InspectAPedia®

Photograph of an air conditioning system suction line temperature chart Air Conditioning & Heat Pump Temperature FAQs

  • POST a QUESTION or READ FAQs about air conditioning or heat pump system temperatures, temperature measurement, diagnosis & repair of temperatures that are too warm, hot, or too cold

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.


Air conditioner or heat pump operating temperature diagnostic questions & answers: HVAC system temperature FAQs:

Questions & answers about air conditioner or heat pump system temperatures at the equipment, at the cooling or heating coil, at the supply or return registers, & how those temperatures help diagnose HVAC system problems.

This article series explains the normal or abnormal operating temperatures of air conditioning equipment and what temperatures can be expected when measured at different locations.

We also provide a MASTER INDEX to this topic, or you can try the page top or bottom SEARCH BOX as a quick way to find information you need.

Air Conditioning / Heat Pump Temperatures Diagnostic Questions & Answers

Photograph of a dial thermometer reading a high output temperature at an air conditioning compressorAir conditioner temperatures that are too high or too low can indicate specific operating problems on central and portable or window air conditioners. These questions & answers about air conditioner or heat pump operating temperatures were posted originally at AIR CONDITIONER TEMPERATURES - the topic home - you will enjoy reading that material.

Question: air conditioner temperature difference across the cooling coil - what's normal?

15 July 2015 Luke Ducote said:

I've been having problems with a Freon leak for a couple of years now on an R22 system. A charge usually lasts several months, however the last charge only went a month before I was having problems again.

Upon placing my gauges on the unit, I noticed the pressures were normal (75/210).

Although the condenser coils did not appear real dirty I cleaned them anyway. Both pressures dropped considerably so I added Freon. Then unit began running better/colder but is still having problems keeping up.

I added a little more Freon (up to 85 psi) on the low side, however the high side is not getting any higher. Did I put too much Freon? Could there be air in the system? I'm wondering if the compressor has been damaged but would rather not replace it as a means of troubleshooting. Any suggestions?

This question was posted originally at DIAGNOSTIC GUIDES A/C / HEAT PUMP

Reply:

Indeed, Luke, if an A/C system has lost enough refrigerant that it is no longer cooling air then adding refrigerant to the system may get it "working" again.

But the temperature difference you cite, if measured across the coil or close to that would be fine.

See AIR CONDITIONER TEMPERATURE MEASUREMENT to make sure you're measuring the A/C temperature drop correctly.

See HVAC TEMPERATURE INSTRUMENTS if you need a better A/C temperature measurement device.

Refrigerant is not a consumable item. If there is a leak the best procedure is to find and fix the leak rather than to keep adding refrigerant.

Question: ice on the coils of a window air conditioner

Hi, the window airconditioner i'm working on shows ice formation on the evaporator coils. It started to around 2 to 3 coils then it gradually increases until almost the entire coils are covered with ice.

I won't go with the idea that the thermostat should be set in a way to avoid the compressor running continously because before the trouble begun the unit has been running almost continously for 8hours for the last several years and there was no occurance of ice/frost build-up. We check the unit current and its ok, so we believe the charge is also ok.

We check other possible causes, like distorted coils fins, dirt, obstructions and blower speed and they seem to be all ok. What do you think should i do more? - Arnie 11/10/11

Reply:

Arnie no way can I be smarter than a trained service tech, but

Question - how did younfigure the charge is ok vs refrigerant is low?

Question 2- could you have a partly crimped or blocked cap tube ? that can result in low side pressure being abnormally low, uneven refrigerant metering; a blob of oil or dirt traveling in the system easily blocks a cap tube.

Is there a drier that could be clogged or has the unit never been opened ?

Is the blower fan itself dirty? This one can foolmyou. Dirt on squirrel cage blower fan blades fills in their curve and really cuts airflow

Keep me posted

Dan

Question: can my liquid refrigerant line freeze?

can my liquid line freez with frost if so why - Kevin Ohio 2/19/12

Reply:

Kevin Ohio, no the liquid refrigerant line does not freeze, but it can be come frost or even ice coated if it is missing insulation, or in some cases if the refrigerant charge is improper, or if a refrigerant metering device is not working properly. In cooling mode on a heat pump or in an air conditioning system you will see frost formation on the suction line - the larger diameter refrigerant pipe.

Question: how long should an air conditioner compressor run before it cycles off?

Hi. How long should my ac compressor keep on running before it automatically turns off. - Mon 5/31/12

Reply: it depends...

Mon: about typical air conditioning compressor run time, I don't think there is a single right answer to your question, because the on-cycle time depends on several variables that could in some cases leave the unit on for a long time, even continuously. Those variables that set the run time for the compressor include

- the indoor temperature, that is in turn affected by outdoor temperature and sunlight as well as building heat gain, windows, insulation, air leakage, and similar factors

- the thermostat set point - if the thermostat is set to a cooling number below what the system can achieve it will run continuously

- the size or capacity of the cooling system versus the actual building cooling load

However there is another way to approach your question that may be more useful diagnostically. That is to ask if something has changed in how your A/C system seems to operate.

So if you think that the building and its insulation, windows, heat gain conditions have not changed, and if your thermostat setting is the same temperature as in previous cooling seasons, and if the outdoor temperature and sun and wind conditions are similar to previous seasons, and THEN if your cooling system seems to run longer or continuously when it did not previously, there may be a problem to diagnose and repair.

Check the LOST COOLING CAPACITY article (links at the ARTICLE INDEX the bottom of this article ) for more detailed diagnostic suggestions.

Question: is the outside compressor unit controlled by indoor temperature?

Is the outside compressor controlled by the temperature outdoors? At a outdoor temp. of 72F and the indoor temp around the same and I turn the thermostate to 70F the compressor will not run only the fan. When the outdoor temp is 82F or higher the compressor runs normally. - Compressor situation 6/11/12

Reply:

The outside compressor on a residential cooling system basically runs under control of the thermostat that is calling for cooling. But the efficiency of the system is affected by outdoor air temperature. In hotter outdoor air the compressor/condenser has to work harder, and perhaps longer to condense the refirgerant back to a liquid.

Question: typical R22 refrigerant pressures

The pressures on our home AC system (R22) seem fine when operating: suction line 73psi, liquid line 233 psi. When the system is off, the pressure equalizes to 115psi. On the manifold I used, the suction gauge indicates anything over 110 psi as in the "danger" zone. In short, would 115psi on the suction line only be a problem when the system is operating but not when it's off? Thanks! - Pete 6/27/12

Reply:

Pete, Yes I think you're quite right. When most A/C systems are off for some time, especially older residential designs, pressure equalizes throughout the system and will ultimately be the standard pressure for that refrigerant gas at the ambient temperature, with a little adjustment for altitude above sea level.

Refrigeration gas pressure/temperature charts (from various manufacturers) summarize these properties. For example R22, at 65 degF will stabilize at about 111 psi if memory serves.

Question: My A/C quit blowing cold air - the repairman said "give it a few days"

My ac quit blowing cold. My ac repair man checked for leaks (found none). He cleaned both outside and inside coils. Still not cooling good so he put a very small amount of coolant in it. My air blowing out of my vents is aaround 80 degrees.

My ac repairmand knew the temp was not cool,he said to give it a few days and let him know. I called him and told him it is still not working. He said he has all the info and would tell me about it. Now he does not return my calls and we are burning up. What can I do to correct my ac problem? - Bill 7/5/12

Reply:

Bill it sounds from your note as if your repair tech is either overloaded with work ( after it's all during very hotvweather) or is stumped .it's time to call someone else who will respond to you.

Question: evaporater temperature

Can you help me pelase ? I have a problem. How to calculate evaporator tempature - Erhan

Reply:

Sorry that's too broad a question to even understand where to begin. Check your textbook for tables relating temperature, pressure, and the specific type of refrigerant gas.

Question: is a hot bathroom wall next to HVAC equipment dangerous?

I have a older unit, central air unit inside the condo. The wall of the unit is against my bathroom shower wall. It gets so hot in there, I can't keep it cool in the bathroom.

I rent and I don't know what kind it is. But I have to so something as it is a one bedroom and my cooling bill is outrageous. Help please? - Donna Van Wie 7/09/12

Reply:

Thanks for the question, Donna, but I'm sorry - I don't really understand the situation that you describe. The indoor air handler unit, if it's a cooling unit only, should not be running so hot - it sounds as if you need a service call from an experienced technician. Keep us posted on what you find - it will surely help other readers.

Question: how accurate is the operating temperature range of an air conditioner?

how accurate is the operating temp range, and if the outside air is hotter than said range, is the machine potentially going to over work itself and have issues?? - JD

Reply:

Nate I do not know a factual answer to your operating temperature range question, it would need to be answered by the specific manufacturer of the A/C system. My OPINION is that the range is the temperature range at which the equipment can adequately cool the space for which it was designed.

At higher outdoor temperatures the system may not be able to produce the same cooling capacity. I would not expect it to be ruined by that fact alone. In fact it is common to see cooling equipment run for very long periods during very hot weather.

Question: should I set the fan to constant ON on very hot days?

should the furnace fan be set to stay on constantly during very hot days, to keep cool air flowing?? JD - 7/09/11

Reply:

JD:
the answer is an OPINION as I don't think there is a single right answer: Often I like running the A/C fan continuously to improve air/dust filtration and give more even indoor temperatures;

Question: does a drop in the temperature of cool air in my system mean the compressor is damaged?

I recently replaced a fan relay. Before the fan relay went bad, the register cooling temp was at 62f. The fan relay was bad for a few days and the outside compressor was running for some number of hours throughout the day until we realized the inside wasn't running.

Now, after the fan relay has been replaced the register cool temp has sometimes hit 56.1f. What's up with that? Could it indicate a damaged compressor? Thanks, Chris K

Reply:

Chris, thanks for the interesting question. But I don't think I can give a straight answer evaluating an 8 degF drop in cool air output temperature after getting a fan relay replaced. That's because building and environmental conditions vary so widely that the temperature of the return air entering the cooling system also varies widely from time to time.

A cooling system generally produces a rather constant temperature drop across the cooling coil, so long as the air flow rate stays unchanged. Something that slows the air rate may cause a greater temperature drop - not always desirable, and vice versa.

So if the weather or your home were hotter when you made the first measurement than when you made the second, that condition alone could explain the change that you saw.

Question: air conditioner compressor unit fan relay problems?

I recently replaced a fan relay. Before the fan relay went bad, the register cooling temp was at 62f. The fan relay was bad for a few days and the outside compressor was running for some number of hours throughout the day until we realized the inside wasn't running.

Now, after the fan relay has been replaced the register cool temp has sometimes hit 56.1f. What's up with that? Could it indicate a damaged compressor? Thanks, Chris - CK 7/14/12

Reply:

CK thanks for the interesting question. But I don't think I can give a straight answer evaluating an 8 degF drop in cool air output temperature after getting a fan relay replaced. That's because building and environmental conditions vary so widely that the temperature of the return air entering the cooling system also varies widely from time to time.

A cooling system generally produces a rather constant temperature drop across the cooling coil, so long as the air flow rate stays unchanged. Something that slows the air rate may cause a greater temperature drop - not always desirable, and vice versa.

So if the weather or your home were hotter when you made the first measurement than when you made the second, that condition alone could explain the change that you saw.

Question: Lennox HVAC control board replaced with White Rodgers Unit?

hello.. wondering i have a 7 to 8 year old lennox hvac. i replaced the control board and they gave me a whiterodgers Single Stage HSI Integrated Furnace Control Kit ... now this happin in winter time .. before this i had around 58F output on AC.. now iam upto 66F output ..

on the AC uint inside home .. the small line is cold . not over cold not froze .. the larger line is middle of road also to the warmer side .. if i had to say example 25 degress diff in the lines by touch .. small again cold .. the little line goin to the tve i thiink its called does drip .
so ? is ... single stage ? my AC not goin to high stage ? stayin on the low stage? or there is no stage ?

airflow seems good i can feel it around 3 foot off floor .. White Rodgers 50M56U-843 Universal Single Stage HSI Integrated Furnace < is what i replaced old board with .. ty - Phil 7/26/12

Reply:

I'm sorry Phil but I'm just baffled by your question. Let's start with asking if there seems to be a problem with how your cooling system is working: is it not cooling? Given that you are finding the system confusing, I can't recommend messing with the controls, wiring, refrigerant and instead I think it's well worth paying a trained HVAC tech to take a look.

no it doesnt seem to cool good enough .. if its say 80 outside. house will cool upstairs to say 75 .. tho the air temp from the registers is 65. and last summer it was 55.. the system never shuts off as it never seems to reach temp . so i was wondering if some home systems have a 2stage compresser high and low . per say ?

Question: question about supply air temperature from the air conditioner

the temp of the air comming out in rooms is 65F even on a 70F day .. i was wondering if the compresser has 2 stages a high and low .. as last summer i had 55F comming out of the AC.. since i put the new board in i seem to have lost 10F somewhere..

the new board says single stage . to me in say car world a single stage is 1 ... so no idea if there is a dual or 2 stage cooling on compressers for home AC units . - Anon 7/27/12

Reply:

Most residential A/C systems do not use temperature staging.

Question: stolen A/C compressor unit, now problems converting to an R410 refrigerant system

My house had its condensor stolen while we were in escrow. Purchased a 410 system. My buddy replaced it and we left the existing furnace. Changed out blower and coil. Evacuated all freon with nee refrigirant. It was cooling fine then one day it could not keep up.

My friend can't find the reason why. He checked temp at register. It was in the mid 40s then jumps up to the 60s. Can this be a faulty t x v ? Even though it was new maybe a deffective piece? - J Flores 8/11/12

Reply:

J

You made a good guess. Check to see that the thermostat is oontinuing to call foes cooling (set it well below the room temp) and that the compressor is continuing to run. In that case if the air temp surges between cool and not cool I too suspect the refrigerant metering device - presuming it's not a heat pump system.

Also check for icing at the TEV and that the TEV is rated to handle the r410

Reader follow-up:

Spoke to my friend and he is convinced that the condensor is to far from the furnace and this why its not blowing cold air. Furnace is in garage in front of house. The condensor is in rear of house. Lines coming from condensor go up aprox 20 ft. Into attic. 2 story house then goes all the way across aprox 40-45 ft.

Then down to furnace. He says any line being over 50 ft is going to struggle. Hes planning on moving the condensor to the side of house. Bringing it closer to the furnace. Aprox 25-30 ft of line. He thinks this will cool properly.

Reply:

J
That distance determines the length of refrigerant piping and thus the amount of charge needed. If the charge s low that could be the issue. On moving the system the whole thing will be emptied and recharged anew, which might then look as if it were the move rather than the charge that fixed matters. Keep me posted.

Reader follow-up:

Dan we are back to step 1. My friend moved the confenser back to its original place. His gauge read blue gauge 42 degrees. Red gauge 370 degrees. Text book temps he said. Temp at coil 48.8 degrees. Air from vent. 68-70 F. So from the coil to the register a distance of about 3 ft the air heats up 18-19 degrees!

Why? We even climbed in attic no leaks. Punctured one duct with thermometer. 68.5 f nxt week hes going to temove coil to see if anything is disconnected. Hes determined to find out why.

Still took it over 6 hrs to drop it from 87 to 81. We concluded that it was not a tpv valve. This system does not have one. It has a coolant regulator which he placed. It allowed the temp of coolant to drop to 42. The most it had come down to was 52.

Question: can my cooling compressor stay outdoors with no damage in cold weather?

i need to cool a very warm room all year round. Can my compressor stay outside and opperate in cold winter temps without harm? - Michigan 8/14/12

Reply:

Outdoor compressor/condenser units are designed for outdoor weather exposure; but that's not to say that your particular unit is designed for outdoor use in cold weather.

Watch out: do not turn on an un-known air conditioner or heat pump system in cold weather if you don't know about the temperature rating of your outdoor A/C system (or heat pump system) and if you have not checked with your HVAC service technician.

For example, if a system has no crankcase heater installed, or even if it has one installed but the system has been left turned off, trying to run the compressor without sufficient time for the crankcase heater to work can damage or even destroy the compressor motor.

Question: question about air temperature differences between intake and supply

temperature difference between intake and suppy was 13 degrees it should be 15 - 20 degrees,how do i fix - Brian 8/23/12

Reply:

Not sure you have a problem; Nor did you make clear exactly where you took your measurements.

Some things to check are refrigerant level, insulation in the system, dirty coil. See DIAGNOSTIC GUIDES A/C / HEAT PUMP - A/C or Heat Pumps for details.

Question: Trane A/C system repair questions - air handler speed is too high?

I recently had my traine system repair under warranty work. At the time the repair technician said my air handler speed was two high, and set it on low. recently I came home and the air was not cooling, so I called repair company who sent another technician, but before he got there I replaced air filter and reset unit. It seem to do the trick but air flow from vents seemed low.

When he arrived he said everything check out, But he said the fan was set to low. So know I don't know what to think as two technicians from same company had opposite recommendations. I live in Texas were is extremely hot in the summer - CB 9/12/12

Reply:

Sounds as if there was confusion about fan speed and a dirty air filter. A clogged air filter reduces air flow through the system.

Question: air blowing sounds when our A/C system is shut off

We have a dual air conditioning unit and when we shut both levels to the off position it still sounds like air is blowing. We are worried this might raise our electric bill if it is continuously running even when shut to off on both levels. Any suggestions? ? - Rob 10/13/12

Reply:

Turn off electrical power to the system at its circuit breaker and check again. If the blower stops then but does not stop when you are using the system operating controls and switches, either a switch is bad or you are confused about the controls.

Question: thermostat improvements on my A/C unit

I had a a guy come and install and new government supplied smart thermostat and the AC was not working so he could not do the install as per his rules. The outside temp is apporx 15 degrees, would this have anything to do with it? - Stumped 10/19/12

Reply:

If the new thermostat was not properly connected your A/C system might indeed stop working.

But at an outside temperature of 15 degrees F, no one would expect the air conditioner to be operated - doing so risks damage.

Question: my window A/C unit fan speed is too high - how can I adjust it ?

HI there, The lowest fan setting on my window A/C is way to high. It blows like a hurricane. Is there any way to adjust the settings to make "low" really "low"? I appreciate any help or suggestions you can offer! Thanks much, Carrie - 11/17/12

Reply:

Carrie,
I'm doubtful that you can at reasonable cost change out the fan speed control on your window A/C unit as long as the original one is operating to factory spec.

But you can try adjusting the air-directing louvers to not blow the hurricane where it's not wanted, or even to leave them partly closed to slow down the air flow.

Question: how cold can it be outside and still get heat from my heat pump system?

How cold can the outside temp. go down to and still let the inside unit warm the inside room to a comfortable temp. on a split system - Jon Joynson 12/14/12

Reply:

John,

The lowest operating temperature of a heat pump varies by brand and model. System efficiency begins to drop when temperatures drop below the low 40's, and eventually it's cold enough that backup heat or alternative heat sources are required. Tyically a modern high efficiency heat pump can extract some heat from cold outdoor air down to the high 30's. And there are some recent models of heat pumps designed to extract heat from air down into the 30's F and even to as low as 15F. (But we'd want to see the efficiency operating curve and operating cost data too.)

Question: What air temperatures should we see out of Trane 2 & 3 ton cooling units?

(June 8, 2014) Carl said:
My friend is trying to buy a townhouse and had a recent home inspection. The inspector noted that there are two Trane units, one 3-ton and one 2-ton. He did not note the model numbers but did note they were manufactured in 2004 and said R-22.
On the 3-ton unit the supply air temp was 60 degrees and the return was 72 and he said this is out of range and is a problem, but did not indicate if this just means the unit is low on freon, has a leak, coils and filters need cleaning, or the unit is at the end of its expected life and should be replaced.
On the 2-ton unit the supply air temp was 61 and return was 77, again he noted this was out of range.
Can anyone shed some light on what these numbers mean, what they should be on a properly working system, and does it sounds like these units need to be replaced or just serviced?
Thanks,
Carl

Reply:

(June 8, 2014) Minh said:
To Carl, the 2 ton unit is within the range 77-61=16 degree different.

(June 16, 2014) Anonymous said:
To Carl: On an R-22 system you should get at least a 67psi reading on the low side (suction line). Once I get this reading I go inside and check the return air temp and then the temp coming off the a-coil. I keep adding refrigerant till I get a 20 degree difference. I typically get the units I work on down to 59 degrees coming out of the air vent

s. The 16 degrees mentioned is what I consider bare minimum. Yes, it appears there is a leak somewhere. Check all brazed joints and look for, or feel for oil on the surface. Add some refrigerant and you are good to go. Also, most AC units last 10-14 years, although I worked on an oldie that was over 30 years old. It finally failed. Good luck. Floyd/HVAC Tech

Question: central air runs continuously, house is cooled fine but the fan won't stop

(July 6, 2014) Anonymous said:
my johnstone central air systems runs continuously. it cools the house down fine but it won't cycle. what's up?

Reply:

Anon,

Some diagnostics for an air conditioner that won't stop running are over at

inspectapedia.com/heat/Furnace_Fan_Wont_Stop.php

Your system may simply be unable to keep up with the heat gain of your building, or there may be another problem worth diagnosing. Check the temperature drop across the cooling coil and check the air flow CFM.

Question: problem on R-22 home a/c unit with electric heat furnace attached to air handling system

(Feb 19, 2015) Anonymous said:
Trying to diagnose problem on R-22 home a/c unit with electric heat furnace attached to air handling system. Compressor unit is Goodman and is 8 years old. Evaporator and air handling system is about 15 years old - probably Rheem system.

Problem: Rubber insulation on suction line from evaporator to about 15 to 18 inches down the line (towards compressor)has melted from heat. It appears the suction line where it connects to evaporator is getting very hot. I'm familiar with this line frosting or freezing at this point, but have never seen one get hot and melt insulation.

System is cooling, but I don't know how efficient. Any input as to problem would be appreciated, but in the simples terms the better. Earl

Reply:

Anon

The suction line is normally cold - which is why it's insulated; if your unit's suction line got hot enough to melt the insulation I worry that there is a failing component, possibly compressor unit; yet you say the unit's cooling. So other things to check:

- has someone done work on the refrigerant piping involving brazing - heating the line during a repair might melt insulation that should have first been removed

- is there evidence (burned wires, odors) of an electrical problem? if so the unit is probably unsafe and should be shut down

Question: My Central Air heat pump with digital thermostat, blows cold air but the temp gage reads hotter than the temp really is.

(May 4, 2015) Rod said:
My Central Air heat pump with digital thermostat, blows cold air but the temp gage reads hotter than the temp really is. I will set the temp on the thermostat at 80 the temp reads 82 but the house is cold. I manually turn off the air and ten minutes later the temp reads 78 deg. While the A/C is running the thermostat reads hotter? I replaced the batteries in the thermostat twice, I blow out with can air to clean dust, no change.

Reply:

I'd check the thermostat position - it may be in a location that does not properly sense room temperature, such as in direct sunlight.

Question:

(June 10, 2015) Ray Myers said:
The air output temperature of the air conditioning is absolutely frigid. Can that be adjusted to a more moderate temperature?

Reply:

First I'd check that the return air is adequate and that the blower fan is moving air properly.

Question: RTU heat pump outdoor condenser turns cold when in cooling mode

(June 10, 2015) kenneth fletcher said:
RTU heat pump outdoor condenser turns cold when in cooling mode ... condenser fan blows out cold air... unit has a reversing valve...what might be the problem ... thanks

Reply:

Sounds like a thermostat or control board or wiring problem putting you in heating mode when you want to be in cooling mode. Also see REVERSING VALVE on HEAT PUMPS

Question:

30 June 2015 Rich said:
outside temp 93F inside temp 78F, vent temp 43F
Thermostat set on 74F, will not cool down anymore.
why

Reply:

If your system has good air flow but temperatures are too warm I suspect lost refrigerant or a bad control.

See LOST COOLING CAPACITY

Question: weak air flow, HVAC tech says replace the TXV (TEV - thermostatic expansion valve)

28 June 2015 Sandy said:
Two of my air ducts are not blowing air. Can this affect the air temperature differential?

Reply:

I'm not sure what temperature differential you ask about but certainly if two ducts have lost air flow that would mean that the areas served by those ducts won't be cooled.

Look for disconnected, crimped, or closed dampers in those duct systems.

Reader follow-up:

Sandy said:
Does the blocked air ducts affect the reading of the return register and the supply register. Our differential reads at 12 which does not meet state standards for a home inspection. They say a minimum of 14. We had an AC guy come over and says we need a TXZ valve replacement. The unit is only 6 yrs. old. The job will be $1070.00 just wondering if the two blocked ducts are the problem and not the TXZ.

Reply:

Sandy

If by TXZ valve you are referring to a thermostatic expansion valve (usually written TEV), that is a refrigerant metering device. The relationship between a TXV or TEV valve problem and low air flow would be indirect: a faulty thermostatic expansion valve MIGHT cause icing of the cooling coil in the indoor air handler unit. In turn, an ice-blocked cooling coil would reduce air flow through the system. But that problem is easily and quickly discoverable by mere inspection of the cooling coil for icing after the system has been on for a time.

In the ARTICLE INDEX to AIR CONDITIONING & HEAT PUMPS given above you'll find more diagnostic articles on blocked HVAC duct air flow, weak air flow, inadequate return.

Or skip directly to AIR FLOW TOO WEAK at InspectApedia.com

Note that if only some of your ducts have poor air flow then it's not a TEV problem since an iced coil would reduce the air flow into ALL of the supply ducts.

I would not pay a thousand dollars for a TEV replacement before knowing that the problem has been correctly diagnosed.

If your air conditioning or heat pump system has lost its cooling capacity or won't start see REPAIR GUIDE for AIR CONDITIONERS.

See RATED COOLING CAPACITYof air conditioning equipment if the system seems to be working but is inadequate to cool your building.

...


Continue reading at AIR CONDITIONER TEMPERATURES - normal, abnormal, rules of thumb, simple diagnostics - topic home, or select a topic from closely-related articles below, or see our complete INDEX to RELATED ARTICLES below.

Or see AIR CONDITIONER TEMPERATURE FAQs-2 - more questions & answers about HVACR temperatures & temperature measurement

Or see AIR CONDITIONER TEMPERATURE MEASUREMENT

Or see HVAC TEMPERATURE INSTRUMENTS

Suggested citation for this web page

AIR CONDITIONER TEMPERATURE FAQs at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

INDEX to RELATED ARTICLES: ARTICLE INDEX to AIR CONDITIONING & HEAT PUMPS

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia


...

Ask a Question or Search InspectApedia

Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.

Search the InspectApedia website

HTML Comment Box is loading comments...

Technical Reviewers & References

Click to Show or Hide Citations & References

Publisher's Google+ Page by Daniel Friedman