Sound Transmission Class - STC & Sound Reduction Index - SRI & OITCSTC: Sound Transmission Classes:
Building Noise & Sound Transmission Levels & Sound Isolation or Insulation Measurements.
This article discusses methods for controlling sound transmission through building walls. Here we define STC - sound transmission class and we provide a table of design details that show STC rating for various building wall framing designs. Sound transmission reduction wall designs are given for both single stud and staggered double stud structural and partition walls. We include soundproofing suggestions for high noise level areas such as music rooms as well as areas where privacy is a concern such as in counseling and psychotherapy offices.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?
This article series discusses noise and sound control in buildings, and includes excerpts or adaptations from Best Practices Guide to Residential Construction (Steve Bliss, J Wiley & Sons) , by Steven Bliss, courtesy of Wiley & Sons.
How effectively a wall or floor reduces airborne sound is measured by STC ratings (sound transmission class). Roughly speaking, the STC rating equals the reduction in decibel levels across the partition. (see Table 5-15).
[Click to enlarge any image]
Sound Transmission Class (STC) is defined in the ISO-140 standards series. Sound Reduction Index (SRI) is defined in ISO-140 (2012).
Sound Transmission Class (or STC) is an integer rating of how well a building partition attenuates airborne sound. In the USA, it is widely used to rate interior partitions, ceilings/floors, doors, windows and exterior wall configurations (see ASTM International Classification E413 and E90).
Outside the USA, the Sound Reduction Index (SRI) ISO index or its related indices are used. These are currently (2012) defined in the ISO - 140 series of standards (under revision). The STC rating figure very roughly reflects the decibel reduction in noise that a partition can provide - Wikipedia 10/21/2013 [3]
STC or sound transmission class is defined as the level of reduction of sound transmission from outside noise sources to the building interior. Higher STC numbers mean higher resistance to sound transmission to the building interior, or as acousticians would describe it, higher STC means greater sound transmission loss between outdoors and the building interior. Typical STC values for metal buildings are STC=20 to STC=55.
OITC or Outdoor-Indoor Transmission Class describes the sound transmission loss properties of building exterior components like windows and walls against noise from traffic, trains, or low flying aircraft. - General Steel Corporation [4]
So, for example, a 50 dB noise on the other side of an STC 35 wall will sound like a 15 dB noise to the average listener (see our Table of STC ratings and noise reduction left).
Walls and floors in the field often measure lower than in laboratory ratings due to variations in workmanship as well as leaks and bypasses.
The higher the STC rating, the more likely it is to be compromised by site conditions. For that reason, it is best to select a building assembly rated at least 5 points above the design goal.
This topic has been moved to SOUND CONTROL for WALLS
-- Adapted with permission from Best Practices Guide to Residential Construction (Steve Bliss, J Wiley & Sons) .
Our building sound control articles begin at SOUND CONTROL in buildings. Other noise and sound diagnosis and control articles are found at NOISE / SOUND DIAGNOSIS & CURE.
(Sept 22, 2014) M.A.Rahman said:
What is the relation between Sound Transmission Class & Sound Reduction Index?
Reply:
M.A.
acoustic-glossary.co.uk offers nice definitions of the term Sound Reduction Index:
Definition of Sound Reduction Index: R : the measured quantity which characterises the sound insulating properties of a material or building element in a stated frequency band - laboratory measurement.
R = L1 - L2 + 10 lg S/A (dB)
where:
L1: average Sound Pressure Level in the source room
L2: average sound pressure level in the receiving room
S: area of the test specimen (m2)
A: Equivalent Sound Absorption area of the receiving room
In comparison
Definition of Sound Transmission Class or STC as author Steve Bliss uses it here, is a American term providing a single number rating of a partition's isolation value based on laboratory measurement.
STC Results may not be compatible with Rw (the weighted "apparent" sound reduction index) as a different range of frequencies is used.
...
Continue reading at SOUNDPROOFING MATERIAL PROPERTIES or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see
NOISE / SOUND DIAGNOSIS & CURE
SOUND CONTROL in BUILDINGS - home
SOUND TRANSMISSION CLASS RATINGS at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Questions & answers or comments about noise & sound transmission through building walls - sound transmission pathways and how to control noise or sound in buildings
Search the InspectApedia website
Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.
In addition to any citations in the article above, a full list is available on request.