Building Inspection, Diagnosis & Repair Info

Honeywell room thermostatThermostat Won't Turn ON FAQs

FAQs on how to diagnose & fix a room thermostat that that won't turn the heating or cooling system ON:

Thermostat ON diagnostic questions help diagnose and fix hermostat wiring problems that cause a heating system or cooling system to stay OFF when it should turn ON.

This room thermostat diagnosis and repair article series provides a sequence of diagnostic steps that determine if the problem is at the thermostat, the thermostat wiring, or at other heating or cooling system controls.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?





ADVERTISEMENT





Thermostat Troubleshooting FAQs: heating or cooling system won't turn ON

Mini analog VOM volt-ohm meter (C) Daniel FriedmanThese questions & answers on fixing a thermostat that won't turn on heating or air conditioning were posted originally

at THERMOSTAT WON'T TURN ON - be sure to see that diagnostic article.

But if it's not a thermostat problem see HEAT WON'T TURN ON

 

On 2019-12-14 by (mod) -

Anon

That sounds odd to me, too. If jumping the red-to-white wires at the wall where you will mount the thermostat turns on the heat, but mounting the thermostat and turning its setting well above room temperature doesn't turn on the heat then the two most likely causes are improper wire-to-terminal connections at the thermostat or improper thermostat switch settings (such as a switch being set to HEAT OFF or to COOL).

More causes and cures are listed in the article above starting at https://inspectapedia.com/heat/Thermostat_Wont_Turn_ON.php THERMOSTAT WON'T TURN ON

On 2019-12-14 by Anonymous

All the wiring are set correctly so that was telling me evening the thermostat that I had was good and didn't have to buy another one but yes All the Wiser set correctly

On 2019-12-14 by David Hopkins

I brought a brand new thermostat thinking it was a thermostat when I take the face off the thermostat and connect the red and white wise it will work when I hook the thermostat back up it won't work I don't understand that

On 2019-12-11 by (mod) -

Glenn

If joining the red and white wires right at the thermostat turns on the heat but the thermostat doesn't switch on the heat when you turn it to well above the present room temperature then either the connections on the thermostat are incorrect or the thermostat switches are not set properly, or the thermostat is defective.

On 2019-12-11 by Glenn Frazier

So what could the issue with my new thermostat be this is from my last comment

I have a brand new Thermostat installed and it doesn't turn heat on it clicks but heat never comes on but when it is set to A/C it clicks and turns A/C on. But I can take the red & white wires and make the heat kick on manually

On 2019-11-25 by (mod) -

Frizz

Start by checking the thermostat wires for a break or short -

If you disconnect the thermostat wires at the heater and jump the two T T Terminals there - that's the same as if the thermostat called for heat - and the heater runs, then the problem is in the TT wiring or in the thermostat itself - its installation or location or switch settings.

On 2019-11-24 by Frizzen54

Just installed a new thermostat because I figured it was old and the cause for my furnace not coming on when temperature dropped below the set temperature. Still having the same problem. Temp drops below set temperature.

On 2019-08-28 by (mod) - I have no power to my thermostat it's on but nothing will come on

Lela

Did you check that there was

- power on to your heating or cooling system?

- power on to the circuit that supplies the low-voltage transformer (usually at the heater or air conditioner) that powers the thermostat

- un-damaged thermostat wires

- dead battery in the thermostat - SOME (a few) thermostats require a battery to work at all

On 2019-08-25 by Lela

I have no power to my thermostat it's on but nothing will come on

On 2019-04-22 by (mod) -

Is possible and easy to check just try the Diagnostics steps in the article above

On 2019-04-22 by Anonymous

Ac, heat or just the fan won't turn on. Could it be the thermostat?

On 2019-04-22 by (mod) - Ac, heat or just the fan won't turn on. Could it be the thermostat?

Is possible and easy to check just try the Diagnostics steps in the article THERMOSTAT WON'T TURN ON

On 2019-04-22 by Anonymous

Ac, heat or just the fan won't turn on. Could it be the thermostat?

On 2019-02-11 by (mod) - red wire at the thermostat?

"touch the red wire" ? at the thermostat?

That sounds to me like a loose connection or a mis-wired connection or a damaged thermostat wire.

If you disconnect the TT wires at the other end - at the heater - and jump the two TT terminals at the heater control board the heat should turn on. If it does the issue is one of those I cited above.

Watch out: there's live voltage also in heater controls and circuit boards - if you don't know how to do what I suggested without being shocked or killed hire a service technician.

On 2019-02-11 by Anonymous

we installed a new (honeywell) thermostat the heat won't kick on unless we touch the red wire at times

On 2018-12-18 by (mod) -

And,

Regarding disappearing questions that you might post, if a question contains what the comments box software thinks is a web link or photo then the question will not be visible to the public until it has been approved by a moderator.

On 2018-12-17 by (mod) -

Don

That sounds to me as if thermostat connections are either incorrect or the thermostat wires have been damaged and are shorted together somewhere in route.

On 2018-12-16 by Don Smith

I tried to get new thermostat didnt work out so hooked old one back up now the old thermostat tries to turn both heater and ac on

On 2018-12-14 by Anne

NEED HELP: I have 2 wall heaters (I will call them the main heater and second heater), both are located in different parts of the house and both are connected to identical separate non-programmable mechanical 2 wire thermostats.

The main heater has stopped responding to the thermostat. I tested the heater by connecting the wires directly ( apart from the thermostat) and the heater turned on immediately.

I then checked the thermostat by connecting it to the 2nd heater, and the thermostat worked just fine.

I then attempted to try the other thermostat (originally connected to the 2nd heater) By connecting it to the main heater; the 2nd thermostat also would not work with the Main heater. So, the heater is working ( when wires are connected directly) , and both thermostats work fine with the 2nd heater. Up until now the main heater was working fine with the thermostat.

We are so confused. If anyone has any ideas we would really appreciate it!

On 2018-11-29 by (mod) - electric heating system does nor respond using thermostat.

Richard

I would start by checking the actual wires that run from the thermostat to the heater.

Disconnect the wires at both the thermostat and at the heater.

FIRST with both ends of both wires disconnected, at each end of the pair check for continuity between them (use a VOM or DMM).

If you see continuity, since the wires are actually disconnected at the other end from that where you're testing, we can bet that they're shorted together enroute - probably this is NOT your case so

NEXT at one end, tie the two thermostat wires together

At their other end, check the wires for continuity.

That will tell us if the wires themselves were broken enroute.

On 2018-11-29 by Richard J Schlogl

My electric heating system does nor respond using thermostat. Tha main switch on the system will turn the heat on/off but the thermostat has no effect.

It started with old thermostat not responding for short while then is fixed itself. I bought a new thermostat but it also does not work. All my celebrations seem to be correct. I'm presently using the main on/off switch. Help?

On 2018-11-27 by (mod) -

Rosenarue

You can also check some easy do-it-yourself diagnostics at

https://inspectapedia.com/heat/No-Heat-Diagnosis.php

Where we describe typical problems when the issue is not the thermostat. Examples would be making sure that you have fuel and that power is on to your heating system.

On 2018-11-27 by Anonymous

(November 27, 2018) Rosemarie said:
I should add that those examples of time where I stated previously I hear the furnace running, but there is no heat.

After a few minutes the furnace sound does turn off.
Same as when I go to the Set to make changes, the furnace sound does comes on but in a few minutes it does shut off.
So it is off now and again at 63 degrees as it was this am saying Heat On, however no furnace sound and no heat.

(November 27, 2018) Rosemarie said:
Didn't post date on last comment. I should add that the thermostat stays at 63 degrees and it says Heat On, however, furnace is not running and there is no heat.

I took the face plate off and put back on moving left and right gently as explained on a site. Now, I hear the furnace which is in the attic run, but no heat. If I go to set to
correct time, etc. again I hear furnace upstairs, but no heat. I did switch the fuse box as well.

Unfortunately, it also says in tiny letters "Leave" and I have tried to
reset that to "return" but always shows "leave" anyway. Again my question is should I until someone comes by to check it, turn the thermostat to Off?

On 2017-05-19 by (mod) re: how to get the Honeywell DT92E thermostat in or out of Standby mode

Liam

If the switch on your thermostat won't change when it should, either the thermostat is defective or there is a heating or cooling system condition and problem on its other end that we don't understand.

You're citing a Honeywell DT 92E Wireless Room Thermostat with ECO energy saving feature. That thermostat includes an Off/standby button, allowing manual switch off, with frost protection active. This instruction from Honeywell should help you -

Off/Standby Button, with Frost Protection

The off/standby button allows DT92 to switch off the heating (or cooling) system at the touch of a button. To prevent accidental switch-off, the button must be held for 2 seconds to activate the change.

When off, DT92 will maintain control at a frost protection setpoint, factory set to 5°C but adjustable between 5 and 16°C. If required, frost protection can be switched off, to provide a positive off function. These adjustments are made by entering the DT92 Installer Mode.

See this HONEYWELL DT 92E THERMOSTAT SPECIFICATIONS sheet that describes the DT92E thermostat features

and be sure to

See this HONEYWELL DT 92E THERMOSTAT INSTALLATION MANUAL where you'll find instructions including how to set the off/standby button and how to enter the DT92 "Installer Mode" when needed.

Both of those are PDF files also available directly from Honeywell

Other readers, see THERMOSTAT WIRING & MANUALS, HONEYWELL for a complete list of Honeywell thermostat wiring and operation manuals that can be downloaded as free PDFs

 

 

Hunter thermostat won't turn on the heat

My thermostat brand name is Hunter

I turn my thermostat to heat and on auto but it won't come on. It only come on when I put it on Manual and then it blows just cold air out not heat On 2017-01-07 by Tracy

Reply by (mod) re: problem isn't the thermostat but it's at the heater itself

Tracy

From what you describe I think the problem is not the forced-air blower for your furnace but rather that the heater itself (gas, oil, electric) is not turning on. You may be out of fuel or there may be a problem with the burner or the heater's control.

See the steps at HEAT WON'T TURN ON and if after that you still don't have heat,

See (depending on whether your heat is hot water or forced warm air)

 

Honeywell CM921 1 day wireless programmable room thermostat is not working

I have a Honeywell CM921 1 day wireless programmable room thermostat wit LOT technology. neither the timing button ( + or -) nor the set temperature buttons will respond and we cannot turn our heating on. We have hot water though. Can this problem be fixed? On 2016-09-22 by brian

by (mod) - Here are the diagnosis and repair steps for your Honeywell CM821 Thermostat

Brian:

First check that power is on to the equipment you're trying to control.

Next

Before the buttons stopped working did you see a Low Battery indicator flashing in the display? The batteries should last about 2 years but may need replacement earlier if they were not fresh to start. This is the MOST LIKELY reason for a blank display.

If the display is not blank but the up and down buttons +/- don't work then the thermostat may be in the wrong mode.

I'd start by resetting the device to factory settings.

Follow these instructions:

Press the time button once. The display will show ‘RESET PROGRAM’.

Press the or buttons to select the preferred setting (0=user program, 1=factory program) and the display will flash, indicating a change has been made.

To confirm this change press the green button.

Next check that the thermostat is in MAN position - there the up and down buttons should work. Here is what Honeywell says:

To operate as a simple thermostat with one temperature for a period of time, move the slider switch to the MAN position. Adjust the manual temperature by pressing the
or buttons.

This can be set anywhere from 5°C to 35°C in 0.5°C steps. The thermostat will continue to maintain this temperature until another operating mode is
selected or the temperature is adjusted.

Next: did you install the BR91 relay box? If so check that the green LED is on. On that device the green LED indicates normal operation of the radio frequency system. m. When the green LED is ON the boiler is also ON. When the LED is OFF the boiler is OFF.

If you're controlling AC rather than heat,

Honeywell explains:

if your system has been set up correctly you can use your thermostat to control the cooling.

To switch the thermostat between heating and cooling modes press the and buttons together for 5 seconds in any of the product operating modes (AUTO, MAN or OFF).

The text ‘COOLING’ will be displayed for a moment on the screen to indicate the cooling operation is now active.

The factory default program for cooling is specified in the table [in the instructions], but this can be modified in the same way as the default heating program.

Last, you can completely disconnect the thermostat and its remote, then connect the TT wires together at your heater or air conditioner to force the unit on.

If that works then we know the problem is with the thermostat or its remote control, not the heater or air conditioner.

If none of these helps I'd give Honeywell support a call before going to the trouble of returning and swapping the unit.

 

My air conditioner won't turn on outside but the inside blower is on.

My unit is NOT working not even the outside unit but the blower inside is blowing is. I changed the batteries and still nothing.

My compressor outside fan won't run I have air in here but it's not cold On 2016-06-20 by david in texas

by (mod) re: when to check power to the heat pump or air conditioner

CHeck power to the outside compressor/condenser;

Then see the diagnosis and repair steps

at AIR CONDITIONER BLOWS WARM AIR

or

at AIR CONDITIONER WON'T START

 

A/C air conditioner won't turn off unless we move the thermostat UP

A/C wont kick off unless set to a higher temp, and then it shuts off normally. If left to run it stays at same temp, and sometimes -after an hour- starts to blow warm. Is that a thermostat control? On 2016-06-01 by Anonymous

(mod) re: A/C can't reach the low set temperature on the thermostat: why?

Your question suggests that the AC unit is not able to reach the lower set-temperature; the problem could be heat gain, air leaks, or a problem with the blower (low air flow) or the compressor.

by Anonymous

First, thank you for the reply. Would that be something that could start happening out of the blue. It has worked fine for several years, until about two months ago.

Sometimes turniing it off and taking the batteries out for 30 minutes fixes it, but not always.

by (mod) re: HVAC control failure versus refrigerant leaks

A control or relay can fail "out of the blue"; a refrigerant leak usually is slow and affects the system increasingly over time.

Low refrigerant can cause coil icing during long on-cycles; then you no longer get cool air.

See AIR CONDITIONER WON'T STOP

 

Honeywell thermostat works with FAN ON but not FAN AUTO

Our Honeywell thermostat works when the fan is turned to on but doesn't when on auto. The heat and cold also do not work. - On 2016-03-05 by Stephanie

by (mod) re: thermostat won't work in AUTO mode

Stephanie it sounds as if you need a service call to repair your heating system. The FAN ON switch is simply turning the fan on manually. That won't turn on heat.

If the thermostat is set well above room temperature and the heat does not turn on, then you can check the RESET button on your oil burner (IF your heat uses oil) and you can press it ONCE. If heat starts and runs you may stay warmer while waiting for repair.

Details are

at FAN-ON, AUTO, MAN THERMOSTAT SWITCH SETTINGS 

We have to hold our thermostat battery cover closed or it won't work

Thermostat said change batteries. We did. It still said change batteries. We found out if we do not close the batteries top all the way it works fine.

When we close the top it once again says change batteries. We have to sit and hold it half way closed in place in order to make it work.

If the batteries are dead will the furnace still run if it a wired thermostat? On 2016-02-14 by Skylar Rote

Reply by (mod): tighten up the battery contact springs

Skylar

I've had this trouble when the springs or contacts in the battery compartment were damaged, bent, or not making full contact. Check that all of the contacts are clean - maybe even wipe them off with an alcohol-dampened cotton swab.

Then slightly stretch out the spring lengths so that the spring pushes the battery firmly in place. Then check that the flat contact at the other battery end is making good contact.

With dead batteries, most but not all thermostats will still work; in those thermostats the batteries are there to keep from losing the thermostat's program during a power outage.

But there are some thermostats that will not work without batteries - typically because their power draw is more than that provided by the thermostat wires. The instructions for your thermostat should indicate which type you have.

 

New Digital thermostat won't work if the cover is fully attached

Our new digital thermostat works fine, as long as its cover is slightly ajar, but when that cover is set flush against the wall, the furnace won't heat.

Had it checked out by a local HV service person who says nothing's wrong with it. Don't know if it's not level or due to bad senors, wiring, batteries.

Any ideas/suggestions greatly appreciated. On 2016-02-13 by freezing cold

by (mod) re: signs of a bad thermostat wire connection

That suggests to me that there's a bad wire connection, Freeze. Digital thermostats don't care about being out of level as the temperature sensor is a tiny thermosensor. (See details about thermistors at https://InspectAPedia.com/electric/Thermistors.php )

"Nothing wrong" is baloney if the thermostat doesn't call for heat. A more honest answer would have been "I don't know how to diagnose this and I give up"

Most digital thermostats connect a bunch of pins on the back of the thermostat into a terminal block in the wall plate. If a wire is loose at the wall plate or if the thermostat itself is defective - for example if one of its pins is loose - your ajar cover explanation may be diagnostic.

It's easy to swap in batteries - worth doing, but I don't know why that'd work or not depending on cover position.

Start by confirming that the heat works properly if you simply jump the two thermostat wires at the furnace or boiler end of the circuit. After all a thermostat is basically a simple low-voltage on-off switch.

by freezing cold

None of the pins inside thermostat wall plate look loose.

Anything else I can try before buying another thermostat or calling for service again?

This never happened with original non-digital furnace thermostat. Neighbor suggests old/faulty furnace wiring might be causing this problem. Thanks again.

by (mod) re: how to rule out the thermostat as the problem cause in a no-heat or no-cooling issue

Freezing:

You can determine if the problem is the thermostat or the thermostat wiring by eliminating the thermostat entirely from the equation. If you remove the thermostat and then simply connect the two heat wires of the thermostat circuit together you're doing exactly what the thermostat itself would do on a call for heat - it's basically just an on-off switch.

So without the TT in place if you connect the wires the heat should run continuously.

by Freezing Cold - Wall furnace pilot went out again during the night & we woke up to no heat.

Wall furnace pilot went out again during the night & we woke up to no heat.

Service tech checked out furnace & thermostat, then got pilot to re-light right away.

He thinks either the furnace has a gas pressure problem, which needs to be determined by our gas company, or it's a problem with the furnace's electrical line, which he says is an easy fix. Do you agree? Thanks

by (mod) re: when to replace a thermocouple on a gas burner

What was suggested is plausible but I'd consider replacing the thermocouple as that's easy, cheap, and often the trouble.

See THERMOCOUPLE REPAIR / REPLACEMENT

Your gas company or a trained service tech can easily measure gas pressures and can tell you if you have a bad main or local (at the heater) gas pressure regulator.

Those details are

at GAS REGULATORS & APPLIANCE / HEATER CONTROLS - home, Natural Gas regulators & appliance regulators, NG & LP

Update by Freezing Cold

danjoe: My brother-in-law, an HV contractor discovered heating problems we had been experiencing, were the result of thermostat wires being stripped & not making contact after "Mr. Nothing's Wrong" squeezed them through a too small opening.

Furnace is working properly since damaged sections of wires were removed & right-sized thermostat installed.

Furnace power-pile (thermocouple) was just replaced January 2016.

Gas company technician could find nothing wrong with our home's gas pressure.

The only other thing left to check out is the wall furnace's electrical lines.

Very frustrating situation since the furnace pilot light never continued going out with the old manual thermostat. Your advice is appreciated.

by (mod)

Freezing:

Thank you for the feedback - it'll help other readers. And apologies for not replying immediately: I was traveling to freezing-cold northern Minnesota when you posted your query and I just managed to thaw out my computer today.

Indeed you're describing one of the two most common problems with thermostat wires

1. wires that are cut, broken, open somewhere in the circuit, including where the wire end is supposed to be in a connecting clamp or under a screw: sometimes this fault can be subtle, such as insufficient insulation stripped from a wire end causing the screw, when turned down, to simply pinch on the insulation rather than contact the bare copper of the wire

The thermostat won't turn ON

or

2. thermostat wires that are nicked or over-stripped and are shorted together: the thermostat won't turn OFF

by Freezing Cold - you nailed this problem right away!

B-I-L told us there were a number of red flags with this guy that could have saved us time, money & aggravation from hiring a HV contractor who was "in over his head" on this job..

.like not returning our calls for service, pressuring us, during a cold snap,he could get the furnace working again if we paid to replace all of its internal parts & finally, when he went ballistic at my wife, because he said she asked too many questions.

Glad you made it back from frigid Minnesota. You nailed this problem right away. Many thanks danjoe!

by (mod) re: red flags warn about an HVAC contractor

Thanks Freezing.
Actually I'm still in Freezing Northern Minnesota - happily the heat is working - at least indoors.

 

 

Heating Furnace keeps trying to start but dies.

Just unsure as to how big a part thermostat plays starting and keeping your furnace running

Know have thermostat issues, but when play around with it furnace will kick on, but then dies out. Will attempt to start about 3 times. Can this still be thermostat issue? Or once it starts and dies, it is probably furnace issue? On 2016-02-06 by Beth

by (mod) re: how big a part does the thermostat play in keeping the heating furnace running?

Beth,

I would stop playing around with the thermostat. Rapid turning on and off of the furnace can cause it to have worse problems, particularly with oil fired heating equipment.

The problem may be at your furnace, or there could be a loose thermostat wire. I suggest calling the repair company.

Watch out: do not keep pressing the furnace primary control reset button. You could cause a puffback explosion.

 

Our heat won't warm the room past 18C - why?

The heat will not go past 18c on the thermostat. Why does it not go higher? On 2016-01-20 by Fred

by (mod) re: why the cooling or heating system seems inadequate

Fred

If your building's rate of heat loss to the outdoors exceeds the capacity of your heating system that could be the problem; look for drafts, air leaks, heat leaks;

If your heat is by forced warm air,

see for AIR FLOW TOO WEAK for details.

Also see THERMOSTAT CALIBRATION

and

see TEMPERATURE RESPONSE of ROOM THERMOSTATS.

 

Why does our heater fuse blow when I turn on the thermostat

Fuse keeps blowing when I turn on thermostat, what is causing it? On 2015-12-21 by grady western

by (mod) re: fuse keeps blowing when I turn on the thermostat

Grady

You don't say which fuse but I suspect that you mean the fuse that powers the 24VAC tranformer that in turn powers your thermostat.

If so, I suspect that either the thermostat wires are shorted together or the transformer has failed.

Or if you see that the heater is actually trying to turn on there could be a short or other electrical failure in the heater itself.

 

We get heat upstairs but no heat downstairs

Thermostat comes on upstairs and the heat is running good, but downstairs it comes on but no heat is coming out of the vent, only cold air. On 2015-12-20 by Gerrard

Reply by (mod)

Gerrard,

Do you have two different furnaces for upstairs and downstairs? If so check the downstairs unit: it sounds as if your heat source, such as an oil burner, is not working.

My thermostat wont hold the set temperature

My thermastat wont hold temp. I need to turn off and then back On.

The heat will turn on for about. 5 minutes, then it Turns o - On 2015-12-01 by veronica

Reply by (mod)

Veronica

First check the location of your thermostat - is it in direct sun or on a wall that's abnormally warm? That can cause the problem you describe. The thermostat thinks the room is warmer than it actually is.

IF the problem is the thermostat itself that's easy to test: your heating service tech can simply jump the thermostat wires at the heater:

if it runs and keeps running the issue is the thermostat or its transformer or power supply or wiring or a bad control board or board relay in your h eater.

More help is at HEAT WON'T TURN ON or won't stay on when it should

and at RESET SWITCH on PRIMARY CONTROL - your heater may be sensing a safety issue and tripping its reset switch OFF>

 

Fix my wood furnace fan control wiring & stop it from buzzing

The fan center on the back of my indoor wood furnace (where the thermostat wires come in and the main power) was buzzing tonight while it was calling for heat.

I checked all the wires, moved them all just a little, made sure the connections were good, and then it stopped.

Does that sound like a loose connection with the wires, or does it sound like the fan center could be going bad? (Feb 12, 2015) Jon

Reply:

Jon

I am not sure from just the info in your note; but buzzing can indeed indicate an unsafe, overheating, burning electrical connection;

Don't forget to check these two common sources of HVAC control buzzing noise:

The low voltage transformer

Any control relays on the system

Detailed diagnosis and repair help for buzzing furnace controls is

at HEATING SYSTEM BUZZING NOISE 


...

Continue reading at THERMOSTAT WON'T TURN ON - topic home, or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.

Or see THERMOSTAT WON'T TURN ON FAQs-2 - more-recently-posted questions and answers about a thermostat that won't turn air conditioning, heat pump, or heating system ON.

Or see these

Recommended Articles

Suggested citation for this web page

THERMOSTAT WON'T TURN ON FAQs at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

Or see this

INDEX to RELATED ARTICLES: ARTICLE INDEX to HVAC THERMOSTATS

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Ask a Question or Search InspectApedia

Share this article:

Search the InspectApedia website

Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.

Citations & References

In addition to any citations in the article above, a full list is available on request.



ADVERTISEMENT