InspectAPedia®

Photograph of a filthy air conditioning air handler filter HVAC Air Filter Location & Renewal
How to Find & Change the Air filter on an Air Conditioner or Furnace

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.


Where air filters are installed on air conditioning or heating systems:

This article explains in detail how to find the air filters on an air conditioning or hot air heating system.

Knowing where air filters are typically located can help find dirty or clogged air filters that are increasing air conditioning or heating cost. Before assuming that your HVAC system does not have an air filter installed, or that it has only one air filter installed, check the locations we describe here.

We also provide a MASTER INDEX to this topic, or you can try the page top or bottom SEARCH BOX as a quick way to find information you need.

AIR FILTER LOCATION - How to Find the Air Conditioning Filter on Air Conditioners or Hot Air Heating Systems

Ceiling mounted central air return on an air conditioning or heating system (C) Daniel FriedmanIf you can't find your air conditioner system filters (there may be more than one air filter) here are some places to look.

After reviewing this list of air filter locations, if you still cannot find your heating or air conditioning system air filter read our detailed instructions on how to find air filters which follows just after this list.

Photo: a ceiling return air inlet for an air conditioning system in a U.S. home. In a two-story home the contractor often locates this return centrally near the top of a stairwell.

Attic air handler unit AHU showing key components (C) Daniel Friedman

[Click to enlarge any image]

Basement furnace air handler showing return air path & supply air path (C) Daniel Friedman

Above: this basement oil-fired heating furnace is an up-flow unit: return air from the building (blue arrows) moves from the building's occupied space through return ducts (blue arrows) into the bottom of the heater.

Heated air moves out of the unit into supply ducts (red arrows) and back into the building.

[Click to enlarge any image] to see more detail.

Watch out: We marked in yellow an unsafe return air inlet grille placed right in the basement on the reutrn air plenum itself.

Someone probably added this air inlet (yellow arrows) to improve the total air flow through the system, but drawing return air from close to the oil or gas burner on a furnace can

Also see UNSAFE DUCT OPENINGS for more about this hazard.

Below: a closer-look at an air filter slot at a typical upright air handler on a basement heating or heating+air conditioning system.

Air filter slot at the return air inlet at the bottom of a basement air handler (C) Daniel Friedman

Below: this photo shows a very common air filter location: behind a service door on the back of an upright warm air furnace or furnace/air conditioner combination unit.

Photograph of a filthy air conditioning air handler filter

Air filter location above an electrostatic air cleaner (C) Daniel Friedman

If after reading this catalog of air filter locations you still can't find your air filter, below we provide AIR FILTER LOCATION-MORE examples of where and how to look for filters on an air conditioning or hot air heating system.

A Detailed Guide on How to Find the Air Filters on an Air Conditioning or Heating System

Photograph of central air returnCentral air conditioning filters (or heating system filters if hot air heat is used as well) are sometimes hard to find. Here are some tips on where to look to find the filters on your central air conditioning system:

How to Find Air Conditioning Filters Located in the Air Duct System

Central Air Return Registers and Filters on Air Conditioning or Heating Systems

Central air returns - Air conditioning filters located on central air return registers:

if the system uses one or just a few central return registers very often a filter is placed behind the inlet grille at the central air return and is easily spotted in installations such as this Arizona central air conditioning air return inlet in the ceiling of a new home - the large rectangle is a return inlet where the air filter is quite visible.

In this photo the small opening is a poorly-installed supply register - air coming out of this register will simply be drawn right back into the return air inlet and won't do much good for the rest of the building.

Look for central air returns on building ceilings and WALLS [photo] in central areas such as in the ceiling near the top of a stairwell to an upper floor, or on lower floors look on hallway ceilings. Below is a central air return on the wall of a New York home.

Wall mounted central air return with air filter (C) DanieL Friedman

This wall return air inlet sports a pleated air filter right behind the hinged grille opening. To minimize the airborne dust levels in this home we used a CASCADED AIR FILTER DESIGNS for which the wall filter shown here was the easily-accessed first-stage of dust filtration.

Floor mounted return air inlet (C) Daniel Friedman

Don't forget to look for central air return registers on floors too, such as shown in this photo of a return air inlet in the front hallway of an older New York home.

We noted that a bit of reduction in air flow and a bit of increase in home heating cost may be the result of leaving stuff on top of the return air inlet.

Photograph of central air returnSometimes there will be a central air return in a ceiling but without any filter as shown in our photo at above/left and in this additional example of a WALL MOUNTED RETURN AIR INLET [photo] .

In that case we'd expect to find an air filter at the air handler unit.

It is usually been better to put the filter at the wall or ceiling return register grille since that way the return air ducts are protected from debris accumulation.

Central return registers are normally located in one or two common areas of the building where they will not be accidentally "shut off" by someone closing a door.

For example, a bedroom won't normally have a central return register since closing the bedroom door would shut off other building areas from the return air path.

This photo shows what you'll see when you open a ceiling return air register and remove the filter that (should have been) installed there. The duct surfaces in this ceiling look rather clean - the filter has been doing its job.

You may see house dust deposits around the edges of the opening into which the air filter is mounted - showing where air bypass leaks are occurring.

Some air filters include a gasket to seal these locations against air and dust leakage. Sometimes these leaky openings at air filters also cause noises when the air handler is running.


Photograph of unsafe basement reuturn air grille

Watch out: If a building air conditioning or heating system air handler gets its return air right at the air handler such as in this photo of a basement air handler the system has several operating problems: it is unsafe if it can draw combustion gases or mold into the duct system, the system lacks adequate return air and so will not deliver good air flow into the living area.

And the system will have high operating costs because the air flow is "one-way" drawing constantly "new" air from the basement into the air handler to be warmed or cooled and sent "one way" into the living area. Return ducts should bring air from the living are back to the air handler for cooling or warming.

See BACKDRAFTING HEATING EQUIPMENT and

also COMBUSTION AIR for TIGHT BUILDINGS for additional details.

Individual Room Air Returns and Filters on Air Conditioning or Heating Systems

Individual room air returns - look in each room where there is an air conditioning supply register to see if the room also contains a return air registers.

Since some rooms have multiple air supply registers and ducts we need to know how to distinguish a supply air register from a return air register.

How to identify individual room supply air registers

Photograph of an old supply air register

The supply registers are usually located in a ceiling [photo] or in a building wall [photo] but may be in a floor too (as shown here), usually near an exterior wall.

Air conditioning supply registers usually have an adjustable louver [photo] at a ceiling or wall supply register.

The louver (notice the little lever at the right end of the register cover?) that permits the air supply register to be opened or closed.

Which way is the air blowing, in or out of a heating or cooling register?

Photograph of an old supply air registerIf the heating or cooling system is operating, you can expect to feel air blowing OUT of a SUPPLY REGISTER [photo] and you may feel air moving into a return register.

But don't be confused. Air moving into a return register also may just be felt as an airflow across your hand and you may not be sure which way the air is moving.

Holding a simple piece of tissue paper next to an air register will by its movement show you for sure which way the air is moving.

How to identify individual room Return Air registers

Once you've located the air conditioning or heating air supply registers, look in the same room to see if there are other registers that collect return air to take it back to the air conditioning air handler.

Return air inlet registers are usually louvered as well, but will normally not have adjustable openings that can be opened or closed.

Main air filters are rarely installed on individual room return (or supply) air registers, but identifying the presence and the location of both supply and return air registers will help us understand whether or not the system uses central returns or individual room air returns, or a mix of both.

That in turn will tell us whether or not to look for filters at central return registers.

Individual air register filters: Sometimes you may see some filter like material installed right on individual air supply or air return registers in rooms.

These are usually "add-on" products that occupants have installed, perhaps in complaint that the duct system itself is dirty and that central filters have proven ineffective, or people may install individual register filters out of a general anxiety about building indoor air quality.

Tissue paper held in front of a weak air flowing supply register can still show that it's a supply not a return register (C) Daniel FriedmanOPINION: individual air supply or return register air filters are either ineffective (not trapping much debris), or if they are effective, they are at risk of significantly reducing the air flow into the rooms where they are used, reducing the effectiveness of the cooling or heating system or increasing system operating costs.

If the building duct system is so dirty that people are installing these filters it may be preferable to have the duct system professionally cleaned.

If a building uses both supply and return air registers in every room, that is, if it is not using central air return registers at just a few locations, then the air filters for the system are most likely going to be found on or very close to the individual air handlers or blower units themselves.

Photo: I'm holding a bit of tissue paper in front of an air register while the furnace (or air conditioner) is operating.

Even a weak air flow at a register will move the tissue showing the direction of air flow. This is a supply register: the tissue is blown away from the register's opening.

We would have guessed that this is a heat or cool air supply register by the presence of louvers inside of the register grille and by the control lever that can open or close them.

Operable control louvers to adjust air flow are normally found only on supply air outlets into the occupied space, while return air registers or grilles normally have no lever controls.

How to Find Air Filters Located At or Near Air Conditioning or Heating Air Handlers or Air Blower Units

When air filters are not found at return registers in a building the most likely place for an air filter to be found is at or even inside the air handler itself.

Some buildings use multiple air handlers, providing air conditioning and/or heating to individual floors or to different building areas on the same floor, so be sure you locate all of the air handlers or blower units in the building.

How to find Air filters located at the return air plenum next to the air handler unit

At the blower unit observe that large ducts will be connected to bring return air from building return ducts into the blower unit and to send conditioned air (cooled or warmed) out of the blower unit into the building supply ducts.

Look first outside the blower unit where return air is entering the blower cabinet.

How to Identify Horizontal, Vertical, Up-Flow or Down-Flow Air Handlers or Blower Units

Photograph of attic air conditioning

Air handlers are installed either horizontally (in an attic or crawl space) or vertically (in a basement, high attic, or other building area). Photos of horizontal and vertical air handlers are shown in this article and at our website.

Horizontal air handlers such as the attic mounted horizontal air handler in the photo above will have return air entering one end of the air handler unit and supply air exiting at the other end.

Photograph of vertical upflow  air conditioningVertical air handlers may be an "up-flow unit" which has return air entering at the bottom of the air handler or blower and conditioned air (cooled or warmed) exiting at the top of the unit.

The photograph shows a vertical or up-flow heating and air conditioner unit whose cooling section was mounted as an add-on atop a hot air furnace.

In this case the overhanging size of the top mounted cooling section suggests poor design - the sizes of the air moving sections are not matched.

Other vertical air handlers may be a "down-flow" unit which has return air entering the top of the air handler or blower and conditioned air passing out into supply ducts connected at the bottom of the unit.

Which side or end or top or bottom of the air handler blower has incoming return air and which has outgoing supply air?

Follow the duct work: If you were able to spot central or room air registers inside the living space, at the air handler unit you should be able to spot where those ducts enter the air handler itself. That will tell you which end of the air handler has entering return air.

Feel the outside temperature of duct work at the air handler: If you cannot determine where return air ducts are entering the air conditioning or heating air handler, if the system has been running in air conditioning mode the supply or outlet air end of the ducts connected to the air handler will be cool or even cold, and the return air end of the ducts connected to the air handler will be warmer to the touch.

If the system has been running in heating mode, the supply or outlet air ends of the ducts connected to the air handler will be warm to the touch and the inlet or return air ducts will be cooler.

How to find the Air Filter at but not inside of the Air Handler

Photograph of air conditioning air handler filter

Air handler filters may be located between the return air plenum and the rest of the air handler which contains a cooling coil for air conditioning or a heat exchanger for heating systems, and also a blower fan that causes air to move across these components and out into the supply ducts.

This photo shows an air filter located between a return air plenum (at photo right side) and the bottom of the air handler unit.

Photograph of air conditioning air handler filter slot

Locating the air filter slot at the air handler:: Now that you've identified the return air end of the air handler look closely in that area for a slot which is perhaps 1 1/2" wide and runs the entire width or height of the metal of the return air plenum (metalwork box connected to the inlet end of the air handler).

The slot may have a removable cover, but inside here should be located a central return air filter. Open the slot, remove the filter, and install a new filter. If an electrostatic air cleaner (photo) is installed at the air handler an air filter is usually installed in the air path just before or just after the electrostatic unit itself.

In this photo of a slot intended to receive an air conditioning filter at the blower unit, the filter had simply been left out and the slot left open - drawing dirt, debris, moisture, and mold from nearby basement areas. At the right side of the upper portion of the slot you can see our little piece of clear adhesive tape bending inwards, showing that air is flowing into the air handler at this filter slot.

How to find the Air Filter that is Located Inside of an Air Handler Blower Compartment

Photograph of a filthy air conditioning air handler filter

Many air conditioning system or warm air heating air handlers, both horizontal and vertical units, have one or more air filters that are installed inside of the blower assembly itself. These systems move air from a return plenum (connected to the return duct end of the system) across a cooling coil (for air conditioning) or a heat exchanger (for heating Systems).

On nearly all central air cooling or heating systems, the blower is located at the return air end of the system.

For many of these systems a filter or a set of air filters are located inside of the cabinet that contains the blower fan itself. Such systems can be recognized by a handle that is turned or pulled to open the blower cabinet.

This photo shows a blue fiber type filter located inside the blower compartment of the air handler.

The photo at the top of this page shows another conventional air filter located inside of a vertical air handler blower compartment - in that case the filter was very dirty and blocked with debris.

Watch out: SAFETY WARNING - injury risk: when opening a blower cabinet, older units may lack a safety interlock switch that turns off power to the blower fan. Reaching inside of a blower cabinet when the fan is running is very dangerous as you can lose fingers in the spinning air conditioner blower assembly fan or its drive motor or belt.

To be safe, turn off power to the unit before opening the blower compartment to inspect for and change a filter.

Opening the blower compartment door on these systems will expose one or several filters which are simply set in place on a frame. Normally the filters are placed inside of this box in a location which will filter air before it reaches the blower fan itself.

Watch out: SAFETY WARNING - filter direction: be sure to place the new air filter properly into its slot (at the air handler) or grille (for ceiling or wall mounted central air return filters). The edge of most air filters has an arrow showing the intended direction of airflow through the filter.

The filter is installed so that the arrow (and air flow) show air moving through the filter INTO the duct system (at a central air return grille) or INTO the air handler (for filters installed on the blower unit).

This is important because many filters are reinforced to prevent the airflow from collapsing the filter material and drawing it right into the blower fan itself. A collapsed filter that is drawn into a blower fan can cause fan overheating and even a building fire.

MAINTENANCE TIP: when inspecting the blower compartment interior of a central air conditioning or central heating air system look at the blower fan itself. Usually these are a round squirrel cage fan driven either directly by an electric motor or driven by a fan belt which is in turn connected to a pulley on a nearby electric motor.

Use a good light to examine the blades of the blower fan itself.

If the air conditioner or heating blower fan blades are clogged with dirt (or MOLD (as in this photo)) you should have the air handler unit thoroughly cleaned by a professional, including the fan blades themselves.

We've seen a 100% improvement in air conditioning or heating airflow when a very dirty blower fan was cleaned. Of course a very dirty air filter will also slow air movement and increase operating cost in an air conditioning or heating system.

Change the air conditioning or heating system air filters every month when the air conditioning system is in operation.

Make sure you find all of the filters as some systems have multiple filters and even multiple types of filters installed, such as a fiberglass or pleated paper filter, a washable filter, and an electrostatic air cleaner. These last two are cleaned, not replaced, when they're dirty.

After you have located the air filter(s) document the placement of the HVAC system air filters for future building owners, occupants, or repairmen. Knowing where the air filters are located, and that you've found all of them, eases air filter inspection and regular changing during the cooling or heating season.

Each month during the heating or cooling season, inspect the air conditioning filter type and condition.

What about air filters that are missing completely or are very dirty?

What about other air filtration methods like electrostatic air cleaners, HEPA or high efficiency air filters, or UV light disinfection systems?

What problems can a dirty or blocked air conditioner filter cause for the air conditioning system and how do we fix these snafus?

That's what we'll cover in other sections of this article - see links below.

...


Continue reading at AIR FILTER OPTIMUM INDOOR or select a topic from closely-related articles below, or see our complete INDEX to RELATED ARTICLES below.

Or see AIR FILTER LOCATION FAQs - questions & answers posted originally at this article

Or see AIR FLOW IMPROVEMENT, HVAC

Or see these

Air Filter Articles

Suggested citation for this web page

AIR FILTER LOCATION at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

INDEX to RELATED ARTICLES: ARTICLE INDEX to BUILDING INDOOR AIR QUALITY IAQ

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Or see

INDEX to RELATED ARTICLES: ARTICLE INDEX to AIR CLEANERS FILTERS PURIFIERS

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia


...

Frequently Asked Questions (FAQs)

Click to Show or Hide FAQs

Ask a Question or Search InspectApedia

Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.

Search the InspectApedia website

HTML Comment Box is loading comments...

Technical Reviewers & References

Click to Show or Hide Citations & References

Publisher InspectApedia.com - Daniel Friedman