes and amps

    See SE CABLE & BRANCH CIRCUIT WIRE SIZES vs AMPS

Watch out: the engineering work and derivation of the table above is derived from the sources listed below including manufacturer's tables and online voltage drop calculators but may not be correct for your specific installation. Check with your engineer or electrician.

Watch out: if you are not trained and qualified to install electrical wiring a mistake can result in fire, injury, or death. Be sure you review your work plan with your local electrical inspector and that work is done to the electrical code for the country and city where you live. In the U.S. that's the U.S. NEC.

Detailed Aluminum SEC Cable Sizes for Long Wire Runs

The table below shows Aluminum SEC wire sizes for various run lengths - be sure to see the additional assumptions in the table notes.

Aluminum SEC Wire Size for Long Runs for 200A Service

Cable Size1

Distance

Ft. / M

Voltage

Drop %

Phase

300 kcmil 200 / 60 2.79 1
250 kcmil 200 / 60 2.77 3
400 kcmil 250 / 75 2.85 1
350 kcmil 250 / 75 2.69 3
500 kcmil 300 / 90 2.92 1
400 kcmil 300 / 90 2.96 3
750 kcmil 350 / 100 2.67 1
500 kcmil 350 / 100 2.95 3
1000 kcmil 400 / 120 2.61 1
750 kcmil 400 / 120 2.64 3
1000 kcmil 450 / 135 2.94 1
750 kcmil 450 / 135 2.97 3
Not Available 500 / 150   1
1000 kcmil 500 / 150 2.83 3

Notes to the table above: Assumptions

  1. Cable size recommended based on voltage drop calculations. Calculated by Online voltage drop calculator: 2019/07/23, Southwire, Tel: 1-800-444-1700 Website: www.southwire.com Email: CableTechSupport@southwire.com Web page: https://www.southwire.com/calculator-vdrop
  2. Electrical Panel & Service Size: 200A 240VAC, Ending amps if voltage drop were 3% will be 194A
  3. Voltage: 240 VAC
  4. Maximum Voltage Drop: 3%
  5. Parallels (Sets) 1
  6. Conductor installation is direct-buried, in conduit, OR overhead, unless otherwise noted

Watch out: if you are not trained and qualified to install electrical wiring a mistake can result in fire, injury, or death. Be sure you review your work plan with your local electrical inspector and that work is done to the electrical code for the country and city where you live. In the U.S. that's the U.S. NEC.

How to Use a Voltage Drop Calculator to Determine Required Service Entry Wire Size

Here we give examples and compare the results of using two example wire size and voltage drop calculators.

You will see that Southwire and Paige calculators give similar results.

1. Southwire's Voltage Drop Calculator example calculating SEC wire size

Southwire's wire size calculator at http://www.southwire.com/support/voltage-drop-calculator.htm is easy to use and clear.

The user specifies the number of phases (1 or 3), conductor (copper or aluminum), installation (direct buried, conduit, or overhead) and the input voltage, maximum allowed voltage drop (I use 3%), the length of the cable run, and the desired current (amps) at the end of the cable run. The calculator gives an appropriate wire selection and its parameters, such as this:

Example: Single phase, aluminum conductor, direct buried, 120VAC, 3% maximum voltage drop, 250 ft. cable run length, 100A current at end of cable

Result: 1 conductors per phase utilizing a #400 Aluminum conductor will limit the voltage drop to 2.94% or less when supplying 100.0 amps for 250 feet on a 120 volt system.

Changing the example above to 240 VAC, keeping other parameters the same gives this result:

Result: 1 conductors per phase utilizing a #3/0 Aluminum conductor will limit the voltage drop to 2.82% or less when supplying 100.0 amps for 250 feet on a 240 volt system.

2. Paige Wire Size Calculator example calculating SEC wire size

Paige Wire's voltage wire size calculator at http://www.paigewire.com/pumpWireCalc.aspx is also easy to use and clear. Testing with the following parameters:

Example: 240 VAC Single Phase, 100A, 250 ft. run, 3% voltage drop allowed,

Result: 1 AWG Copper or 2/0 Aluminum

Changing the example above to 120VAC, keeping other parameters the same gives this result:

Result: 3/0 AWG Copper or 250 MCM Aluminum

Siemens offers an XLS spreadsheet [ http://w3.usa.siemens.com/us/internet-dms/internet/consultingengineerscomm/general/Docs/DA_VD_Calculator_V1.1.xls - this address leaves InspectApedia.com] that can be used to calculate voltage drop as do other sources, and there are numerous online voltage drop calculators - I like the Southwire calculator given above. Be sure to compare the calculator's result with what the applicable electrical code will permit.

Voltage Drop Index - VDI - when to increase wire size for long electrical wire runs

The voltage drop index or VDI is a reference number that is based on the electrical resistance of a wire and is calculated as

VDI = (Amps x Feet of run) / (% Voltage Drop allowed x Voltage)

Typical allowable voltage drop is 2% or 4% depending on the application.

3% is the most commonly-accepted voltage drop target.

More about the VDI and VDI tables are given

at SE CABLE & WIRE SIZE TABLES vs AMPS

Question: what size Aluminum Service Entry Cable do I need for a 200A panel on a 400 foot length?

2019/07/23 Bob s.

I'm running a 400 foot main cable from street to home, I want 200amp service and use aluminum wire. What size do I use to compensate for distance

Reply:

From the table of Aluminum SEC Cable Sizes for Long Runs you'll see the answers given below,

Answer: 200A, Aluminum wire, 400 foot run, direct buried SEC cable

For single phase power: 1000 kcmil aluminum wire will have a voltage drop under 3% for a 400 foot run of direct buried cable and a 200VAC single phase electrical service. That gives us 194 Amps at the end of the SEC run.

For three phase power: 750 kcmil aluminum wire will have a voltage drop under 3% for a 400 foot run of direct buried cable and a 200VAC three phase electrical service. That gives us 194 Amps at the end of the SEC run.

Using a typical online voltage drop calculator, keeping your voltage drop below 3%, and using your 400 foot run and Aluminum wire for a 200 VAC service, we plugged the data into Southwire's voltage drop calculator to see what wire size would suit.

Details about Wire Size vs Voltage Drop for Long SEC Wire Runs

Voltage drop across a wire is proportional to the current flow and wire resistance; for AC power such as your service entry cable (SEC) total impedance and power factor (the ratio of power loss) are considered too.

None of the standard voltage drop tables go beyond 200 feet of wire run. At 200 ft and 200A the tables get to 350 to 500MCM copper wire and for 200 ft and 200A the tables get to 600 MCM aluminum wire (Cerrowire.com)

For longer runs (like your 400 ft) your engineer would either perform the voltage drop calculation and wire size. Or use one of the online voltage drop calculators. Southwire provides an easy-to-use voltage drop calculator that I recommend. .

I expect you're going to end up with at least 600 or 750 MCM AL wire - such a large size may not be practical even though the Cu will of course be more expensive. Let's look at the details.

  1. Example calculation 1 - Copper Wire, 1 phase power
  1. Example calculation 2 - Aluminum Wire, 1 phase power
  1. Example calculation 2 - Aluminum Wire, 3 Phase power
  1. Example calculation 2 - Copper Wire, 3 Phase power

Online voltage drop calculator used: 2019/07/23, Southwire, Tel: 1-800-444-1700 Website: www.southwire.com Email: CableTechSupport@southwire.com Web page: https://www.southwire.com/calculator-vdrop

Key points in calculating voltage drop and selecting wiring cable

...




ADVERTISEMENT





Reader Comments, Questions & Answers About The Article Above

Below you will find questions and answers previously posted on this page at its page bottom reader comment box.

Reader Q&A - also see RECOMMENDED ARTICLES & FAQs

On 2022-12-05 by InspectApedia (Editor)

@Bruce,

You can find that in the tables above, Please take a look.

Do let me know if the table is unclear.

On 2022-12-05 by Bruce

I've got a run of 155 feet on a 200 Amp box what size copper wire would be used

On 2022-10-18 by InspectApedia-911 (mod)

@Joe Frank,

You can find that in the tables above, Please take a look.

On 2022-10-18 by Joe Frank

What size Aluminum would I use for a 420 foot run for 100 amps of service?

On 2022-10-03 by InspectApedia-911 (mod) - use one of the voltage calculators

@Roman,

For very long wire runs like that, exceeding the wire size & length tables you'll want to use one of the voltage calculators that we discuss above on this page.

On 2022-10-03 by Roman

Hello, bought a piece for land and need to run approx 1200 feet cable to the construction site. Could you please guide on the wire requirements? Would an additional transformer need? thank you

On 2022-08-13 by InspectApedia-911 (mod) - must know layout and distances among the fields

@DAVID,

We sure do. But we have no information at all about the layout relations among the fields and thus don't know the distances involved.

If possible you'd bring power to a central location, install a master panel there, and thus use shorter runs at smaller wire sizes to each of the fields. Long run wire sizes are given above, or you can use one of the wire run calculators that we cite. Keep your voltage drop down as described above on this page.

On 2022-08-13 by DAVID

Hello im bidding a job for 3 football feids all in a row each one gets a score board 300 yards I have to bring 220v power to each score board plus a snack stand 125 yards from the last score board panel .

Power is coming for utility pole thants not yet installed. Wire size is kicking my butt. Im installing a 125 amp panel outdoor at each score board .. All underground you have any ideas ?

theshocker32@hotmail.com please email me love the lay outs on this site

On 2022-04-06 by Inspectapedia Com Moderator - can I get the same total amperage needed using a smaller wire

@Tim M,

On the surface of it your idea sounds appealing: run 240V to get the same total amperage needed using a smaller wire.

I may be missing something in your implementation, but consider that normally we obtain 240V by running a pair of hot wires from the main electrical panel, each bringing 120V to the destination; the 240V is obtained by connecting a device across the two 240V wires.

So at the far end of your 450 ft. buried cable, where you want to draw just 120V and need 20A or 15A, the individual circuit wire still needs to be sized to carry a 15A or 20A load at the 450 foot distance.

On 2022-04-05 by Tim M

Wanting power 120v @20amp or.15amp 450ft length buried. Would it be possible( or a bad idea) to run 220v from the power box and then use 220v to 120v .adapters at the end point to reduce the gauge size of wire?

Since I don’t really need 220v at end point is there any problem simply expecting the voltage drop of a smaller wire to save $ even if it goes down from 220v to say 150v as I really only need 120v?

On 2022-04-01 by Inspectapedia Com Moderator - What size wire size should I use

@Jeff Williams,

Thank you for the question. You'll see long run cable sizes for aluminum and copper in the tables above.

But as you and others will note, when an installation exceeds the tables of wire sizes and run lengths or amps, we need to go to a manufacturers or engineers voltage drop calculator to get the right or acceptable wire size.

On the page above we include links to wire size and voltage drop calculators.

On 2022-03-31 by Jeff Williams

My home has a 200 amp box in the front yard and underground electrical cables running to the rear of the house, to the meter. It’s approximately a 150 foot underground run. I want to replace the existing cable and increase the amps to 400.

I have no preference as to aluminum or copper wire, but would prefer the best, if not to big of a cost increase. What size wire size should I use. Thank you.

On 2022-02-03 by Inspectapedia Com Moderator - What size aluminum wire do I need

@Bob,

Sorry but no one can answer your question the way it's phrased, because you don't state the current requirement or amps.

Once you know that information take a look at the tables above on this page.

On 2022-02-02 by Bob

What size aluminum wire do I need for a 425 ft run at 220 volts

On 2021-11-25 by Inspectapedia Com Moderator (mod) - what size of electrical wire for a 2,500 foot run on a 15A circuit? Stop well pump wire shorting-out.

Long electrical wire run sizing table at InspectApedia.comReally? you ran or plan to run #10 copper wire 2,500 feet - nearly half a mile of electrical wire. In conduit?

There is simply no way that you can run a conventional 15A o 20A 120V or even 240V wire using #10/2 copper wire from your home to a barn that's nearly half a mile away using any conventional wiring means. The wire will have such a large voltage drop that your delivery voltage will be too low and your pump either won't run or will have constant trouble.

Here we discuss using a voltage drop calculator (we like one provided by Southwire) at which you input the basic parameters of

- cable run length

- voltage

- allowable voltage drop (usually limited to 3%)

- current(amp) required at end of cable

- number of parallel wire set

I ran your case for two solutions:

Case 1: 2500 ft., 15Amps, 120VAC, and the wire size calculator returns

1 conductor per phase utilizing a 400 kcmil Copper conductor installed Direct Buried will limit the voltage drop to 2.95% or less when supplying 15 amps for 2500.0 feet on a 120 volt 1 phase system.

OR

Case 2: 2500 ft., 15Amps, 240VAC, and the wire size calculator returns

1 conductor per phase utilizing a 3/0 AWG Copper conductor installed Direct Buried will limit the voltage drop to 2.74% or less when supplying 15 amps for 2500.0 feet on a 240 volt 1 phase system.

Frankly, if I were going to the trouble and cost of running half a mile of electrical wire I'd run a 240V line to have a bit more capacity at the other end -
and I'd consider going to a 20A circuit, for which you'd need

1 conductor per phase utilizing a 250 kcmil Copper conductor installed Direct Buried will limit the voltage drop to 2.69% or less when supplying 20 amps for 2500.0 feet on a 240 volt 1 phase system.

Why? What are the chances that once electrical service is brought to an isolated building nobody is going to want to run more than just a well pump? What about a light, or a receptacle to power an electric drill?

Shown above is a wire size table adapted from Encorewire.com cited thereon

I'd do some shopping or consider an alternative power source (Solar ?)

Consider that at some suppliers we checked online (you may find better price from a bulk electrical wire supplier)

the price for 2,500 ft of 3/0 copper electrical wire is over $11,000. U.S.

the price for 2,500 ft. of 400 kcmil copper wire is around $30,000 U.S.

Thats for using UF-rated wire - intended for direct burial into soil.

If you instead want to try to run half-a mile of conduit - not something that's necessary in my OPINION, and if you used a 3/4" diameter flexible water-tight non-metal conduit like that provided by Southwire, shown below, you may save by buying individual conductors instead of sheathed UF SEC cable, at $136 / 100 ft., you'll add about another $3,400. U.S. varying up or down in cost depending on the conduit diameter needed.

Flexible non-metallic electrical conduit, water-tight, from Southwire, sold in various diameters and lengths - cited & discussed at InspectApedia.com

This flexible conduit is rated as permitted for direct burial or for burial in concrete. The conduit wall is Schedule-40.

Also see conduit products from Hydromaxx.

On 2021-11-25 by Guy Priano - this is the third time my well pump wire has shorted out

I have 10/2 UF-B Wire w/ Ground which runs underground with no conduit for 2500 feet from the control box in the barn to the two pressure tanks in my pump house.

This is the third time it is shorting out and the well person who installed the system saids he is not an electrician and unable to recommend what kind of wire I need to replace it with.
Something about it is bleeding over causing the short.

Sending 120 volts up the wire and only receiving 58 volts back = which is burning the control components up.

What would be the correct kind and size of the wires to tell the pump to turn off.

There is hardly any load on the wires what would I replace it with?

Any feedback would be greatly appreciated. 503-663-2244 priano@gmail.com

Guy's question and our reply were posted originally at

WATER PUMP WIRING REPAIR

On 2021-09-10 by mak.church (mod)

@Jerry,

When you get to longer lengths than illustrated above on this page, you need to go to an online voltage drop calculator as noted above, such as:
http://www.southwire.com/support/voltage-drop-calculator.htm

or

http://www.paigewire.com/pumpWireCalc.aspx

The section above:

How to Use a Voltage Drop Calculator to Determine Required Service Entry Wire Size

will help you in using those online calculators.

Using a voltage drop calculator as we suggested, you'll see that if you allow a 3% voltage drop your copper wire size for a 15A circuit at 120V and 650 ft needs to be a #2 AWG copper wire

3% is the recommended allowable voltage drop

5% is the maximum permitted drop on a typical branch circuit;
If you accept 5% voltage drop your copper wire could be #4 AWG.


For other readers:

For branch circuits at 15A up to 50A and for distances up to 400 ft
you will find our

Branch Circuit Wire Sizes Needed for Longer Run Lengths Table

at SE CABLE & WIRE SIZES vs AMPS

On 2021-09-10 by Jerry

What size/type direct burial cable do I need to provide 15 amps with at the end of a 650 ft run?

On 2021-04-05 by (mod)

@Anonymous,

Please take a look in the table "Copper SEC Wire Size for Long Runs for 200A Service" at the top of this page.

On 2021-04-05 by Anonymous

what size wire for 200amp 140 foot run underground

On 2021-03-22 by danjoefriedman (mod) - What size service entrance cable do I need for a 100 amp service and a 150 ft. run?

@Larry, please check the sizing tables in the article above and let me know if any of that is unclear or confusing

On 2021-03-21 by Larry

What size service entrance cable do I need for a 100 amp service and a 150 ft. run?

On 2020-07-03 - by (mod) -

Tim

Check out

SE CABLE SIZES FOR LONG WIRE RUNS

at https://inspectapedia.com/electric/Long-Run-SEC-Cable-Sizes.php

and don't hesitate to ask if that leaves you with questions

Thanks This Q&A were posted originally

at UNDERGROUND SERVICE LATERAL FAQs

On 2020-07-03 by Tim

I'm putting underground electric service to my house. I have 200 amp service. I need 200 feet of underground. What size wire do I need.

On 2019-07-23 - by (mod) -

Bob,

Please check out the table for long runs of aluminum service entry cabling at SE CABLE & WIRE SIZES FOR LONG RUNS

at https://inspectapedia.com/electric/Long-Run-SEC-Cable-Sizes.php

where I repeat your question and give a detailed reply.

Let me know if that information is not clear or if you're left with questions.

On 2019-07-23 by Bob s.

I'm running a 400 foot main cable from street to home, I want 200amp service and use aluminum wire. What size do I use to compensate for distance



...

Continue reading  at SE CABLE & BRANCH CIRCUIT WIRE SIZES vs AMPS - topic home, or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.

Or see these

Recommended Articles

Suggested citation for this web page

SE CABLE & WIRE SIZES FOR LONG RUNS at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

Or see this

INDEX to RELATED ARTICLES: ARTICLE INDEX to ELECTRICAL INSPECTION & TESTING

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Ask a Question or Search InspectApedia

Share this article:

Questions & answers or comments about electrical wire sizes, diameters, and ampacity ratings.

Ask a Question or Search the InspectApedia website using the box just below.

Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.

Citations & References

In addition to any citations in the article above, a full list is available on request.



ADVERTISEMENT