Building Inspection, Diagnosis & Repair Info

Siemens GFCI circuit breaker at InspectApedia.comGround Fault Circuit Interrupters, GFCI Test Procedure

Ground Fault Circuit Interrupters, GFCI testing:

Here we cite expert sources' description of the proper way to test a ground fault circuit interruptor GFCI for proper and safe operation.

We include additional notes on situations in which proper testing is impossible even though the device might actually work if a current leak to ground or neutral occurs on the circuit.

This article series GFCIs and AFCIs as well as safe GFCI & AFCI installation, wiring, testing, and inspection.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?





ADVERTISEMENT





GFCI Testing Instructions

GFCI wall receptacle or A GFCI or Ground-Fault Circuit Interrupter is a safety device intended to prevent electrical shock by detecting an improper flow of electrical current and shutting the electrical circuit off very quickly - in milliseconds.

The GFCI is designed to protect people from severe or fatal electric shocks by quickly detecting a small flow of electrical current between the electrical circuit (wires, switch, electrical receptacle or something plugged-in to the receptacle) and "ground" or the earth.

A GFCI also can protect against some electrical fires by detecting arcing and other faults to ground but a GFCI cannot detect hazardous across-the-line arcing faults that can cause fires.

[Click to enlarge any image]

The photo also shows an independent GFCI test tool plugged into the lower receptacle openings.

On the GFCI tester the round black button on the top of the devicve is an independent test button that attempts to simulate a short to ground or neutral. If the device tester trips the GFCI the RED RESET button will pop out as above.

GFCI Test Procedure for Receptacles: Using the Receptacle Built-In Test & Reset Buttons

Red and black test & reset buttons on a GFCI receptacle (C) Daniel Friedman at InspectApedia.com

On many GFCI wall receptacles the TEST button is red and the RESET button is black (photo above), but as you can see in our earlier photo above and in a closer view below, on other models there is no color code.

You'll notice in our photo below that one button is emossed with the word TEST (our red arrow) and the other with the word RESET (our black arrow).

In these photos the GFCI TEST button on the wall receptacle itself checks the wiring connections at the GFCI receptacle.

The RESET button on the electrical GFCI receptacle will pop out if the device is tripped off. Pushing the RESET button all the way in should re-set the device and restore electrical power.

Identify the TEST & RESET buttons on a GFCI wall receptacle (C) Daniel Friedman at InspectApedia.com

The following GFCI test details are adapted from advice from Eaton CH cited just below.

(a) Turn the power ON at the service panel.

Press the RESET button fully. Plug a lamp or radio into the GFCI (and leave it plugged-in) to verify that the power is ON. If there is no power, go to Troubleshooting.

(b) Press the TEST button in order to trip the device.

This should stop the flow of electricity, making the radio or lamp shut OFF and the yellow Correct Wiring/Trip Indicator come on. To restore power, press the RESET button.

(c) Test Downstream receptacles:

If you installed your GFCI using step 7B,
[that stepincludes wiring to protect downstream or surrounding receptacles - Ed.] now plug a lamp or radio into surrounding receptacles to see which one(s), in addition to the GFCI, lost power when you press the TEST button.

Do not plug life saving devices into any receptacles that lost power.

Place a “GFCI Protected” sticker on every receptacle that lost power.

(d) Press the TEST button (then RESET button) every month
to assure proper operation.

(e) Note that this Eaton GFCI is shipped in the Tripped state and cannot be Reset until it is wired correctly and powered from it’s Line terminals.

(f) Note that the RESET button will pop-out. If the power goes OFF and the correct wiring/trip indicator stays on, you have installed the GFCI receptacle correctly.

(g) LINE/LOAD reversal will be indicated by the reset button not staying in after being pressed.

Such LINE/LOAD reversal will also be indicated by failure of the Correct Wiring/Trip Indicator to be on while the GFCI is tripped.

- source: Eaton, INSTALLING & TESTING a GFCI RECEPTCLE [PDF], Eaton, Website: www.eaton.com or www.cooperwiringdevices.com retrieved 2018/07.27,original source: http://www.cooperindustries.com/content/dam/public/wiringdevices/products/documents/instruction_sheets/EIS-0018-E.pdf

Excerpt:

Watch out: If you miswire the GFCI, it may not prevent personal injury or death due to a ground fault (electric shock). Upon initial installation, if you mistakenly connect the LINE wires to the LOAD terminals, this Eaton GFCI will not be able to be reset, and will therefore not provide power to it’s receptacle face or load terminals.

Watch out: the integral test buttons on a GFCI device installed on an electrical circuit that has no ground, such as on a knob and tube circuit will generally not work because the device expects the GFCI device to be connected to an electrical ground (used to simulate a current leak.

However the device might still work properly if there is an actual current leak between the GFCI device or receptacle, or something plugged into-it, and ground or neutral.

More about this test limitation including a discussion of testing GFCI devices installed on knob-and-tube electrical circuits or un-grounded circuits is found

at AFCI GFCI WIRING, TESTING & SAFETY .

GFCI Receptacle Test Procedure using a Plug-In Receptacle Tester

Using a receptacle tester to test a GFCI operation (C) Daniel Friedman at InspectApedia.comIn our photo above, you can see the built-in red TEST and black RESET buttons on this GFCI wall receptacle, but we're going to use an independent test device, the plug-in GFCI receptacle tester that wev'e inserted into the lower openings of the receptacle.

While the wall receptacle's built-in test and reset buttons are useful, this test is less complete than the test made using an external, plug-in test device.

Our photo shows a GFCI tester: the red light is off and the two yellow lights are on, indicating that this receptacle is wired properly.

When we push the black "test" button on our test device the GFCI receptacle should trip OFF.

GFCI Receptacle Test Procedure Details using a plug-in tester

See ELECTRICAL TOOLS BASIC for details of the meaning of the all combinations of indicator lights on plug-in type wall receptacle testers including GFCI testers in our dicsussion titled " Electrical receptacle tester and GFCI tester (outlet tester)".

How To Re-Set a Tripped Receptacle Type GFCI

Un-Plug any tools or devices that are connected to the receptacle circuit whose GFCI tripped off.

Press and hold the RESET button on the device.

That should re-set the GFCI.

This procedure will usually apply as well to portable GFCI devices such as those discussed

at GFCI DEVICE SELECTION & WIRING

Watch out: If the GFCI will NOT re-set when you press the RESET button it's likely that there is an unsafe condition on the circuit or circuit wiring itself.

In that case leave the circuit switched OFF at the electrical panel and ask for help from a licensed electrician. She will trace the circuit to find the problem such as a short to ground or a short to neutral in circuit wiring.

An example that we encountered was a short to neutral when the screw tightening a clamp that connected flexible metal cable conduit to a metal electrical box was screwed-in too tightly and where the normal plastic bushing inside the fitting had been omitted.

The sharp metal edge of the BX armored cable cut into and shorted the hot and neutral wires together.

More help is at CIRCUIT BREAKER RESET STEPS

GFCI Test Procedure for GFCI Circuit Breakers

GFCI circuit breakers in an electrical panel (C) Daniel Friedman at InspectApedia.com

As our illustration shows, a GFCI circuit breaker also has a "TEST" button that is depressed to test the device.

How to Re-Set a Circuit-Breaker Type GFCI

Instead of a reset button such as is found on a GFCI receptacle, on the GFCI circuit breaker the test function will trip the breaker toggle.

You will need to re-set the circuit breaker by

More help is at CIRCUIT BREAKER RESET STEPS

GFCI Test Procedures, Standards, Documents


Reader Comments &

On 2021-07-29 by inspectapedia.com.moderator (mod)

@Mack,

The typical plug-in GFCI receptacle tester works by making an internal short to ground - that should work on a conventional receptacle that has GFCI or ground-fault circuit interrupter) protection anywhere upstream from the test point.

That protection can be a GFCI receptacle or it can be a GFCI circuit breaker.

Really? It's interesting (perhaps significant) that the test of GFCI circuit breakers using these tools is NOT mentioned explicitly in any of the receptacle-type GFCI receptacle tester instructions that we provide above on this page - from 7 different sources.

Here are two examples:

GFCI TESTER INSTRUCTIONS, SOUTHWIRE [PDF] https://inspectapedia.com/electric/GFCI-Receptacle-Tester-Instructions-Southwiretools.pdf

GFCU TESTER INSTRUCTIONS, KLEIN TOOLS [PDF] https://inspectapedia.com/electric/GFCI-Receptacle-Tester-Instructions-Kleintools.com.pdf

On 2021-07-29 by Mack

Can a gfci breaker be tested by using a plug tester with the test button

On 2020-03-10 by (mod)

Alan

Thanks for the interesting points - ones that we'll be sure to keep with the article.

Indeed there is probably no GFCI tester on the market that is designed for in-field use that considers trip time.

The good news is that the most-essential, most-common GFCI faults - the ones most-likely to cause a failure and perhaps injury or worse - are not trip times but rather no-trips - a mis-wired GFCI that simply won't trip in response to a current leak to neutral or to ground.

It's also worth noting that the internal test exercised by pushing the test button on a GFCI depends on a proper local ground connection that may be absent entirely in some GFCI installations (such as on 2-wire circuits) - those GFCI's cannot be tested by normal means, even if the GFCI would trip in response to a short to neutral or to some other ground.

On 2020-03-10 by Alan

Before I worked at the mine I worked for an Electrical OEM where we did breaker and ground fault testing.

Anyone who had done breaker testing with current knows the expensive equipment that it takes to do this job. Does not really matter if it is primary or secondary injection.

I was working at a open pit mine in NW when this first reared its ugly head. We were instructed to put a gfci in every location there was water/liquid.

So a coffee pot on a cabinet without a sink qualified. We installed gcfi's by the 100's. Then the inspector came back and said he wanted a testing record for all of the gfci's.

At the time there was no REAL gfci testing equipment out there. I objected to the concept of self testing. We tested grounding in the process building records for all equipment. Required a meter and checking the continuity for all the equipment. ( Lots of work to do this)

I started asking to what standard did the IMSHA inspector wanted these to be tested. He said whatever the manufacturer published.

The self testing issue sprung to the top of the list. Our management and our inspectors did not know there are different levels for gfci's. They were thinking that they were all the same. Until I pointed out gfcis for equipment protection. Which if installed on a personnel circuit could be bad news. They were unaware of those.

I found this on and IEEE page.

"A GFCI de-energizes the circuit when the leakage current level reaches 5 ± 1 mA in 1/40 th of a second. This value of current is well below heart fibrillation levels."

Looking about on the web I found a 8 dollar box from a well know vendor for testing gfci's.

"Tester trips between 6-9 mA" No mention as to the time required to trip.

This box might do a great job for what it was designed to do, how ever I do not call it a tester, a tripper yes, tester no.

My point is most people using these cheap devices are doing themselves and clients a disservice.

I have not looked recently (last 3 years) since I got out of the business. Someone may have come up with a device that really does test, current and time. Bet my government check it is not inexpensive.

 



...

Continue reading  at AFCI GFCI WIRING, TESTING & SAFETY or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.

Or see AFCI GFCI TESTING & SAFETY FAQs - questions & answers posted originally at this page

Or see this

Article Series

Suggested citation for this web page

GFCI TEST PROCEDURES at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

Or see this

INDEX to RELATED ARTICLES: ARTICLE INDEX to ELECTRICAL INSPECTION & TESTING

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Ask a Question or Search InspectApedia

Share this article:

Search the InspectApedia website

Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.

Citations & References

In addition to any citations in the article above, a full list is available on request.



ADVERTISEMENT