FREE Encyclopedia of Building & Environmental Construction, Diagnosis, Maintenance & Repair The accuracy & trustworthiness of every article or Q&A is researched by human experts. See WHO ARE WE?
Arc Fault Interrupter AFCI Nuisance Tripping Definition of nuisance AFCI Tripping or Crosstalk Tripping & Why It's Dangerous
POST a QUESTION or COMMENT about buying, wiring, installing, & using AFCIs and the performance and about possible nuisance tripping of arc fault circuit interrupters
Nuisance tripping of an electrical safety device such as an AFCI refers to annoying and un-necessary shut-downs of an elecrical circuit, device, or appliance that was unnecessary and/or did not represent a condition for which the device was designed and intended to operate.
Nuisance tripping of AFCIs may be a more-serious problem than it first appears, as annoying and pereceived-incorrect or unnecessary operation of any safety device may lead a consumer or building occupant or even a licensed electrician to subvert or even remove the device, thus leaving real safety hazards un-protected.
This article series about AFCIs combines electrical code information, studies & reports of AFCI performance, field experience with AFCIs, and information from the U.S. CPSC on AFCIs with additional details and commentary answers most home owner and home inspector questions about installing, testing, and inspecting AFCIs - arc fault protectors in homes.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?
Electrical Arc Fault AFCI Nuisance Tipping or Crosstalk Problems
This material was originally prepared by DF for the American Society of Home Inspectors New England Chapter,(
ASHI -NE) Educational Seminar, Sept 22-23, 2008.
Portions of this text are quoted from the Arc Fault Circuit Interrupter
(AFCI)
FACT SHEET provided by the US CPSC .
Coffee Maker Demonstrates Early warning about nuisance tripping of AFCI circuit breakers and consumer objections to these devices
AFCIs devices are tested under the UL 1436 standard, and are required to have included in the instructions the following clause (or equivalent):
"CAUTION: AFCIs recognize characteristics unique to arcing, and AFCI indicators produce characteristics that mimic some forms of arcing.
Because of this the indicator may give a false indication that the AFCI is not functioning properly. If this occurs, recheck the operation of the AFCI using the test and reset buttons. The AFCI button test function will demonstrate proper operation."
Watch out: we have heard several reports of excessive "nuisance" tripping of arc fault circuit interrupters, and our own limited testing has confirmed this problem in our laboratory where we installed the coffee maker shown at left.
On a newly-wired AFCI electrical circuit with tight, well-made connections and powering a string of electrical receptacles, we connected a single device: a Keurig™ coffee maker to the circuit (photo at left). The circuit also supports a wall mounted light that uses florescent bulbs. No other devices were connected to the circuit.
The coffee maker was set to turn itself off automatically after one hour of idle time. Yet consistently over 30 days of testing, every day we observed that the 15-A Square D AFCI for this circuit tripped off at least once.
We suspect that electrical properties of the coffee maker may have been the source of noise on the circuit that was causing the AFCI to switch off. Replacing the AFCI with a conventional 15-A Square D circuit breaker completely eliminated the nuisance tripping on this circuit.
Three other AFCIs were installed in the same electrical panel, but only one was connected to an electrical circuit in active use. On that circuit, also supporting a string of electrical receptacles powering lighting and computer equipment during the same 30-day test period, no nuisance trips of the circuit were observed.
Photo: a view of the interior components and the three wiring connection points of an AFCI circuit breaker, courtesy Dr. Jess Aronstein.
[Click to enlarge any image]
Watch out: do not attempt to disassemble an AFCI nor any other circuit breaker. Disassembly is not required for making proper electrical connections, and doing so is likely to make the circuit breaker unsafe or unreliable.
installing AFCIs on multi-wire branch circuits using a shared neutral requires installation of a common trip tie, and nevertheless the circuit and this circuit protection device may be subject to further nuisance trips or unexpected behaviors.
Watch out: An installing electrician informed us that many of his customers were complaining about nuisance tripping and that he was asked by those clients to remove the AFCI devices and to replace them with conventional circuit breakers. This raises an issue about national and local electrical code compliance and about building electrical and fire safety - removing a code-required safety device.
Further testing of the nuisance-tripping AFCIs as well as three others installed in the same electrical panel and samples of non AFCI breakers of the same age, rating, and brand is underway and will be reported here.
Nuisance tripping refers to a circuit breaker or an AFCI that trips off, turning off electrical power when there was no apparent reason to do so.
In the photo I'm holding an AFCI-type circuit breaker after un-snapping it from its position in a Square-D electrical panel. I had to remove this breaker because of nuisance tripping.
Some sources assert that what appears to be "nuisance tripping" of AFCI's actually occurs due to wiring practices of some electricians more than for any other reason. These include
Reversed hot and neutral wires - reversed polarity - which is an unsafe condition
Shared neutral wiring on single pole circuit breaker circuits: this is already an existing problem with GFCI's on multiwire branch circuits.
Incorrect or accidental connections between the ground and neutral wire: this is also an unsafe condition which can permit live current to flow on a ground wire that should normally never carry current. We've personally seen this condition lead to an electric shock.
A common source of accidental ground-neutral connections occurs when an electrician over-tightens the clamp connector on BX (armored cable) where it connects to a steel junction box. Our ex-brother-in-law made this mistake at every single BX connector when he did his own over-zealous wiring in a New York City apartment.
When he installed a GFCI circuit breaker to protect some circuits, he could not keep the breaker from tripping immediately whenever power was turned on.
We saw that his over-tightening the connector pinched inwards the edges of the BX cable. If the BX cable edge cuts into the hot wire the electrician (or Matthew) discovers this fault immediately when power is restored to the circuit.
But if the cable edge cuts into the neutral wire, the electrician (or our brother in law) does not discover this fault until a GFCI or an AFCI is installed on the circuit, or until someone touches a supposedly safe armored cable wire exterior and gets a shock.
Normal arcing in appliances: Nuisance tripping that could occur from the normal arcing that occurs in some appliances (such as a vacuum cleaner motor) has been considered in the design of the AFCI circuit. The AFCI is designed to tell the difference between this ordinary arcing and the type of arcing in a circuit that may cause a fire.
The experts also use the term "crosstalk" in discussing nuisance tripping on AFCI circuits. Our first citation (Engel 2012) is discussed in more detail in the article above where readers will also find a link to the full-text of the article. The other citations are examples of research papers discussing crosstalk and nuisance tripping in AFCI breakers.
Engel, Joseph C. "Combination AFCIs: What they will and will not do." In 2012 IEEE IAS Electrical Safety Workshop, pp. 1-18. IEEE, 2012. Abstract:
All new home branch circuits are required by Code to be electronically protected, either by Ground Fault Circuit Interrupters (GFCIs) or Arc Fault Circuit Interrupters (AFCIs). Areas including kitchens, bathrooms, garages, etc. must be protected by GFCIs, while living areas must be protected by AFCIs.
The AFCI is the fourth generation in residential branch circuit protection after fuses, circuit breakers, and GFCIs. National Electrical Code in 2002 first added AFCI protection, for bedrooms outlets.
In 2008, coverage was expanded to all living areas, also adding that only “Combination AFCIs” are allowed. Manufacturers and UL claim that arcing across a break in a cord's conductor is hazardous, and that a Combination AFCI will respond to prevent a fire.
The author believes the claim is unproven, and will explain why the disallowed Branch/feeder AFCI provides more protection at less cost.
Restrepo, Carlos E. "Arc fault detection and discrimination methods." In Electrical Contacts-2007 Proceedings of the 53rd IEEE Holm Conference on Electrical Contacts, pp. 115-122. IEEE, 2007.
Johnson, Jay, and Jack Kang. "Arc-fault detector algorithm evaluation method utilizing prerecorded arcing signatures." In Photovoltaic Specialists Conference (PVSC), 2012 38th IEEE, pp. 001378-001382. IEEE, 2012.
Johnson, Jay, and Jack Kang. "Arc-fault detector algorithm evaluation method utilizing prerecorded arcing signatures." In Photovoltaic Specialists Conference (PVSC), 2012 38th IEEE, pp. 001378-001382. IEEE, 2012.
Ming, Zong, Yang Tian, and Fengge Zhang. "Design of arc fault detection system based on CAN bus." In Applied Superconductivity and Electromagnetic Devices, 2009. ASEMD 2009. International Conference on, pp. 308-311. IEEE, 2009.
How to Report an AFCI or other Electrical or Product Failures or Incidents to the U.S. CPSC
Question:
AFCI vs grandfathering homes older than 2008
This does not address grandfathering for homes older than 2008! - John, 7/24/2011
Reply:
Granfathering and the AFCI requirement: good point, John. We find a variety of opinions among building code officials. At a recent building addition project the BCO wanted AFCIs in the new sub panel in keeping with the new electrical code AFCI recommendations, but he also decided that other areas in the home needed certain updates too.
Other electrical inspectors and building code inspectors look only at the new work - I'd say that's the most common case. Only when an older home is being renovated to include electrical work will most inspectors call for current codes to be complied-with.
A more subtle exception occurs in the case of egregious electrical hazards: when an older home is being purchased, some lenders and some insurance companies may require certain updates such as in panel ampacity or in replacement of some of the more troublesome brands (FPE Stab-Lok is an example.)
Question: are AFCI's required on lighting-only circuits?
do you have to use arc fault on lighting only circuits? - Hugh Owen 8/22/2011
Reply:
Yes. On the illustrations I've seen the overhead lighting circuits were included. see 210.12(B) Dwelling Units - quoting the Minnesota Electrical Association reference found at the bottom of this article:
Combination-type AFCI-protective devices are now required in all dwelling unit rooms, except for kitchens, bathroom, garages, basements, and rooms or areas not specified in this section. This continues the incremental migration to provide whole-house AFCI protection for dwelling units that was the objective of the original proposals in the 1999 NEC development cycle.
This section was revised to include a list of rooms and areas where the serving branch circuits are to be protected by arc-fault circuit-interrupter protection. Essentially, the requirements for this protection are expanded to most areas and rooms in the dwelling unit with the exception of those named above and other areas or rooms not specifically identified in this section. The AFCI-protective devices must be listed combination types.
Question:
I don't have space in the panel to make proper ground bus connections. - Roger 9/11/11
Reply:
Roger, as long as your panel won't be overcrowded, you can always add an additional ground bar (or neutral bar) in the existing panel, connecting it to the originals and locating it where your AFCI white wire will reach.
Question:
I have a Sylvania main breaker panel in an existing dwelling. I am adding 3 circuits to basement finish. Inspector wants a Listed product for the panel . Any idea what AFCI breaker I can use? - Nice Article 12/10/11
Reply:
Nice:
Any AFCI breaker sold at any electrical supplier will be code compliant. Just how well the product works is a different issue as discussed in this article. Be sure to see the comments and links to Dr. Engel's paper given in FAQs. below.
Question: having trouble wiring 14-3 wired homes
How to deal with 14-3 wired rooms. I need AFCI for the outlets and the lighting, I have wired 14-3 and would need a special AFCI that doesn't seem to be offered by Square D. - Eric J 5/22/2012
Reply:
Erick J
You raise an important question: how to use AFCIs or GFCI's on 3-wire circuits. I don't know a solution and so far the solution certainly is not offered in the device itself. We have ongoing reports as well as direct experience with nuisance tripping and so unreliable behavior when AFCIs or GFCI's are installed on shared-neutral circuits.
The electrician I worked with most recently says he's changed is policy and won't install 3-wire shared neutral circuits where an AFCI or GFCI is going to be required.
In sum, AFCI's are NOT going to work properly on shared-neutral electrical circuits; neither do GFCIs.
Question: Nuisance Tripping of AFCI devices on circuit used to power a TV
I have two Seimen's AFCIs for 3 bedrooms. They were placed approx spring 2004 in a new build. No problems until several months ago with LED TV in master bedroom. Breaker would trip upon trying to turn on tv on rare occasion. At first seemed overload but now it trips every time TV is turned on.
TV is tripping the other AFCI in the other bedrooms as well. It IS NOT tripping the standard breakers elsewhere in the house. Are these older model AFCIs needing replaced to handle the load of the new appliances? Have new breakers become more reliable as stated above at avoiding nuisance tripping (which I assume this is)? - Kathy 8/20/2012
Reply: how to report AFCI problems to the US CPSC:
You are reporting nuisance tripping.
You should also contact the US CPSC directly to make your concerns known.
Question: nuisance tripping of AFCI circuit with ham radio equipment.
i have ham radio equipment the AFCI is reading the fluctuating current demands as arching. breaker constantly trips. this is a pain! can i safely replace the afci with a standard breaker? - Paul 8/23/2013
Reply:
Paul this sounds like another instance of nuisance tripping. You can replace the AFCI with a standard breaker and stop the tripping problem; you will be giving up what limited added safety protection the AFCI offered, and you could face a technical issue with your local electrical inspector.
You should also contact the US CPSC directly to make your concerns known.
Questions/comments: on AFCI's: Reference to Engel (2012)
DanJoeFriedman (mod) said:
Repeating Steve's suggestion 1/31/13 that we read Joe Engel's paper on Combination AFCIs, we contacted Mr. Engel as well, and appreciate your contribution of a publicly-available copy of this important paper. In the article above we include a reference and link to
Joseph C. Engel, PhD., IEEE, "Combination AFCIs" What they Will and Will Not Do", IEEE, 2012
Question/comment:
(Sept 2, 2011) Honest Electrician said:
How much money has been paid to the NFPA to make AFCI breakers code since there have been arc outs and fires on protected circuits and they were introduced as code before they were available
Questions: AFCI be used to protect Alum branch wire circuits
(Sept 19, 2014) Mike said:
Can a AFCI be used to protect Alum branch wire circuits
Reply:
Yes, and no.
yes if the AFCI is connected using CPSC-recommended methods (AMP TYCO COPALUM or the King Innovations AlumiConn) to connect the device to the circuit
No if you are thinking of direct-wiring the device to the aluminum wire. I have personally seen an aluminum wired test circuit overheat and begin to burn (we turned off power at that point) while powered through an AFCI.
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Ask a Question or Search InspectApedia
Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.
Search the InspectApedia website
Note: appearance of your Comment below may be delayed:if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.
Only one image can be added per comment but you can post as many comments, and therefore images, as you like.
You will not receive a notification when a response to your question has been posted. Please bookmark this page to make it easy for you to check back for our response.
Our Comment Box is provided by Countable Web Productions countable.ca
In addition to any citations in the article above, a full list is available on request.
Dr. Jess Aronstein, protune@aol.com is a research consultant and an electrical engineer in Schenectady, NY. Dr. Aronstein provides forensic engineering services and independent laboratory testing for various agencies. Dr. Aronstein has published widely on and has designed and conducted tests on aluminum wiring failures, Federal Pacific Stab-Lok electrical equipment, and numerous electrical products and hazards.
Contact: J. AronsteinConsulting Engineer Bme, Msme, Ph.D., N.Y.S.. P.E. Lic. No. 39860, 909 Londonderry Ct., Schenectady, NY 12309 USA, Tel: (845) 462-6452 Email: AronsteinJesse@ieee.org
Steel, J. G., and D. T. Swift-Hook. "Statistics of circuit-breaker performance." Electrical Engineers, Proceedings of the Institution of 117, no. 7 (1970): 1337-1345.
Lai, M. L., S. Y. Park, C. C. Lin, H. Naidu, A. Soom, A. M. Reinhorn, Y. H. Lee et al. "Mechanical failure detection of circuit breakers." Power Delivery, IEEE Transactions on 3, no. 4 (1988): 1724-1731.
[1] AFCI Circuit Interrupters, US CPSC Publication www.cpsc.gov/CPSCPUB/PUBS/afcifac8.pdf, with extensive edits and additions by the website author. Original source cpsc.gov/CPSCPUB/PUBS/afcifac8.pdf
[2] Note 1 Ault, Singh, and Smith, “1996 Residential Fire Loss Estimates”, October 1998, U.S. Consumer Product Safety Commission, Directorate for Epidemiology and Health Sciences.
[3] Schneider Electric, North American Operating Division, 1415 South Roselle Road, Palatine IL 60067 16 December 2004 , Letter addressed to Dan J Friedman, from Jim Pauley, Vice President, Industry and Government Relations.
[4] Underwriters Laboratories (UL) describes the the types of AFCIs and the types of tests performed on AFCIs at www.ul.com/regulators/afci/AFCI_scenarios020502.pdf. Also, UL 1699, “Standard for Arc-Fault Circuit Interrupters” at the UL website provides more detailed information on the differences between the older AFCI's and the new combination type devices.
[5] Nuisance tripping of AFCI's is described in detail, along with other details about AFCIs in an online article, "Arc Fault Detection: your questions answered", ecmweb.com, August 2008.
[6] Mike Holt, in our opinion the leading writer about electrical wiring and devices, has a nice article about AFCIs at https://www.mikeholt.com/mojonewsarchive/AFCI-HTML/HTML/Arc_Fault_Protection~20020124.htm Mr. Holt discusses current electrical code requirements for GFCIs (Ground Fault Circuit Interrupters) at http://ecmweb.com/mag/electric_branch_circuits_part_2/.
[7] Testing of AFCIs using external devices (not the test button): see article by Underwriter's Laboratories (UL) March 21, 2005 at https://www.ul.com/tca/winter05/news.html and this comment by Ryan Jackson at Mike Holt's website: (a reply from Jim Gregorec,
Group Manager - T&M Division, Ideal Industries posted at the website takes a different view which is also posted there)
[8] To paraphrase the article, there is no such thing as an AFCI tester, other than the test button that is an integral part of the AFCI device itself.
The reason for this is that an AFCI device is very complex, and recognizes the actual waveform of an arcing fault.
While the advertised "AFCI Testers" do produce a waveform similar to that of an arc fault, they cannot produce an actual arc fault. Because of this, the "tester" may not trip the AFCI circuit breaker, despite the breaker having nothing wrong with it. For this reason, UL classifies these devices not as "testers", but as "indicators", which is much more accurate.
[8] These devices are tested under the UL 1436 standard, and are required to have included in the instructions the following clause (or equivalent):
"CAUTION: AFCIs recognize characteristics unique to arcing, and AFCI indicators produce characteristics that mimic some forms of arcing. Because of this the indicator may give a false indication that the AFCI is not functioning properly. If this occurs, recheck the operation of the AFCI using the test and reset buttons. The AFCI button test function will demonstrate proper operation."
[10] While these indicators may have some value for convenience to determine if the outlet in question is on an AFCI protected circuit, they are not to be substituted for the test button of the AFCI circuit breaker, and they are not an AFCI tester.
[13] GE, General Electric Corporation, General Electric Company,
41 Woodford Ave., Plainville, CT 06062, one of the companies producing AFCIs, provides wiring diagrams and installation instructions for their product. See GE's DEH-40117R4.pdf for detailed installation instructions from GE for the wiring of a typical AFCI on a simple 120V home electrical circuit.
[14] The Minnesota Electrical Association has posted an article of the most important electrical code changes for 2008 at http://www.electricalassociation.com/catalog/2008NECTop10.aspx - by Michael J. Johnston, IAEI
[15] "HUD Regulation for Manufactured Homes; Requirement that Heat-Tape not include a GFCI [ copy on file as /plumbing/GFCI_Heat_Tapes_HUD_CPSC_Letter1994.pdf ] - ", Meeting Log, US CPSC, HUD, Dennis McCoskrie, ESEE, 2/14/1994
[16] Personal communication, [electrician P prefers to remain anonymous], to DJF, 1/29/2012.
[17] Joseph Engel, "Ground Fault / Arc Fault Circuit Interrupter and Method of Testing the Same with a Test Button and a Resest Button", Patent No. 6,720,872 B1, Apr. 13, 2004. [copy on file as AFCI Patent US6720872.pdf and as AFCI_Patent_History.pdf]
[18] Engel, J.C., "Combination AFCIs: What they will and will not do", Electrical Safety Workshop (ESW), 2012 IEEE IAS, Jan. 31 2012-Feb. 3 2012, pp. 1 - 18,
Conference Publications, 9 March 2012, INSPEC Accession Number: 12578656. Mail: Joseph C Engel, PhD,
Member, IEEE,
107 Overlook Circle,
Monroeville PA 15146
USA, Email: josephengel1013@gmail.com
Abstract: All new home branch circuits are required by Code to be electronically protected, either by Ground Fault Circuit Interrupters (GFCIs) or Arc Fault Circuit Interrupters (AFCIs). Areas including kitchens, bathrooms, garages, etc. must be protected by GFCIs, while living areas must be protected by AFCIs.
The AFCI is the fourth generation in residential branch circuit protection after fuses, circuit breakers, and GFCIs. National Electrical Code in 2002 first added AFCI protection, for bedrooms outlets.
In 2008, coverage was expanded to all living areas, also adding that only “Combination AFCIs” are allowed. Manufacturers and UL claim that arcing across a break in a cord's conductor is hazardous, and that a Combination AFCI will respond to prevent a fire.
The author believes the claim is unproven, and will explain why the disallowed Branch/feeder AFCI provides more protection at less cost. Dr. Engel provides this link for a downloadable copy of this paper: http://www.combinationafci.com/
[18b] Engel, J.C., Aronstein, J., & Friedfman, Daniel J, personal correspondence 2/8/2013.
[19] Wafer, J.A., "The evolution of arc fault circuit interrupters", Electrical Contacts, 2005. Proceedings of the Fifty-First IEEE Holm Conference,
26-28 Sept. 2005, Eaton Corp., Pittsburgh,pp. 156 - 161 Abstract:
Traditionally, circuit breakers and fuses have provided overcurrent and short circuit protection in electrical distribution applications. Despite this protection, approximately 70,000 residential fires with more than 500 deaths and in property damage occur each year in the U.S. that are attributed to electrical initiation.
When investigated it was found that in some cases the circuit breaker had not tripped. Arc fault circuit interrupters can recognize the unique signatures of arcing faults and initiate a trip condition to isolate and de-energize the arcing fault.
This paper identifies the conditions that can lead to fire hazards. These include arcs to ground, wiring failure modes, earth leakage conditions and high resistance faults such as glowing contacts, and in-line low current arcs (sometimes referred to as series arcs).
[20] Douglas A. Lee,
Andrew M. Trotta,
William H. King Jr., "New Technology for Preventing Residential Electrical Fires: Arc-Fault Circuit Interrupters (AFCIs)",
Fire Technology
August 2000, Volume 36, Issue 3, pp 145-162,
Abstract:
A new generation of residential electrical branch circuit breakers that incorporates technology to detect and mitigate the effects of arcing faults is described. Fire loss estimates attributed to electrical wiring and the development of the arc-fault circuit interrupter for the prevention of residential electrical fires are discussed.
The industry voluntary standard for arc-fault circuit interrupters as well as the 1999 National Electrical Code requirement are reviewed.
[21] Shea, J.J., "Conditions for series arcing phenomena in PVC wiring", Electrical Contacts, 2005. Proceedings of the Fifty-First IEEE Holm Conference on
Date of Conference: 26-28 Sept. 2005, Eaton Corp., pp: 167 - 175 Abstract
Under certain circumstances, unintentional series arcing, caused from damaged line cords and loose connections, can pose a serious fire and safety hazard.
This work, focusing on residential 115 Vac applications, shows how continuous bursts of ignited gases can be created from overheated PVC insulation created from glowing contacts with subsequent series arcing, or surface breakdown with subsequent series arcing.
Also, surprisingly, these potentially hazardous fire conditions were created with currents as low as 0.9 Arms, at 115 Vac (100 W lamp load). Little research is available about the interaction of glowing contacts, formed from loose or broken copper conductors in wiring (outlets, switches, line conductors, etc.), with electrical insulation.
This work shows how glowing contacts and surface arcing can decompose PVC insulation, form ignitable gases, and that it is possible for the subsequent series arc to ignite, and burn insulation. Two conditions are identified that can create an overheated connection - a glowing contact and/or breakdown over a charred insulation surface.
Mechanisms are discussed along with data for glowing contact voltage drop, photographs of glowing connections, and a gas chromatograph analysis of the evolved gases emitted from overheated PVC wiring.
Selected high-speed video frames (1000 fps) taken from videos of the series arc and bursts of ignitable gasses along with synchronized current and voltage waveforms over a current range of 0.9 Arms to 5 Arms are presented. These findings are useful for advancing the state-of-the-art in fire protection by providing a better understanding of how electrical fires can initiate.
[22] Restrepo, C.E., "Arc Fault Detection and Discrimination Methods", Electrical contacts - 2007, the 53rd ieee holm conference, 16-19 Sept. 2007, pp. 115 - 122 , Siemens Energy & Autom., Norcross, Abstract:
Arc waveform characteristics can be evaluated with various methods to recognize the presence of hazardous arc fault conditions.
Discussion covers the arc phenomena and how it is generated in a low voltage electrical distribution circuit, as well as the isolation of the presence of hazardous conditions versus conditions that could falsely mimic the presence of an arc fault.
Many waveform characteristics and conditions support the detection of hazardous arc faults and foster a more robust design, capable of withstanding unwanted tripping conditions.
[23] Parise, G., "Arc-fault protection of branch circuits, cords and connected equipment" Industrial and Commercial Power Systems, 2003. 2003 IEEE Technical Conference, 4-8 May 2003,
Dipt. di Energia Elettrica, Rome Univ., Italy
Martirano, L. ; Nabours, R.E., pp: 85 - 88, Abstract:
In electrical power systems, the fault frequently involves arcing and burning for all the wiring exposed to mechanical damage and other insulation stresses including wiring not fixed and connected by flexible cords and cables.
The IEC Standard 60364 stops the design of electric power systems at the outlets of branch circuits or at the fixed equipment. A complete design instead should take care of the connections of the portable equipment and of extension cords (as requested by NFPA 70) that are exposed to arc-faults and may cause fire and/or electric shock hazard.
The cords supplying the Class II equipment are without a grounding protection conductor, so the failure of the double insulation, caused by external damage, can't be expected to be easily detected as a ground fault.
A protection must be provided to prevent the fault from extinguishing itself without being detected and remaining energized, thus presenting an electric shock hazard by direct contact with a live part, rendered accessible after local insulation failure.
The authors highlight this worst case and suggest the protection achieved by wiring the circuits, particularly extension cords, with special power cables. Ground-fault-forced cables, GFFCs convert a line-to-line fault into a line to ground fault, that will be detected and protected by ordinary ground fault protective devices (GFPDs).
By adopting the GFFC type of cables internally to Class II equipment, the disconnecting supplying measure could be extended to equipment also.
[24] Gregory, G.D., "More about arc-fault circuit interrupters" Industry Applications Conference, 2003. 38th IAS Annual Meeting. Conference Record, 12-16 Oct. 2003
Author(s): Gregory, G.D. Schneider Electr., Square D Co., Cedar Rapids, IA, USA, Kon Wong ; Dvorak, R.
Volume: 2, pp: 1306 - 1313 vol.2 Abstract:
Since the arc-fault circuit interrupter (AFCI) was commercially introduced in 1998, questions have arisen about how it detect arcs, whether it detects series and parallel arcs, and what types of AFCIs are available. Types other than the original branch/feeder AFCI are emerging.
This paper is intended to provide an update regarding answers to those questions, following an earlier paper that introduced the basic functioning of the AFCI (see G.D. Gregory et al., IEEE Trans. Ind. Apps., p. 928-33, 1998).
[25] Gammon, T., Matthews, J., "Instantaneous arcing-fault models developed for building system analysis", Industry Applications, IEEE Transactions on, Jan/Feb 2001, Volume: 37 , Issue: 1
Page(s): 197 - 203. Abstract:
An arcing fault is a dangerous form of short circuit that may have a low current magnitude. In the case of such faults, the magnitude of the current is limited by the resistance of the arc and may also be limited by the impedance of a ground path.
This lower level fault current is often insufficient to immediately trip phase overcurrent devices, resulting in the escalation of the arcing fault, increased system damage, tremendous release of energy, and threat to human life.
Despite modern advances in system protection and the adoption of National Electrical Code Section 230-95, people continue to be injured or killed from arcing faults, initiated by accidental physical contact or through a glow-to-arc transition.
The initial phase of an arcing-fault research project was to review the historical evolution of arc modeling for low-voltage systems. A summary of the electrical aspects and the physics involved in arcing faults appeared in previous work.
Today's better analytical tools facilitated the development of new instantaneous arc models with current-dependent arc voltages, which better represent the arcing phenomenon than the assumed arc voltage associated with previous instantaneous arc models.
The arc currents in a typical medium-size building system are determined and harmonic analysis is performed Excerpt: "ARCING FAULTS have been recognized as a potential hazard in low-voltage systems as far
back as the 1920s [1]"
[26] Gammon, T. & Matthews, J., "The historical evolution of arcing-fault models for low-voltage systems", Industrial & Commercial Power Systems Technical Conference, 1999 IEEE.
Aug 1999 Abstract:
An arcing fault is a dangerous form of short-circuit that may have a low current magnitude. In the case of such faults, the magnitude of the current is limited by the resistance of the arc and may also be limited by the impedance of a ground path.
This lower level of fault current is often insufficient to immediately trip overcurrent devices, resulting in the escalation of the arcing fault, increased system damage, tremendous release of energy and threat to human life.
Despite modern advances in system protection, many people are critically injured or killed each year as a result of such faults. The initial phase of an ongoing arcing-fault research project was to review the pioneering work, dating back to the 1920s.
After a comprehensive literature search was completed, today's sophisticated analytical tools are aiding development of a new arc model. An improved arc model will more accurately calculate the arc currents in an actual arcing event.
This paper summarizes the physics involved and describes the historical evolution of arc modeling. The condensed review presented in this paper facilitates a better understanding of arcing faults in low-voltage power systems; in addition, it serves as a foundation for current and future research
In addition to citations & references found in this article, see the research citations given at the end of the related articles found at our suggested
Carson, Dunlop & Associates Ltd., 120 Carlton Street Suite 407, Toronto ON M5A 4K2. Tel: (416) 964-9415 1-800-268-7070 Email: info@carsondunlop.com. Alan Carson is a past president of ASHI, the American Society of Home Inspectors.
Carson Dunlop Associates provides extensive home inspection education and report writing material. In gratitude we provide links to tsome Carson Dunlop Associates products and services.