Metal stud framed building under construction Freedom Plains NY (C) Daniel Friedman Thermal Conductivity of Metal Studs - Metal Stud Wall R-Values
Energy efficiency of steel studs

  • FRAMING METAL STUD PERFORMANCE - CONTENTS: What are the thermal conduction values for metal stud walls?What are the R-values of metal stud insulated walls. Heat flow through walls built using metal studs. Metal stud thermal short-circuiting studies and heat loss data. How to save on building energy costs: heating, cooling, electricity usage & cost reductions where metal stud framing is used. Test data giving effective R-values for nominal 2x4 and 2x6 metal stud walls.
  • POST a QUESTION or READ FAQs about the effects of metal stud framing on building heating or cooling costs & energy efficiency
  • Solar Age Magazine Articles on Renewable Energy, Energy Savings, Construction Practices
  • REFERENCES
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

Metal framing studs & building energy efficiency:

This article discusses the thermal properties and heat loss characteristics of metal stud framed walls, including metal stud wall R-values. We include test data giving effective R-values for nominal 2x4 and 2x6 metal stud walls.



Green links show where you are. © Copyright 2017 InspectApedia.com, All Rights Reserved.

Metal Stud Thermal Performance & Thermal Conduction Data

Metal studs at a New York City High Line Jobsite (C) Daniel Friedman

The question-and-answer article below paraphrases, quotes-from, updates, and comments an original article from Solar Age Magazine and written by Steven Bliss.Our page top photo shows a metal stud-wall framed building (Dunkin Donuts) being constructed in Freedom Plains, NY. In the steel stud photo just above metal studs remain banded and on pallets waiting for use at a New York City High Line jobsite.

Thermal Properties of Metal Stud-Framed Walls

Question:

Commercial buildings are often required by code to be constructed using metal studs. I have been unable to find accurate thermal conduction values for metal studs in exterior building walls.

Do you know of any test data giving effective R-values for nominal 2x4 and 2x6 metal stud walls framed on 16- and 24-inch centers with fiberglass batts in the wall cavities? - Thomas Anderson, IKM SGE, Inc., Architects, Engineers, and Interior Designers, Pittsburgh, PA.

Answer: Two Studies Report on Thermal Properties and Heat Loss Characteristics of Metal Stud Walls

Metal stud framed building under construction Freedom Plains NY (C) Daniel Friedman

We found what we think are the only two papers on thermal properties of metal stud framed walls. They draw different conclusions.

In the first, written in 1972, J.R. Sasaki of the International Research Council of Canada concluded that metal stud wall R-values were 9 to 13 percent less than the R-value as calculated by the ASHRAE Zone Method. The ASHRAE Zone Method uses a weighted average of the U-Values (see INSULATION R-VALUES & PROPERTIES and see HEAT LOSS R U & K VALUE CALCULATION) of individual elements to calculate the thermal resistance of a multi-component system such as a stud wall.

Sasaki attributed the differences to convective heat transfer in the stud space or convective air exchange through the insulation. The walls in his test, however, were unlike more recent insulated building walls: they had only 2 inches of fiberglass insulation in a 3 1/2" stud cavity.

[That design leaves an open air space that invites in-wall-cavity convection currents. The very large heat losses that can occur with in-wall convection currents is discussed at ENERGY SAVINGS RETROFIT CASE STUDY and "solved" at ENERGY SAVINGS RETROFIT LEAK SEALING GUIDE - Ed.]

The second study of metal framed stud wall thermal properties was completed in the 1980's and used modern materials. Donald Larson and Bakhtier Farouk at Drexel University in Philadelphia measured heat flow through a wall built of foil-faced R-11 fiberglass, 1/2-inch drywall, and 0.02-inch-thick steel studs spaced at 16-inches on center.

Using a portable 4-foot-square test plate, they found the wall R-value to be 43-percent lower than that determined by a simple one-dimensional calculation.

The discrepancy, they speculate, was due to increased lateral heat flow through the flanges of the metal stud.

Thermal short-circuit ng was made worse by the foil facing on the insulation.

Larson and Farouk concluded with a note of caution, saying that the test method needed further assessment.

Standard design booklets for metal-stud buildings list R-values for the insulation only - they ignore the metal studs altogether. -- S Bliss.

The question-and-answer article about the thermal properties of metal stud-framed walls, quotes-from, updates, and comments an original article from Solar Age Magazine and written by Steven Bliss.

The link to the original Q&A article in PDF form immediately below is preceded by an expanded/updated online version of this article.

Metal stud framing in New York - Poughkeepsie (C) Daniel Friedman Dunkin Donuts steel stud framed EIFS building at Freedom Plains, Dutchess County NY (C) Daniel Friedman

The steel stud-framed building underway at above left is shown after completion at above right. This EIFS-Steel-Stud-framed building is located in Freedom Plains (Dutchess County) NY.

Metal_Stud_Energy_Efficiency.php

...


Continue reading at or select a topic from closely-related articles below, or see our complete INDEX to RELATED ARTICLES below.

Or see ENERGY SAVINGS in BUILDINGS - home

Or see FRAMING DAMAGE, INSPECTION, REPAIR - home

Or see FRAMING MATERIALS, Age, Types

Suggested citation for this web page

FRAMING METAL STUD PERFORMANCE at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

INDEX to RELATED ARTICLES: ARTICLE INDEX to BUILDING ENERGY SAVINGS

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia


...

Frequently Asked Questions (FAQs)

Click to Show or Hide FAQs

Ask a Question or Search InspectApedia

Use the "Click to Show or Hide FAQs" link just above to see recently-posted questions, comments, replies, try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.

Search the InspectApedia website

Comment Box is loading comments...

Technical Reviewers & References

Click to Show or Hide Citations & References

Publisher's Google+ Page by Daniel Friedman