InspectAPedia®   -   Search InspectApedia

Photograph of the outdoor safety switch for an air conditioning residential systemA/C or Heat Pump Compressor / Condenser Disconnect Switch

Electrical Code & Distances

  • POST a QUESTION or COMMENT about how to find, identify, & use or troubleshoot each control or switch found on air conditioners or heat pumps.

A/C or Heat Pump Compressor/Condenser Unit Safety Disconnect Switch:

What is the proper location & permitted distance for a safety electrical disconnect switch at or near the outdoor compressor/condenser unit of HVAC systems?

What is the requirement for placement, distance, and readily accessible nature of the disconnect or motor controller for equipment operated by an electric motor. U.S. NEC code citations, excerpts, discussion.

Page top photo: at right is a Square D service switch for an outside compressor/condenser unit. The larger metal box at left in the photo is used as an electrical junction box for wiring the outdoor condenser unit.

Notice that its cover is secured by a bottom screw while, for safety, the shutoff control at right can be quickly opened by lifting and pulling forward on the cover to expose the switch itself. Our next photo, below, shows the service switch in this box once I (DF) have opened the cover.

This article series explains where to find and how to use the switches and controls for air conditioning and heat pump systems. We list and explain the function of each air conditioner or heat pump control or switch, including providing identification photographs and troubleshooting tips.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?

List of Outside A/C or Heat Pump Service Switches, Fuses, Circuit Breakers

Photograph of the outdoor safety switch for an air conditioning residential system, shown here with the cover open

The pair of photographs at page top and just above show the outdoor air conditioner or heat pump compressor/condenser service control switch, in this case a circuit breaker, installed outside at a compressor for a ductless cooling system compressor.

More photographs of a ductless or split system air conditioning system are

at A/C TYPES, ENERGY SOURCES.

[Click to enlarge any image]

Below you will see an air conditioning system compressor/condenser service switch for an outdoor compressor/condenser outdoor unit that was remarkably unsafe.

The photo (below) shows that there was a 240V fused circuit with outdoor fuses in the box, but this close up photograph [Image file] shows that someone has installed 1/2" copper pipes in place of the original fuses.

This might be a dangerous installation, risking fire as well as a burn up of the air conditioning equipment.

But as Mark Cramer contact reference] pointed out, if the circuit were properly protected by breakers or fuses at the main panel, the insertion of metal pipes in these fuse sockets just converts the device from a fuse box to a simple switch. An on-off switch is all that is required for this location and application by electrical codes.

Circuit breaker(s) at the electrical panel protect the circuit supplying power to the air conditioning system. Typically separate circuit breakers (or fuses) power the compressor/condenser unit and the indoor air handler/blower assembly.

In any case, simply installing fuses would restore the proper safety device but it's likely that further testing and diagnosis of the electrical circuit and the compressor/condenser unit will be needed to determine why someone installed copper pipes where fuses belonged in the first place.

Photograph of the outdoor safety switch for an air conditioning residential system

When someone converts fuses to a switch in this location it may be because the air conditioning system was frequently blowing the fuses -- someone wanted to force the compressor/condenser to run.

Compressor Service Switch or Disconnect Air conditioner compressor (C) Daniel FriedmanLocation & Distance

The air conditioning system compressor service switch is located outdoors, at the compressor/condenser unit, typically on a building wall near the outdoor unit, this switch may be a circuit breaker, a fuse block pull-out, or a simple electrical switch.

Service switches permit a service technician to work safely on the equipment by turning off electrical power to the unit without having to run back and forth through the building to the main electrical panel.

Where the compressor/condenser service switch is omitted some technicians are tempted to work on equipment while it is electrically "live", and a few of them get shocked.

These switches are required by current electrical codes but may be absent on old A/C installations.

If no service switch is installed at the compressor/condenser you should have one installed at the next A/C service call or next electrical work done on the building.

Watch out: In our photograph just above, the A/C service switch is very unsafe for two reasons: first, because it is falling off of the wall it may be difficult to operate the switch. Second, ask yourself, "What happened to the screws that were used to fasten this switch to the building wall?"

We've seen cases of the mounting screws falling into the switch box, causing a short circuit or even a fire. In this particular case the vinyl siding installers pulled the switch loose to install siding and didn't bother to reinstall it.

Air Conditioner / Heat Pump Compressor Condenser Switch Maximum Distance to the Compressor/Condenser Unit Disconnect

Photograph of an air conditioning compressor/condenser service switch that is unsafeWatch out: our photo shows an outdoor disconnect switch for a condenser unit: it is falling off of the wall. Loose electrical boxes pose fire and electrical s shock hazards.

Wires move and connectors may come loose, exposing someone touching the box to fatal electrical shock, and on occasion a screw falling out of the wall and into an outdoor electrical box can cause a short circuit that starts a building fire.

The following details are excerpted from the 2011 edition of the US National Electrical Code / NEC.

NEC 430.102(A) and (B) apply to electric motors driving other equipment such as a non-hermitcally-sealed compressor motor found on some commercial equipment or such as a fan coil unit.

I [DF] have encountered these installations at both walk-in coolers and some commercial freezers. NEC 430 includes definitions of readily accessible and of within sight.

NEC 440.13 and NEC 440.14 rules for motor disconnect means apply to typical outdoor HVAC compressor/condenser units while

The two sets of disconnect distance rules are similar.

NEC 440.13 disconnect for room air conditioners or heat pumps - paraphrasing: the air conditioner or heat pump unit disconnect must be within sight from and readily accessible from the unit.

440.13 Cord-Connected Equipment. For cord-connected equipment such as room air conditioners, household refrigerators and freezers, drinking water coolers, and beverage dispensers, a separable connector or an attachment plug and receptacle shall be permitted to serve as the disconnecting means.

Informational Note: For room air conditioners, see 440.63.  

For a room air conditioner such as a window-unit, an electrical cord plug that can be simply un-plugged from the electrical receptacle counts as an acceptable disconnect provided the cord is shorter than 6 ft. on a 220VAC unit or less than 10 ft. for a 120VAC unit.

NEC 440.14 disconnect for central or split system air conditioners or heat pumps

- paraphrasing: The air conditioner or heat pump compressor/condenser outside service switch or service disconnect must be readily accessible & within sight of the compressor/condenser unit

440.14 Location. Disconnecting means shall be located within sight from and readily accessible from the air- conditioning or refrigerating equipment. The disconnect- ing means shall be permitted to be installed on or within the air-conditioning or refrigerating equipment.

The disconnecting means shall not be located on panels that are designed to allow access to the air-conditioning or refrigeration equipment or to obscure the equipment name- plate(s).

Exception No. 1: Where the disconnecting means provided in accordance with 430.102(A) is capable of being locked in the open position, and the refrigerating or air-conditioning equipment is essential to an industrial process in a facility with written safety procedures, and where the conditions of maintenance and supervision ensure that only qualified persons service the equipment, a disconnecting means within sight from the equipment shall not be required.

The provision for locking or adding a lock to the disconnecting means shall be installed on or at the switch or circuit breaker and shall remain in place with or without the lock installed.

Exception No. 2: Where an attachment plug and recep- tacle serve as the disconnecting means in accordance with 440.13, their location shall be accessible but shall not be required to be readily accessible.

nformational Note No. 1 : See Parts VII and IX of Article 430 for additional requirements. Informational Note No. 2: See 110.26.

Examples where this exception apply include room air conditioners, home refrigerators or freezers, similar free-standing plug-in cooling appliances.

NEC 440.63 disconnecting means for room air conditioners

gives more guidance for the disconnect for portable devices like room air conditioners

440.63 Disconnecting Means.

An attachment plug and re- ceptacle or cord connector shall be permitted to serve as the disconnecting means for a single-phase room air condi- tioner rated 250 volts or less if

(1) the manual controls on the room air conditioner are readily accessible and located within 1.8 m (6 ft) of the floor, or

(2) an approved manually operable disconnecting means is installed in a readily ac- cessible location within sight from the room air conditioner.

440.64 Supply Cords.

Where a flexible cord is used to sup- ply a room air conditioner, the length of such cord shall not exceed 3.0 m (10 ft) for a nominal, 120-volt rating or 1.8 m (6 ft) for a nominal, 208- or 240-volt rating.

440.65 Leakage-Current Detector-Interrupter (LCDI) and Arc-Fault Circuit Interrupter (AFCI).

Single-phase cord-and-plug-connected room air conditioners shall be provided with factory-installed LCDI or AFCI protection.

The LCDI or AFCI protection shall be an integral part of the attachment plug or be located in the power supply cord within 300 mm (12 in.) of the attachment plug.

Definition of readily accessible & within sight

NEC 430.107 Readily accessible & within sight

means that the disconnect switch is visible from the controlled-device and can be reached and used without having to climb obstacles or use a ladder.

This distance is typically described as within 50 feet (15 meters), and in practice at most residential properties the disconnect is much closer (3-6 ft), on a wall or standard near the compressor/condenser unit.

Within sight of is defined as within 50 feet (15 m) and able to be seen from the component being disconnected (and vice versa). The disconnect also has to be directly accessible, so "seen through a window or over a fence" would not be acceptable as it would not be safe.

Typically there is also a GFCI protected outdoor electrical receptacle within 25 feet of the compressor/condenser, it's likely that those two features will be together at most installations.

We have read reports that some local building code officials may require a closer distance - 3 feet - to the switch.

Note that for the indoor equipment the rule is a bit different. NEC 440.14 permits the air handler disconnect to be on or even inside of a cover at the air handler unit, though in my OPINION on or adjacent-to the unit is safer as it doesn't require opening a panel into the air handler itself (where there could be moving parts or exposed wires) to access the service switch.

Maximum distance between disconnect or controller and an electric motor

NEC 430.102 disconnect for electric motors driving equipment or machinery provides minimum distance requirements for the disconnect for the electric motor or its controller.

NEC 430.102(A) Motor-Controller disconnect

(paraphrasing) the disconnect must be in sight from the controller and must disconnect the controller from its power source. (A controller is defined in NEC 430.81 as the device used to start and stop a motor. )

It's worth noting that for commercial installations OSHA 1910.333 requires that equipment be powered off when being serviced, with the exception that some test procedures will require the equipment to be on. (Additional protection for the worker is required.)

NEC 430.102(B) Motor electrical disconnect

(paraphrasing) the electrical disconnect must be within sight of the motor (and driven machinery operated by the motor). This rule provides safety for workers on equipment that might be switched on or off without power passing through a separate motor controller device.

Where both an electrical disconnect and a separate motor controller are both installed, at least one of these devices capable of turning off the motor itself (and thus turning off the machinery it drives) must be within sight from the motor and must be readily accessible.

Where the electrical motor disconnect is within sight of and readily accessible to both the motor controller and the motor itself and the equipment driven by the motor then the electrical disconnect will satisfy both NEC 430(A) and NEC 430(B).

Exceptions to these US NEC provisions are permitted where applying the provision is not feasible or not safe.

Where there are multiple motor controllers installed, NEC 430.102(A) permits the use of a single electrical disconnect switch that turns off all of the "coordinated" motor controllers.

Where to Find Copies of NEC or Other Building Codes online

List of Other HVACR Controls & Switches

Heat off switch © D Friedman at InspectApedia.com Other electrical switches and controls such as an air conditioner or heat pump pressure safety switch found on or near the compressor/condenser unit and in some window and through-wall units can also shut down an air conditioner or heat pump system, as we discuss in this article.

...





ADVERTISEMENT





...

Continue reading at CONTROLS & SWITCHES, A/C - HEAT PUMP or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.

Or see A/C HEAT PUMP CONTROL / SWITCH FAQs - questions & answers posted originally on this page

Or see these

Recommended Articles

Suggested citation for this web page

COMPRESSOR DISCONNECT SWITCH at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.


Or see this

INDEX to RELATED ARTICLES: ARTICLE INDEX to AIR CONDITIONING & HEAT PUMPS

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Ask a Question or Search InspectApedia

Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.

Search the InspectApedia website

Note: appearance of your Comment below may be delayed: if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.

Only one image can be added per comment but you can post as many comments, and therefore images, as you like.
You will not receive a notification
when a response to your question has been posted.
Please bookmark this page to make it easy for you to check back for our response.


Comment Form is loading comments...

IF above you see "Comment Form is loading comments..." then COMMENT BOX - countable.ca / bawkbox.com IS NOT WORKING.

In any case you are welcome to send an email directly to us at InspectApedia.com at editor@inspectApedia.com

We'll reply to you directly. Please help us help you by noting, in your email, the URL of the InspectApedia page where you wanted to comment.

Citations & References

In addition to any citations in the article above, a full list is available on request.

  • Thanks to Alan Carson and Bob Dunlop, Carson Dunlop, Associates, Toronto, for permission to use illustrations from their publication, The Illustrated Home which illustrates construction details and building components. Carson Dunlop provides home inspection education, publications, report writing materials, and home inspection services. Alan Carson is a past president of ASHI, the American Society of Home Inspectors.
  • Thanks to Lester Richer, a professional home inspector, for the reminder that a bad air conditioner condensate drip tray switch can shut the whole system down.
  • Behr Hella Service A/C pressure switches,
  • Grainger, http://www.grainger.com/
  • Ranco Corporation, http://www.invensyscontrolseurope.com/ranco/ Tel (Europe) +44 (0)845 130 5522
  • Sensata Technologies, 529 Pleasant Street, B41 Attleboro, MA 02703-2964 Phone: 1-248-692-5600 Fax: 1-248-692-5630 Email: auto-mktg@sensata.com Web: www.sensata.com, pressure switches for automotive air conditioning systems
  • Micro Pneumatic Logic, Inc., Pompano Beach, Florida Tel. (954) 973-6166 - pressure switches
  • Modern Refrigeration and Air Conditioning, A. D. Althouse, C.H. Turnquist, A. Bracciano, Goodheart-Willcox Co., 1982
  • Principles of Refrigeration, R. Warren Marsh, C. Thomas Olivo, Delmar Publishers, 1979
  • Refrigeration and Air Conditioning Technology, 5th Ed., William C. Whitman, William M. Johnson, John Tomczyk, Cengage Learning, 2005, ISBN 1401837654, 9781401837655 1324 pages
  • In addition to citations & references found in this article, see the research citations given at the end of the related articles found at our suggested

    CONTINUE READING or RECOMMENDED ARTICLES.


ADVERTISEMENT