InspectAPedia.com InspectAPedia®
Google
InspectAPedia
 

Free Encyclopedia of Building & Environmental Inspection, Testing, Diagnosis, Repair

Ask a Question or Search InspectAPedia

  • HOME
  • AIR CONDITIONING
  • ELECTRICAL
  • EXTERIORS
  • HEATING
  • HOME INSPECTION
  • INTERIORS
  • PLUMBING
  • ROOFING
  • SEPTIC SYSTEMS
  • STRUCTURE
  • WATER SUPPLY
  • ENERGY SAVINGS
  • ENVIRONMENT
  • INDOOR AIR IAQ
  • INSULATION
  • MOLD INSPECT TEST REMOVE
  • NOISE
  • ODORS
  • SOLAR ENERGY
  • VENTILATION
  • EXPERTS DIRECTORY
  • CONTACT US



Mobile Phone or PDA view of this websiteMobile View
HEATING SYSTEMS

AGE of AIR CONDITIONERS & HEAT PUMPS
AGE of HEATERS, BOILERS, FURNACES
AIR CONDITIONING & HEAT PUMP SYSTEMS
AIR FILTERS for HVAC SYSTEMS
  AIR FILTERS, OPTIMUM INDOOR
  CONTINUOUS BLOWER FAN OPERATION
  AIR FILTER EFFECTIVENESS
  FIBERGLASS & AIR FILTERS
  SOURCES FOR AIR FILTERS

AIR HANDLER / BLOWER UNITS
AIRBOUND HEAT SYSTEM REPAIRS
ANODES & DIP TUBES on WATER HEATERS
ANTI SCALD VALVES
ANIMAL ALLERGENS / PET DANDER
ANIMAL ENTRY POINTS in buildings
ANIMAL ODORS IN buildings
APPLIANCE EFFICIENCY RATINGS
ASBESTOS IDENTIFICATION IN buildings

BACKDRAFTING HEATING EQUIPMENT
BACKFLOW PREVENTER VALVE, HEATING SYS
BACKFLOW PREVENTER, HEATER WATER FEEDER
BACKUP HEAT for HEAT PUMPS
BANGING HEATING PIPES RADIATORS
BAROMETRIC DAMPERS
BIOGAS PRODUCTION & USE
BLEVE EXPLOSIONS
BLOWER DOORS & AIR INFILTRATION
BLOWER FAN CONTINUOUS OPERATION
BLOWER FAN OPERATION & TESTING
BLUE vs YELLOW COMBUSTION FLAMES
BLUERAY Recall

BOILERS, HEATING
  BACKDRAFTING HEATING EQUIPMENT
  BACKFLOW PREVENTER VALVE, HEATING SYS
  BANGING HEATING PIPES RADIATORS
  BOILER COMPONENTS & PARTS
  BOILER CONTROLS & SWITCHES
  BOILER LEAKS CORROSION STAINS
  BOILER LEAKS, HOW TO LOCATE
  BOILER OPERATING PROBLEMS
  BACKDRAFTING HEATING EQUIPMENT
  BACKFLOW PREVENTER VALVE, HEATING SYS
  BANGING HEATING PIPES RADIATORS
  BOILER COMPONENTS & PARTS
  Air Bleeder Valves
  Air Scoops Purgers Separators
  AQUASTAT CONTROL Functions
  BACKDRAFTING HEATING EQUIPMENT
  BACKFLOW PREVENTER VALVE, HEATING SYS
  BANGING HEATING PIPES RADIATORS
  Cad Cell Relay Switch Flame Sensors
  CHECK VALVES, HEATING SYSTEM
  Chemical treatments, Boiler
  Circulator Pumps & Relays
  Draft Regulators, Barometric Dampers
  ELECTRIC MOTOR OVERLOAD RESET SWITCH
  ELECTRICAL POWER SWITCH FOR HEAT
  Expansion Tanks
  FIRE SAFETY CONTROLS
  Gauges on Heating Equipment
  Limit Switches, Boilers
  Low Water Cutoff Valves, Boilers
  MIXING / ANTI-SCALD VALVES
  OIL LINE QUICK STOP VALVES
  OIL LINE SAFETY VALVES
  Pressure Gauges, Boilers
  Pressure & Temperature Settings, Controls
  RELIEF VALVES - TP VALVES
  Reset Switch - Primary Control
  Reset Switch - electric motors
  Spill Switches
  Stack Relay Switch
  THERMOSTATS, HEATING / COOLING
  Water Feeder Valves, Hydronic Boiler
  Zone Valves

BOILER LEAKS CORROSION STAINS
BOILER LEAKS, HOW TO LOCATE
BOILER NOISE SMOKE ODORS
BOILER OPERATING PROBLEMS
BOILER OPERATION DETAILS
BOILER PRESSURE & TEMPERATURE SETTINGS
BUILDING SAFETY HAZARDS GUIDE
BUILDING SETTLEMENT

CABINETS & COUNTERTOPS
CAR MOLD CONTAMINATION
CARBON DIOXIDE - CO2
CARBON MONOXIDE - CO
CARBON MONOXIDE WARNING

CARPETING & INDOOR AIR QUALITY
CARPETING, SELECTION & INSTALLATION
CAT DANDER in buildings
Cell phone Radiation Hazards
CHAIN OF CUSTODY - TEST SAMPLE

CHIMNEY INSPECTION DIAGNOSIS REPAIR
CHIMNEYS & Flues - Asbestos Transite Pipe
CHINESE DRYWALL HAZARDS
COOL OFF HEAT Thermostat Switch

COMBUSTION AIR DEFECTS
COMBUSTION AIR for TIGHT buildings
COMBUSTION GASES & PARTICLE HAZARDS
COMBUSTION PRODUCTS & IAQ
COMPLETE COMBUSTION, Stoichiometric
CREOSOTE FIRE HAZARDS

CONDENSING BOILERS/FURNACES
CONDENSING BOILERS/FURNACES DAMAGE

DEFINITION of Heating & Cooling Terms
DRAFT HOODS - gas fired
DRAFT MEASUREMENT, CHIMNEYS & FLUES
DRAFT REGULATORS, DAMPERS, BOOSTERS
DUCT SYSTEM & DUCT DEFECTS
DUST CONTAMINATION FROM HVAC?

ELECTRIC HEAT
ELECTRIC MOTOR DIAGNOSTIC GUIDE
ELECTRIC MOTOR OVERLOAD RESET SWITCH
ELECTRICAL POWER SWITCH FOR HEAT
ENERGY SAVINGS in buildings
EVAPORATIVE COOLING SYSTEMS

FAN CONVECTOR HEATERS - HYDRONIC COILS
FIRE SAFETY CONTROLS
FIREPLACES & HEARTHS
FLAME COLOR, BLUE vs YELLOW COMBUSTION
FLOODED HEATING EQUIPMENT REPAIR
FLOODED SEPTIC SYSTEMS, REPAIR
FLOODED WATER HEATER REPAIR
FLUE SIZE SPECIFICATIONS
FLUE VENT CONNECTORS
FREEZE-PROOF A BUILDING
FUEL OIL TYPES & CHARACTERISTICS
FUEL UNIT, HEATING OIL PUMPS

FURNACES, HEATING
FURNACE CONTROLS & SWITCHES
  BACKDRAFTING HEATING EQUIPMENT
  CAD CELL RELAYS
  DRAFT HOODS
  DRAFT REGULATORS
  FAN AUTO ON CONTROLS
  FAN LIMIT SWITCH
  SPILL SWITCHES
  STACK RELAYS
  THERMOSTATS, HEATING / COOLING
  ZONE DAMPER CONTROLS
FURNACE HEAT EXCHANGER LEAKS
FURNACE OPERATION DETAILS

GALVANIC SCALE & METAL CORROSION
GAS BURNER Flame & Noise Defects
GAS FIRED WATER HEATERS
GAS PIPING, VALVES, CONTROLS

HEAT EXCHANGER LEAKS
HEAT LOSS in buildings
HEAT LOSS DETECTION TOOLS
HEAT LOSS INDICATORS
HEAT LOSS PREVENTION PRIORITIES
HEAT LOSS R U & K VALUE CALCULATION
HOUSEWRAP AIR & VAPOR BARRIERS
HEAT TAPES, Heat, Insulation prevent Freeze-Up

HEATING COST FUEL & BTU Cost Table
HEATING COST SAVINGS METHODS

HEATING LOSS DIAGNOSIS-BOILERS
HEATING LOSS DIAGNOSIS-FURNACES

HEATING OIL CLOUD WAX GEL POINT
HEATING OIL EXPOSURE HAZARDS, LIMITS
HEATING OIL - OLD, USEABLE?
HEATING OIL PIPING TROUBLES
HEATING OIL SHELF LIFE
HEATING OIL SLUDGE
HEATING OIL USAGE RATE
HEATING SMALL LOADS

HEAT PUMPS

HEATING SYSTEM INSPECT DIAGNOSE REPAIR
HIGH EFFICIENCY BOILERS/FURNACES

INDOOR AIR QUALITY IMPROVEMENT GUIDE
  AIR CLEANER PURIFIER TYPES
  Air Filter Effectiveness
  Air Filtering Strategies
  Air Pollutants, Health Effects
  Air Pollutants, Common Indoor
  Air Pollutants, Finding & Reducing
  Asbestos Hazards
  BACKDRAFTING HEATING EQUIPMENT
  BIOLOGICAL POLLUTANTS
  BLUE vs YELLOW COMBUSTION FLAMES
  BLUERAY Recall
  BUY PRODUCTS for MOLD & ALLERGY CONTROL
  CABINETS & COUNTERTOPS
  CARPETING & INDOOR AIR QUALITY
  CHINESE DRYWALL HAZARDS
  Combustion Appliance Contaminants
  Fireplace & Woodstove Contaminants
  Formaldehyde Hazards
  GAS EXPOSURE EFFECTS
  GAS EXPOSURE LIMITS & STANDARDS
  Gases, Quick Guide to Indoor
  INDOOR AIR HAZARDS TABLE
  INDOOR AIR QUALITY IMPROVEMENT, KEY STEPS
  INDOOR COMBUSTION PRODUCTS & IAQ
  Lead Exposure Hazards
  LP & Natural Gas Safety Hazards
  LP & Natural Gas Pressures
  METHANE GAS SOURCES
  Natural Gas Combustion Products
  ODORS, Smells, Gases in buildings
  Particles in Indoor Air - Chart
  Pesticide Exposure Hazards
  Radon Hazards
  Urea Formaldehyde Foam Insulation UFFI
  URETHANE FOAM Deterioration, Outgassing
  VENTILATION, BALANCED
  VENTILATION, BALANCED HEAT COST SAVINGS
  VENTILATION, EXHAUST ONLY
  VENTILATION, SUPPLY-ONLY
  VENTILATION, WHOLE HOUSE STRATEGIES
  Volatile Organic Compounds VOCs

INDOOR AIR QUALITY METHODS COMPARED

INSULATION INSPECTION & IMPROVEMENT

LP & Natural Gas Safety Hazards

MANUALS & PARTS GUIDES - HVAC
MIXING / ANTI-SCALD VALVES
MOTOR OVERLOAD RESET SWITCH

Nanomaterials Hazards
Natural Gas Combustion Products
NO HEAT - BOILER
NO HEAT - FURNACE
NOISE / SOUND DIAGNOSIS & CURE
NOISE, AIR CONDITIONER COMPRESSOR
NOISE, DUCT VIBRATION DAMPENERS
NOISE CONTROL for HEATING SYSTEMS
NOISE CONTROL for FLOORS
NOISE CONTROL for PLUMBING
NOISE CONTROL for ROOFS
NOISE, PLUMBING DRAIN DIAGNOSIS
NOISE, PLUMBING DRAIN REPAIR
NOISE, PLUMBING CHECKLIST
NOISE, WATER HEATER
NOISES, WATER PUMP

ODORS & SMELLS DIAGNOSIS & CURE
ODORS FROM HEATING SYSTEMS

OIL BURNERS
OIL BURNER FUEL UNIT
OIL BURNER INSPECTION & REPAIR
OIL BURNER NOISE SMOKE ODORS
OIL BURNER NOZZLE & ELECTRODES
OIL BURNERS, RETENTION HEAD
OIL BURNER SOOT & PUFFBACKS

OIL FUEL TYPES & CHARACTERISTICS
OIL & GAS PIPING
OIL LINE CLOGGING FIX
OIL LINE QUICK STOP VALVES
OIL LINE SAFETY VALVES
OIL ODORS, LEAKY OIL TANK PIPING
OIL PUMP FUEL UNIT
OIL SPILL CLEANUP / PREVENTION

OIL TANKS
OIL TANK GAUGES
OIL TANK LEAKS & SMELLS
OIL TANK PIPING & PIPING DEFECTS
OIL TANK PRESSURE
OIL TANK SAFETY
OIL TANK SLUDGE
OIL TANK TESTING
OIL TANKS, BURIED

PLASTIC HEATER VENT
PULSE COMBUSTION HEATERS

RADIANT HEAT
RADIANT HEAT Floor Mistakes to Avoid
RADIANT HEAT TEMPERATURES
RADIANT SLAB FLOORING CHOICES
RADIANT SLAB TUBING & FLUID CHOICES

RADIATORS

RELIEF VALVES - TP Valves on Boilers
RELIEF VALVES - Water Heaters
RELIEF VALVES - Water Tanks

SAFETY, HEATING INSPECTION
Safety Recalls, Chimneys, Vents, Heaters
  BLUE vs YELLOW COMBUSTION FLAMES
  BLUERAY Recall
  CHIMNEYS & Flues - Asbestos Transite
  Goodman HTPV RECALL
  Heat Recovery Ventilator RECALL
  Lennox Furnace Manuals
  Lennox SAFETY WARNING
  PLASTIC Plexvent / Ultravent RECALL
  Weil McLain RECALL
SPILL SWITCHES
STACK RELAY SWITCHES

STAIN DIAGNOSIS on BUILDING INTERIORS

STEAM HEATING SYSTEMS
  AQUASTAT CONTROL Functions
  BACKDRAFTING HEATING EQUIPMENT
  Cad Cell Relay Switch Flame Sensors
  CHECK VALVES, HEATING SYSTEM
  Chemical treatments, Boiler
  Circulator Pumps & Relays
  COMBUSTION GASES & PARTICLE HAZARDS
  DRAFT HOODS - gas fired
  DRAFT MEASUREMENT, CHIMNEYS & FLUES
  DRAFT REGULATORS, DAMPERS, BOOSTERS
  ELECTRIC MOTOR OVERLOAD RESET SWITCH
  ELECTRICAL POWER SWITCH FOR HEAT
  Expansion Tanks
  FIRE SAFETY CONTROLS
  Gauges on Heating Equipment
  Limit Switches, Boilers
  Low Water Cutoff Valves, Boilers
  MIXING / ANTI-SCALD VALVES
  Pressure & Temperature Settings, Controls
  Pressure Switch, Steam Boiler
  RELIEF VALVES - TP VALVES
  Sight Glass, Steam Boiler
  Spill Switches
  Stack Relay Switch
  Steam Pressure Gauge
  STEAM TRAPS
  Steam Vents
  THERMOSTATS, HEATING / COOLING
  WATER FEEDER Valves, Steam

TANKLESS COILS

THERMAL EXPANSION of MATERIALS
THERMAL MASS in buildings
THERMAL TRACKING & HEAT LOSS

THERMOSTATS, HEATING / COOLING
THERMOSTATIC EXPANSION VALVES
Transite Pipe Chimneys & Flues

VIDEO GUIDES: Heating System Videos
VIDEO GUIDES - InspectAPedia.com

WATER HEATERS
WATER HEATER SAFETY
WATER HEATERS for HOME HEATING USE?
WATER HEATER NOISES
WATER HEATER SCALE - De-Liming Procedure
WATER HEATER SCALE PREVENTION

WINTERIZE A BUILDING
Wood Burning Heaters Fireplaces Stoves

More Information

Airborne debris indoors (C) Daniel Friedman Backdrafting Heating Equipment Hazards Guide
InspectAPedia®  -      

  • INDOOR AIR QUALITY IMPROVEMENT, KEY STEPS
  • Removing or keeping out indoor contaminants
  • Home ventilation strategies
  • Best methods for cleaning & filtering indoor air
  • Backdrafting heating equipment: safety hazards and combustion air problems
  • Questions & answers about back-drafting and flue gas hazards at heating equipment, fireplaces, in tight houses

This article discusses the causes and cures of back drafting and flue gas spillage hazards in tight houses. We explain the difference between flue gas spillage and back-drafting.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers nor with topics or services discussed at this website.

© Copyright 2012 InspectAPedia.com, Daniel Friedman, Steve Bliss, Wiley & Sons, All Rights Reserved. Information Accuracy & Bias Pledge is at below-left. Use page top links to major topics or use links at the left of each page to navigate within topics and documents at this website. Green links show where you are in a document series or at this website.

Backdrafting of Heating Appliances & Indoor Air Hazards

This article includes excerpts or adaptations from Best Practices Guide to Residential Construction, by Steven Bliss, courtesy of Wiley & Sons.

See COMBUSTION AIR for additional details about the requirement for combustion air. COMBUSTION AIR for TIGHT buildings explains how to provide outside combustion air for tight buildings. See COMBUSTION GASES & PARTICLE HAZARDS for an explanation of the dangers of inadequate combustion air. See COMBUSTION PRODUCTS & IAQ for the relationship between fuel burning appliances and building indoor air quality. More about carbon monoxide - CO - is at CARBON MONOXIDE - CO and at CARBON MONOXIDE WARNING.

See ENVIRONMENTAL HAZARDS - INSPECT, TEST, REMEDY for our full list of environmental hazard identification and remedy related to buildings. See our summary table of INDOOR COMBUSTION PRODUCTS & IAQ and see ENVIRONMENTAL HAZARDS - INSPECT, TEST, REMEDY for our full list of environmental hazard identification and remedy related to buildings.

As discussed in Best Practices Guide to Residential Construction:

While the trend is toward power-vented appliances, most furnaces, boilers, and water heaters still use atmospheric or “natural” venting. Atmospheric venting relies on the natural buoyancy of warm air in the flue or chimney to carry exhaust gases from the home. The strength of the draft depends on the temperature difference between the flue gases and outside air, the height of the chimney, and the indoor air pressure.

  • Leaky vs. tight homes. While brief spillage of flue gases has always occurred in homes, natural-draft appliances had little trouble establishing and sustaining an adequate draft in older, leaky homes. Not only was there a ready supply of combustion and dilution air, but the flue gases were also hotter than they are in today’s more efficient appliances.

In newer, tighter houses, significant negative pressures can be generated by kitchen and bath exhaust fans, gas dryers, and unbalanced air flows in the home’s air distribution system.

Unbalanced pressures can also be caused by leaks in return ductwork, by the use of building cavities as ducts, or by the simple closing of bedroom doors in homes with a central return register. Leaky return duct- work in a basement may be enough to backdraft a water heater or furnace.

See COMBUSTION AIR for TIGHT buildings for details on how to provide adequate combustion air in tight buildings.

Gas log fireplace (C) Daniel Friedman

Spillage vs. backdrafting. If a naturally vented appliance lies in an area of the house with strong enough depressurization, the flue gases will spill into the home. When the flow reversal lasts for 30 seconds to a minute, it is called spillage; longer sustained spills are called backdrafting, a far more serious condition.

If the gas-log fireplace shown at left is not properly vented, spillage of combustion gases including possibly carbon monoxide into the building interior may be continuous. In tight quarters there is also the risk of oxygen depletion.

Watch out: Both of these are potentially fatal hazards.

While the manufacturer of the gas log shown in our photograph advertised that the burner includes a safety device that would shut off the fire in the event of dangerous oxygen depletion, we found that we were unable to operate this appliance without setting off the carbon monoxide detector alarm in the room, and the alarm continued to sound even when the detector was placed in an adjoining hallway.

Continuing from from Best Practices Guide to Residential Construction:

Once backdrafting begins and the flue gets cold, it may be sustained for a long time. Research has shown that negative pressure of as little as 5 Pascals (Pa) creates a risk of backdrafting with naturally vented boilers and furnaces. Numerous studies have documented the prevalence of high negative pressures and frequent spillage in new homes built to current codes but not intentionally built airtight.

If the heating equipment is well adjusted and has adequate combustion air, the flue gases will contain primarily water vapor and carbon dioxide, along with nitrous and sulfur oxides, and particulates.

If the burner is malfunctioning for any reason, it may put out large quantities of carbon monoxide and turn a backdrafting situation deadly. Fireplaces and poorly sealed woodstoves are most likely to reverse flow late at night when the fire is smoldering, producing a weak draft and high levels of CO.

Guide to Preventing Backdrafting at Heating Equipment, Woodstoves, & Fireplaces

There are three key elements to preventing backdrafting:

  1. Heating equipment maintenance to avoid backdrafting: In existing equipment, make sure all burners are properly adjusted and that flues are properly sized and free of cracks or blockages. Inspect annually. Common Indoor Pollutants and Sources 295
  2. Heating equipment venting to avoid backdrafting: In new construction, eliminate all atmospherically vented appliances, including woodstoves and fireplaces.
  3. Building Depressurization causing backdrafting: Minimize depressurization by reducing exhaust fan sizes and balancing airflows in heating, cooling, and ventilation systems. See COMBUSTION AIR for TIGHT buildings for details on how to provide adequate combustion air in tight buildings.

Photograph of unsafe basement reuturn air grilleWatch out: as we discuss also at Air Filter Location, a common backdrafting problem found by heating service technicians and by experienced home inspectors is the addition of an improperly-located return air or "makup air" opening in a warm air heating system return duct or in the return duct at an air handler that works for both air conditioning and heating air supply.

When the supply of cooled or heated air to occupied building spaces is inadequate and the cause is suspected to be inadequate return-air in the system duct design, an amateur retrofit "repair" for this condition is to simply cut additional return air openings in the return duct.

But if those openings are cut too close to a heating appliance, especially gas fired heating appliances, the in-draft created by the return air opening cut close to the gas burner can interfere with adequate combustion air supply to the burner, causing dangerous or even fatal carbon monoxide production, and backdrafting into the occupied space.

Also see COMBUSTION AIR for TIGHT buildings for additional details. - Ed.

Chimney Problems Related to Backdrafting

A chimney or flue that is too large, too small, or blocked by a bird’s nest or loose brick will not draw properly and will be prone to spillage problems. Uninsulated chimneys on outside walls are also prone to poor draft and to condensation problems that can deteriorate flue materials. These problems should be fixed first before addressing problems inside the house.

At CHIMNEY INSPECTION DIAGNOSIS REPAIR we discuss chimney inspection and diagnosis including unsafe venting and fire hazards.

Mechanical-Draft Appliances

Heating systems with fan-powered exhaust systems can withstand higher negative pressures than natural-draft appliances. Some types of fan-powered systems are much better than others, however. In order of effectiveness, the choices are:

  • Sealed-combustion. Also called “direct vent,” these appliances draw all combustion and dilution air from outside. These can typically tolerate negative pressures in the range from 25 to 50 Pa.
  • Power-vented. These draw their makeup air from indoors and are also called fan-assisted, forced-draft, or mechanical-draft. These can typically tolerate up to 15 to 20 Pa of negative pressure.
  • Induced-draft. These have a small fan added for energy performance, not to overcome house depressurization. These can typically tolerate 5 to 15 Pa of negative pressure.

By comparison, an atmospherically vented furnace can backdraft with as little as 5 Pa of negative pressure, and a gas water heater will have spillage at 2 or 3 Pa. Fireplaces can start having problems at about 3 Pa. Canadian codes limit negative pressures in homes with atmospherically vented equipment to 5 Pa. U.S. codes do not currently address the issue.

Guide to Reducing Building Depressurization to Assure Safe Heating Equipment Venting

To keep indoor depressurization to a minimum, do not oversize bathroom and kitchen fans (see VENTILATION, WHOLE HOUSE STRATEGIES), and avoid the use of downdraft and island fans, which can draw 600 cfm or more. If large fans must be used, they should be interlocked with a supply fan to provide makeup air.

Canada’s 1995 National Building Code requires that in homes with fuel- burning appliances vented through a chimney, any exhaust fan with a net capacity greater than 160 cfm must have fan- supplied makeup air. The makeup air fan should be sized to reduce the net exhaust rate to no more than 160 cfm and can be delivered to an adjacent room or through the forced-air distribution system. For example, a 300 cfm exhaust fan should have at least 140 cfm (300 minus 160) of makeup air.

How much an exhaust fan will depressurize a house depends on the tightness of the house. A 1993 study of several newly built energy-efficient homes in Minnesota found that exhaust airflows of 300 to 550 cfm depressurized the homes to 5 Pa, the level at which natural-draft appliances start having spillage problems.

Other studies indicate that a 600-cfm exhaust fan can produce negative pressures from 3 to over 20 Pa, depending on house tightness. Without an adequate source of makeup air, a fan this size (or a combination of exhaust fans running at the same time) will pull air from the path of least resistance—often a nearby chimney or flue. Unless makeup air is provided, exhaust fans of this strength should not be used in homes with chimneys.

How to Check for Dangerous Chimney & Flue Backdrafting by Performing a "Worst Case" Test

In homes with the potential for back- drafting, a simple test can be conducted to determine the likelihood of problems:

  1. Close all interior doors except those leading to the furnace room and rooms where exhaust fans are located.
  2. Switch on all exhaust fans, dryers, and other exhaust equipment, including the air handler if the home has forced-air heating.
  3. Turn up the thermostat to turn on the boiler or furnace, and run hot water to turn on the water heater burner.
  4. Hold a smoke indicator, such as an incense stick, about 3 inches from the draft hood of a gas furnace or water hater or near the barometric damper of an oil furnace. Test a fireplace near the top center of the firebox opening, and a woodstove near the doors or where the stovepipe connects to the stove.

Perform the test with the air handler both on and off, since unbalanced airflows can be a significant factor. If smoke spills into the room for more than 30 seconds at any combustion appliance, the home has a potential backdrafting problem that requires attention.

A more scientific procedure for determining backdrafting potential, using a pressure gauge, can be found in Step 7 of the “Recommended Procedures for Safety Inspection” in Appendix H of the National Fuel Gas Code.

Guide to Fireplaces & Woodstoves as Sources of Indoor Air Pollutants

Traditional open fireplaces and older leaky woodstoves burn very inefficiently and produce hundreds of chemical compounds, including carbon monoxide, organic gases, particulates, and some of the same cancer-causing agents found in tobacco smoke. Minor spillage of these pollutants occurs regularly, primarily when starting or stoking the fire. However, the larger concern is when the fire smolders late at night, producing high levels of CO and a weak draft. Backdrafting at this time can be dangerous or even fatal.

Another problem, particularly with fireplaces, is created when the fire is roaring and drawing up to 400 cfm of combustion air. At this point, its voracious appetite for air can cause backdrafting in other combustion appliances such as a gas water heater. Also, the need to reheat all the makeup air drags down the fireplace’s heating efficiency to less than 15% and, if the fireplace is allowed to smolder all night, it becomes a net heat loser.

Woodstove efficiency has improved dramatically in response to EPA emissions standards (begun in 1988 and updated in 1990), which apply to most freestanding wood stoves and to fireplace inserts with air-supply controls and tight-fitting doors. To meet these standards, manufacturers use either a catalytic converter, similar to the ones used in cars, or a reengineered firebox.

The new fireboxes have primary and secondary combustion zones capable of reaching system efficiencies of 60% or more and reducing combustion air intake to as little as 10 cfm. If installed with an outdoor air supply, these can be successfully de- coupled from household air pressures.

While many fireplaces are fitted with glass doors, and some have outside air intakes, nearly all of the glass doors leak air. Even with low levels of depressurization, these fireplaces can still backdraft, and the fireplace’s outdoor air supply might become the makeup air for the kitchen range hood or other exhaust fans, drawing fireplace fumes along with it. The best solution is an airtight fireplace insert.

To minimize pollution, indoors and outside, from wood-burning appliances

  • Choose a properly sized stove or insert certified as meeting EPA emissions standards.
  • Make sure the door gaskets are in good shape, the doors fit tightly, and the stove is free of air leaks.
  • Make sure the flue is the correct diameter and height, and have it inspected and cleaned annually.
  • Use wood that has been split and dried for at least six months. Try to use small pieces, and do not overload the firebox. Leave enough room for air to circulate freely around the wood.
  • For safety purposes, install a smoke alarm and carbon monoxide detector in the same room as the woodstove or fireplace.

-- Adapted with permission from Best Practices Guide to Residential Construction.

Questions & Answers regarding this article

.

Ask a Question or Search InspectAPedia

HTML Comment Box is loading comments...

Recommend / Share this Article            

...

Technical Reviewers & References

  • InspectAPedia.com® - Daniel Friedman - Publisher & Editor.
  • Steven Bliss served as editorial director and co-publisher of The Journal of Light Construction for 16 years and previously as building technology editor for Progressive Builder and Solar Age magazines. He worked in the building trades as a carpenter and design/build contractor for more than ten years and holds a masters degree from the Harvard Graduate School of Education. Excerpts from his recent book, Best Practices Guide to Residential Construction, Wiley (November 18, 2005) ISBN-10: 0471648361, ISBN-13: 978-0471648369, appear throughout this website, with permission and courtesy of Wiley & Sons. Best Practices Guide is available from the publisher, J. Wiley & Sons, and also at Amazon.com.
  • InspectAPedia Bookstore lists recommended books, organized by topic & available for purchase. Most of our articles also include a list of recommended books for the specific article topic as well as other references, and information sources.
  • Critique, contributions wanted: Contact Us to suggest corrections or additions to articles at this website, and if you wish, to receive online listing and credit as a contributor. Particular thanks are due to the many experts and also consumers who read and critique technical articles at InspectAPedia.com.
  • Additional technical contributors & reference sources for this article are listed below.

Use links just below or at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website.

BACKDRAFTING HEATING EQUIPMENT

CAR MOLD CONTAMINATION
CARBON MONOXIDE - CO
CARBON MONOXIDE WARNING

COMBUSTION AIR DEFECTS
COMBUSTION AIR for TIGHT buildings
COMBUSTION GASES & PARTICLE HAZARDS
COMBUSTION PRODUCTS & IAQ
COMPLETE COMBUSTION, Stoichiometric
CREOSOTE FIRE HAZARDS

  • [6] US EPA - Mold Remediation in Schools and Commercial Building [ copy on file as /sickhouse/EPA_Mold_Remediation_in_Schools.pdf ] - US EPA

Books & Articles on Building & Environmental Inspection, Testing, Diagnosis, & Repair

  • Our recommended books about building & mechanical systems design, inspection, problem diagnosis, and repair, and about indoor environment and IAQ testing, diagnosis, and cleanup are at the InspectAPedia Bookstore. Also see our Book Reviews - InspectAPedia.
  • Best Practices Guide to Residential Construction, by Steven Bliss. John Wiley & Sons, 2006. ISBN-10: 0471648361, ISBN-13: 978-0471648369, Hardcover: 320 pages, available from Amazon.com and also Wiley.com. See our book review of this publication.
  • Decks and Porches, the JLC Guide to, Best Practices for Outdoor Spaces, Steve Bliss (Editor), The Journal of Light Construction, Williston VT, 2010 ISBN 10: 1-928580-42-4, ISBN 13: 978-1-928580-42-3, available from Amazon.com

Home About Us Accuracy Contact Us Content Use Policy Printing Tips Privacy Website Description © 2012 Copyright InspectAPedia.com