InspectAPedia®   -   Search InspectApedia

Flexible corrugated gas connector tubing, stainless steel, un-coated, missing shutoff valve (C) Daniel Friedman LP Gas & Natural Gas Flexible Connector Installation FAQs
Q&A on how to Install & inspect flexible gas connectors

  • POST a QUESTION or COMMENT about inspecting, testing, diagnosing, and repairing gas piping, gas regulators, and gas storage tank defects used with LP or natural gas burning appliances

Flexible gas connector installation FAQs: questions and answers about how to select & install a flexible connector for gas fueled appliances or heating equipment.

This article series summarizes manufacturer's advice for the selection & installation of flexible gas connector tubing to assure adequate gas flow to support the input BTUH rating of the connected appliance, and to avoid some common sources of gas leaks such as stretching, vibration, or mechanical damage to the tubing.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?

Flexible Gas Appliance Connector Installation Procedure & Warning FAQs

Coated stainless steel gas connector for appliances or heaters (C) Daniel FriedmanThese questions & answers about installing flexible gas line connectors between an appliance and the gas supply piping and valve were posted originally at x - be sure to see the safety warnings and details given there.

On 2018-12-30 by (mod) - Required diameter & flow capacity for flexible gas line connectors

Kelly

Perhaps I've misunderstood but you want to use a 106,000 BTUh capacity connector to supply fuel to a 79,000 BTUh kitchen gas range.

That says to me that the connector is more than adequate. There is not a shred of advantage of going to a longer than necessary connector and in fact doing so can cause installation fit and even subtle safety hazards.

Use a connector that's long enough to safely install the appliance but not one of unnecessary length - that extra length can cause unnecessary bends or crimps that could damage the connector, risking a gas leak, fire, or explosion.

A connector that has the *capacity* to deliver more gas than the appliance needs is *not* a problem and won't hurt a thing. It isn't going to "force-feed" gas to your new range. It's getting the gas *pressure* correct that's important in this case. The pressure will be set by your gas supply regulator and by the appliance's own gas regulator.

On 2018-12-30 by Kelly

The new kitchen range i’m Installing has a total btu rating of 79,000 BTU.

The new connector is gold 5/8 OD x 48in @ 106,000 BTU, according to the connector chart a 60 inch connector is closer to the BTU rating of the range however I cannot locate a 60 inch locally. Is there a problem with using the 48in @
106,000 BTU?

On 2018-05-03 by Jack

Are there any flexible connectors which are safer than others? I was reading about CSST and its vulnerability to lightning strikes, which made me wonder about the flexible connector to the appliance itself.

I’ll be having natural gas installed in my home soon. After reading about CSST, I’ll tell my installer not to use it. Better safe than sorry. Besides, the distance from the meter to the appliances isn’t far anyway, so saving on labor costs is insignificant. I’ll ensure the gas line gets properly grounded as well.

On 2018-04-16 by kathy

is it bad to use a connector hose with a much higher gas input rating (106,000) than is required by our gas stove (50,500)?

On 2018-01-28 by Ted

My residence has a natural gas pressure of 7 inches of water column for the appliances. What is BTUH rating for 36 inches of 3/8 inch EHD of CSST?

On 2018-01-20 by Betty

Can a yellow brass craft gas connector be used ina gas fireplace

On 2017-01-07 by (mod) -

Sorry Danny I don't quite understand the question. If you mean that you want to use a flare adapter at the gas fire log set and that you want to use simple non-flexible copper tubing as the piping to that installation, I think you'll see that violates the manufacturer's installation instructions. A concern is that jiggling around the log set during operation may cause a gas leak.

On 2017-01-07 by (mod) - don't connect the gas shutoff hanging on a flexible gas line

Madison:

Watch out: IMO it's improper, and unsafe: I would be pretty nervous about using a gas shutoff valve mounted on a flexible gas connector piping - concerns would include ease of operation of the valve and also extra movement of the flexible line that might invite a leak.

On 2017-01-07 by Danny

The 3/8 flex connector I have has a pipe to flare connection. At the flare connection to hook up logs can I interchange the adapter at logs to a flare brass to hook up at the logs.

On 2016-04-18 by Madison

Does code allow the connection of flex gas line from BBQ to a shut off valve and then flex gas line from shut off valve to supply?

On 2015-06-02 by (mod) - gas appliance flex connector go through the side of a cabinet?

Debbie I don't know and haven't seen that detail. The final OK or authority is with your local building inspector.

What did she say? My OPINION is that if both sides of the cabinet leave the flex connector in plain view then it should be ok in that the risk of some idiot driving an nail through an un-seen gas line should be low.

On 2015-06-01 by Debbie

is it a code violation to have a gas appliance flex connector go through the side of a cabinet?

On 2014-11-29 by (mod) - gas lines that pass through building walls must be iron piping

Anon;

no. gas lines that pass through building walls must be iron piping or other approved material to reduce risk of puncture or leak

On 2014-11-29 by Anonymous

can i run a gas flex line through a wall?


...

Continue reading  at FLEXIBLE GAS CONNECTOR INSTALL - topic home, or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.

Or see these

Recommended Articles

Suggested citation for this web page

FLEXIBLE GAS CONNECTOR INSTALLATION FAQs at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.


Or see this

INDEX to RELATED ARTICLES: ARTICLE INDEX to GAS APPLIANCES, PIPING, CONTROLS

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Ask a Question or Search InspectApedia

Questions & answers or comments about inspecting, testing, diagnosing, and repairing gas piping, gas regulators, and gas storage tank defects used with LP or natural gas burning appliances

Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.

Search the InspectApedia website

Note: appearance of your Comment below may be delayed: if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.

Only one image can be added per comment but you can post as many comments, and therefore images, as you like.
You will not receive a notification
when a response to your question has been posted.
Please bookmark this page to make it easy for you to check back for our response.
Our Comment Box is provided by Countable Web Productions countable.ca

Comment Form is loading comments...

Citations & References

In addition to any citations in the article above, a full list is available on request.



ADVERTISEMENT