Building Inspection, Diagnosis & Repair Info

6 inch  DuraTech 0/12 - 6/12 Metal Roof Flashing - 6DT-F6DSA cited & discussed at InspectApedia.comFlashing for Round Metal Chimneys & Flues

Chimney flashing installation for round metal chimneys & flues: how to choose & install round chimney flashing & storm collars.

This article series on chimneys, chimney construction, and chimney safety provides detailed suggestions describing how to perform a thorough visual inspection of chimneys for safety and other defects. Chimney inspection methods and chimney repair methods are also discussed.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?





ADVERTISEMENT





Metal Flashing & Storm Collar for Round Metal Chimneys & Flues

Metal flashing & storm collar installation details for round metal chimeys - selkirk at InspectApedia

Installing the metal flashing and storm collar for a round metal chimney or flue that passes through a rooftop is not technically difficult, but it is important to follow the manufacturer's instructions completely: making a mistake in fire clearances, support, cooling venting, or storm collar installation can lead to a serious or even fatal chimney or building fire or may risk leaks causing costly damage to the building.

The illustration above shows a typical flashing and collar assembly for a round metal chimney or flue, adapted from Selkirk, cited just below.

In addition to preventing leaks and water entry and respecting fire clearances, your metal chimney installation will include a support kit that carries the weight of the chimney where it passes through the building roof or floors below.

Metal Chimney Flashing, Cap, Storm Collar Installation Instructions

Do Not Re-use a Smaller Chimney Flashing With a New Larger Chimney

Photo: a B-vent chimney venting a gas heater in a New York home. Cutting or modifying the round flashing and collar for a B-vent or gas-vent in order to push through a larger diameter chimney of a different type for venting a different fuel such as an oil-fired heater or a wood stove is likely to be unsafe and may also violate your local building and fire codes.

It also risks loss of insurance coverage should a fire or loss occur.

Several readers have asked about re-using an existing but "too-small" round metal chimney flashing when installing a new, larger metal chimney or flue.

Bottom line: don't try modifying a manufacturer's original round chimney flashing kit to fit a different size or different type of metal chimney.

The cutting and modifications to "enlarge" a "too-small" existing round metal chimney flashing risk several hazards that we list below.

Details:

There are quite a few reasons why modifying factory-designed chimney and vent products can be dangerous as well as ineffective, as we list below.

Why would someone try to modify round metal chimney flashing?

The advantage of re-use of the existing metal chimney flashing is that we avoid having to disturb the roof covering itself, as would be necessary when installing new flashing.

For an asphalt, tile, metal shingle or wood shingle/shake sloped roof, a new round metal chimney flashing installation will require loosening and probably removing some of the existing shingles or shakes to slip the upper edge and sides of the metal flashing system under the roof material.

The risks of modifying round metal chimney flashing products

If the fuel used by the new heater is different from the old one, such as changing from gas to wood fuel, the chimney design often requires more than just a larger size and use of an insulated flue.

Depending on the chimney type, additional venting is required in the chimney flashing itself - a feature not present on the gas chimney flashing system.

Watch out: cutting to enlarge around metal chimney flashing so that you can push through a larger diameter chimney will result in modified and probably reduced vent openings, risking overheating and a building fire.

6 inch  DuraTech 0/12 - 6/12 Metal Roof Flashing - 6DT-F6DSA cited & discussed at InspectApedia.com

Above and below we show what happens if you try to cut-down a standard 6-inch round metal chimney flashing kit to change to a 7-inch or 8-inch diameter opening.

6 inch  DuraTech 0/12 - 6/12 Metal Roof Flashing - 6DT-F6DSA cited & discussed at InspectApedia.com

Poor fit, leaks, especially if the flashing is old and corroded, possible fire clearance distance hazards with the new larger chimney, and thus having to do the job over again.

There's also the risk that when you install an unapproved, modified chimney product, not only will you lose any warranty from the chimney and woodstove manufacturers, I've seen insurance companies deny fire loss claims when they discover that an installation was completed without a permit and/or without respecting the installation instructions of the product manufacturers.

Watch out: as frequently warned in the metal storm collar chimney flashing installation instructions that we've reviewed, failure to follow the manufacturer's installation instructions could cause FIRE, CARBON MONOXIDE POISONING, or DEATH.

Also see FIRE CLEARANCES, METAL CHIMNEYS

Photo above: installing an insulated metal chimney in a New York home; notice the round metal flashing at the rooftop level. The weather collar has not yet been set in place.

Can You re-use round chimney flashing when switching from gas vent to woodstove?

Our reader asked:

I am changing from an existing direct-vent gas heater to a woodstove for my 1950's cottage on the Downs in Berkshire, England.

The required Class-A rated metal chimney, or insulated metal chimney for my woodstove will be two inches larger in its outside diameter than the chimney I have installed right now.

My woodstove installation contractor said he'd remove the old chimney, cut away the above-roof portion of the existing round chimney flashing, then install a new, properly sized flashing right over the old one.

I asked him why can't I just keep using the present roof flashing - I'd just trim it back to push through the new, larger metal chimney. What do you think? - Bobby Dodorino, Berkshire Downs, U.K.

Answer:

Possibly you could "use" the existing on-roof flashing, though I suspect that it will be difficult to cut a perfectly-round well-sealed hole in the existing flashing working on-the roof, and I worry that there will be other unsafe conditions such as inadequate clearance from combustibles as well as the risk of having to do the job all over again when this obviously old, rusted flashing fails.

It would be helpful to see a photo description of the flashing that we are discussing.

Even with a perfect cut and meeting fire clearance from wood framing in the roof structure, you'll also need a new properly-sized collar and that will need to be sealed to the new chimney.

And as we'll discuss here, if your cutback of the metal chimney flashing reduces or changes its venting design, it may be unsafe.

Watch out: when changing fuels, such as from gas to oil or wood, not only do chimney sizes and materials change, the chimney fire clearances, and in some designs, vents built into the chimney flashing must meet different requirements.

You cannot assume that a flashing kit for a gas fueled B-vent chimney can be safely used for sealing around an oil-fuel or wood-fuel venting chimney.

Reader follow-up:

My installer would install a new larger round chimney flashing over the remains of the cut-back original one, thus avoiding disturbing the roof shingles. He says the original under-flashing, properly-integrated with the existing roof shingles will prevent any leakage.

I'm not sure that double flashing won't trap heat and so might not work right.

My present gas heater is a direct vent gas heater that combines a concentric chimney whose outer passage is a 7" OD fresh air inlet diameter.

That's just one-inch smaller than a standard 8-inch insulated chimney that will provide a six-inch ID flue for my woodstove.

Moderator reply:

I'm baffled as to how "going over the old flashing with new flashing" (presumably larger) would buy you more gain than risk and trouble.

Metal flashing & storm collar installation details for round metal chimeys - selkirk at InspectApedia

Unless the original chimney flashing, AFTER being cut back to accept a larger chimney, still sits tall enough to avoid leaks (you don't worry as much about deep snow in Berkshire), there could still be a leak risk, and I worry that the old flashing, now out of sight, rusts and leaks into the building, causing far more-costly damage than the money you saved by re-using it.

And unless the original chimney flashing, AFTER being cut out as we're discussing also meets any heat venting requirements, it's unsafe.

You're saving only the cost of more-careful work to install the new flashing properly-integrated with the roof shingles, and you're risking the cost of much greater damage, even if safety isn't your personal worry.

So all we're doing is adding a kluge of material.

Watch out: Heat trap hazard:

Typical round metal chimney and chimney flashing and storm collar installations warn specifically that vent openings in the storm collar should not be blocked, at risk of fire.

Watch out: Venting is required & is built into flashing for some fuel type chimneys:

You need to understand as well that either your existing metal chimney flashing does not even have the required venting used with the insulated chimneys required by your woodstove, or by cutting back the flashing to pass a larger-diameter round metal chimney you're reducing or even eliminating those vent openings, creating a potentially fatal fire or CO hazard. See the illustration we include above, adapted from Selkirk whom I'll cite later.

Also, you're describing an existing "direct vent" through-roof vent system for a gas appliance - operating at substantially lower temperatures than a woodstove, and using a smaller flue.

What's the fire clearance distance from the existing chimney to nearest wood framing in the structure?

Can your new chimney meet its fire clearance requirement? Often a zero-clearance chimney still wants an inch of air space - depending on brand, model, type of chimney.

But I agree that re-working interlocking shingles on an older roof risks troublesome damage to the shingles themselves. I'd want to have the work done by someone who has experience installing and repairing metal roof shingles.

There are several roofing companies near Berkshire who offer metal roofing consulting, repairs, and installation. Have the chimney flashing installed by one of those experienced companies and you'll avoid a lot of trouble and perhaps unnecessary cost of damaged metal roof shingles.

A quick and thus incomplete search for metal roofers near Berkshire in southern England found that there's no shortage of experts:

  • Bracknell Roofing Ltd.,
  • Crown Roofing Contractors
  • Newbury Metal Roofing
  • Ramsey Roofing Limited
  • Reymills Estate Metal Roof Company
  • WillFix Roofing

In my OPINION, the practical concerns and risks of modifying an existing gas vent chimney to fit a wood-fueled vent chimney include at least:

Cutting back the existing flashing might permit a new larger diameter chimney to physically pass through, I agree, but at loss of flashing height, leak risks, fire clearances and other more subtle risks that you should consider:

  1. poor fit, leaks and water and mold damage to the building
  2. depending on an old flashing that looks rusted or corroded, maybe unreliable and leading to doing the same job twice
  3. possibly failing to provide proper fire clearance risks much greater cost than the money saved by not replacing the flashing

A new, 8-inch replacement round chimney flashing, depending on materials and features such as adjustable pitch, costs between $50 and $150. U.S.D. or 40 to 120 GBP pounds - a small price to pay for assuring a proper fit, safer installation, to which we indeed must add the greater cost of installation.

Steps to Follow if You Insist on Under-Sized Re-Using Old Round Metal Flue Chimney Flashing

Here is my OPINION of a reasonable sequence that respects your wish to re-use the old chimney if you can:

1. Comply with insurance and codes:

Establish with your insurance company that modifying and re-using an old chimney flashing and roof penetration during a change of chimney use from gas appliance to wood-burner will not affect your insurance coverage - lest you lose protection in the event of a fire or loss.

Check the same question with your local building department to be sure you're not in violation of local building codes.

2. Check that you can physically fit the new chimney

through the existing vent passage, roof opening, and cut-out rooftop flashing while meeting required fire clearance distances and new chimney manufacturer's instructions

3. Try the modification route to re-use the old roof opening & flashing:

IF steps 1 & 2 are satisfied, remove the old gas vent and try an on-roof cut-back and modification of the existing flashing to pass the new, larger insulated chimney.

At the very least, for a proper seal you'll need a new collar around the new chimney, just above the top of the old rooftop chimney flashing.

If in the course of this modification you don't see any evidence that the old flashing is rusted or corroded so as to have short remaining life then you can try it.

4. Or replace the flashing assembly with the right one.

If steps 1,2,3 don't all pass acceptably, then work carefully to remove or loosen just enough roof shingles to remove the old flashing and then get the new flashing in place.

Consider that you may have to adjust the original chimney opening through the roof and through any ceilings below to meet required fire-clearances to combustibles. Replace the removed shingles.

The recommended articles listed at the end of this page may also be of help.

...

Continue reading at METAL CHIMNEYS & FLUES - home, or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.

Or see these

Recommended Articles

Suggested citation for this web page

FLASHING, CHIMNEY MISTAKES & LEAKS at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

Or see this

INDEX to RELATED ARTICLES: ARTICLE INDEX to CHIMNEYS & FLUES

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Ask a Question or Search InspectApedia

Share this article:

Questions & answers or comments about chimney flashing leaks & defects that are found by an on-roof inspection.

Search the InspectApedia website

Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.

Citations & References

In addition to any citations in the article above, a full list is available on request.



ADVERTISEMENT