Building Inspection, Diagnosis & Repair Info

Electrical worker on residential power line (C) Daniel Friedmanh Outdoor Electrical Safety Hazards for Electrical Inspectors & Home Inspectors

This electrical safety procedures article discusses outdoor safety hazards at residential properties and suggests safety procedures for the electrical inspector, home inspector, or other professionals who examine residential electrical systems.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?





ADVERTISEMENT





The Electrical Panel Inspection for Water & Rust Begins Outside

Service conductor inspection start point (C) Carson Dunlop AssociatesASHI Home Inspector Educational Seminar Proceedings: ASHI-NE Chapter Annual conference, September 22-23, 2008, Randolph, MA. -- by Daniel Friedman.

8. System: Electrical Inspection Standards for Home Inspectors (ASHI and other Associations & State Regulations)
8.1.C. [The inspector shall observe] amperage and voltage ratings of the service

Keep in mind that this determination is required by ASHI Standards and is to be derived based on visual inspection of the wiring and equipment. It is not required to use test equipment for this purpose. Sketch courtesy of Carson Dunlop Associates, a Toronto home inspection, education & report writing tool company [ carsondunlop.com ].

Safe electrical inspection procedures and safe use of volt meters, DMMs, multimeters, and similar electrical test equipment is discussed at the end of the article.

These electrical inspection suggestions are not a complete inventory of all electrical safety procedures nor of all electrical components that should be inspected; these notes focus on identification of conditions that may present special electrical hazards for the electrical inspector.

Contact Us by email to suggest changes, corrections, and additions to this material.

Electric shocks are responsible for about 1,000 deaths in the United States each year, or about 1% of all accidental deaths.- Refs.

Fatal Shock Hazard Warning: Inspecting electrical components and systems risks death by electrocution as well as serious burns or other injuries to the inspector or to others. Do not attempt these tasks unless you are properly trained and equipped.

See ELECTRIC METERS & METER BASES for a discussion of examining the electric meter and meter base portion of the service entry.

See AMPS& VOLTS DETERMINATION for determining the ampacity of an electrical service: How to determine the electrical Ampacity and Voltage provided to a building discusses in detail how to determine the service amps and voltage by visual inspection.

Also see AMPACITY - the LIMITING FACTOR.


8.1 The electrical inspector shall observe:

Electrical service masthead sketch (C) Carson Dunlop Associates

Observe does not mean touch except where removing access covers or operating certain devices is explicitly required.

8.1.A. Electrical service entrance conductors Inspection Procedure

When new service entry cables are installed don't assume that those exposed bare ends of old SEC you see are "dead." Non-contact voltage sensing devices can determine if any questionable wiring is "hot."

Sketch courtesy of Carson Dunlop Associates, a Toronto home inspection, education & report writing tool company [ carsondunlop.com ].


Electrical worker on residential power line (C) Daniel FriedmanhWatch the location of overhead lines when moving ladders to access roof and if the roof is walked, watch for the location of power lines, antennas, guy-wires, and masts when getting to, walking on, and getting off the roof.

November 10, 1988 - Marshall, TX - Donald Cleveland Jones, 45, was electrocuted when equipment he was moving came into contact with electrical wires, according to deputies. -- Same source as previous news report.

If you see fallen wires do not go near them. Notify the utility company and appropriate others promptly.

Also watch out for TV antennas which can be pushed into or fall onto electric wires. -- advice from NY Central Hudson Gas and Electric Company, G&E/1-2/85 consumer safety pamphlet.

Use extreme caution in crawl spaces and wet crawl or basement areas - avoid contacting electrical components.

We advise against entering wet or flooded sub areas at all. we have an unsubstantiated report of an inspector [or contractor] death by electrocution while inspecting a damp crawl space using a light plugged into an extension cord.

Use battery-powered lighting or if an extension cord is required, inspectors should provide their own portable GFCI protected receptacle.


Cut service entry cable may still be live (C) Daniel Friedman Don Hartley

Do Not Assume that "Old Wires" are "Dead"

The Tiff Tic TracerTM [Figure 2, page 11 in the original article, and shown in the next text section below] will not make a quantitative measurement of voltage.

But this instrument is very helpful in checking for live 120/240V voltage at wires and devices.

Without physical contact, the instrument will indicate the presence of a nearby live AC voltage field.

We found a property at which the old service entry cable (SEC) at the building corner was left in place, cut with a hacksaw about 6' from the ground, bare wire ends exposed, electrically live - it had been left connected in an old main panel which was used by the installer as a "sub panel" when the new larger main was installed.

This was an exciting installation!

See AMPS & VOLTS DETERMINATION for details of how to determine the ampacity and voltage of electrical service at a building.

Advice For Handling Immediate Threats to Life and Safety at a Building Inspection

If in the inspector's judgment equipment is an immediate threat to life and property, such as a boiler whose flue connection has fallen off, we recommend that dangerous equipment be shut down and the appropriate people notified.

See SHUT DOWN UNSAFE EQUIPMENT. In some cases "appropriate people" includes not only the client and building owner, but also building occupants.

In some instances such as sparking electrical panels, gas leaks, or evidence of a fire, the inspector and everyone else should leave the building immediately and from outside, call the fire department and as appropriate, the gas company, police, or rescue personnel.

...




ADVERTISEMENT





Reader Comments, Questions & Answers About The Article Above

Below you will find questions and answers previously posted on this page at its page bottom reader comment box.

Reader Q&A - also see RECOMMENDED ARTICLES & FAQs

Question:

2779 Mcallister San Francisco California has exterior light outside 2779 cottage that had white vertical waving cloud pop sound and smelled bad. this resulted said electrican of destroying 2779 outdoor light connected to 2781 mcallister which destroyed 2781 mcallister garage indoor lights.

The disconnect labeled 2779 did not turn off the short circuit so I turn off the main circuit breaker panel for 2779.

2779 disconnect and 2781 and 2783 mcallister san Francisco CA are Murray and Westinghouse brands.

What facts tell me what is a good electrican. I am physically disabled and old. outdoor wood doors over outdoor 2779 disconnect and 2781 and 2783 circuit breaker panels do not cover completely.

The open air gap spaces allow rainwater and fog to touch 2779 disconnect that has a horizontal switch that looks like a indoor light switch that has no metal cover over 2779 disconnect. moisture touches he circuit breaker panels with metal doors covering circuit breakers. - L.L. 4/2/2014

Reply:

L.L. I recall that we have discussed your electrical safety worries previously, at we discussed electrical issues before - see report #3 at FPE FAILURE FIELD REPORTS though now I see you are reporting two other electrical panel brands, Murray & Westinghouse.

I agree that electrical codes will require outdoor electrical panels to be weather-tight, rated for outdoor use, and properly installed.

Electricians are licensed by your state and often local municipality; beyond that we're in trouble trying to evaluate them by email. It's a tougher question to ask how to evaluate electricians as eductaion, experience, skill and importantly, attitude vary among inviduals all of whom may have obtained a license.

Perhaps your local building department can make a suggestion, particularly as you cite unsafe conditions in the homes and addresses in your email.


...

Continue reading  at ELECTRICAL INSPECTOR SAFETY PROCEDURES or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.

Or see these

Recommended Articles

Suggested citation for this web page

OUTDOOR ELECTRICAL INSPECTION SAFETY at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

Or see this

INDEX to RELATED ARTICLES: ARTICLE INDEX to ELECTRICAL INSPECTION & TESTING

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Ask a Question or Search InspectApedia

Share this article:

Search the InspectApedia website

Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.

Citations & References

In addition to any citations in the article above, a full list is available on request.



ADVERTISEMENT