Shower Pan & Shower Pan Membrane Construction & Installation: Best PracticesShower pan choices, installation, troubleshooting:
This article discusses the proper construction or installation of cement, pre-fab, or mortar-bed shower pans and shower pan membranes to build a leak-proof shower floor.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?
This article series discusses current best design practices for kitchens and bathrooms, including layout, clearances, work space, and accessible kitchen and bathroom layout, clearances, turning space, grab bars, controls, etc.
We include advice on choosing and installing kitchen countertops, cabinets, and kitchen or bathroom flooring, sinks, and other plumbing fixtures and fixture controls such as faucets. A list of kitchen and bath product manufacturers and sources is included.
The fiberglass shower pan shown at left was placed and secured to the floor during bathroom construction, then protected from damage with cardboard pending installation of shower enclosure, plumbing, controls, and door.
As explained in Chapter 6 of Best Practices Guide to Residential Construction (Steve Bliss, J Wiley & Sons) :
A shower pan must be completely watertight and able to hold pooled water should the drain get clogged.
Most are built in place over a mortar bed with a waterproof membrane liner.
However prefabricated setting beds have also become available recently.
Our collapsing, leaking shower pan/floor installation (left) illustrates why site-built lead lined shower pans are a "lost art" and why most contractors opt for pre-fab shower pans of cement, fiberglass, or other materials.
For standard shapes and sizes, one option is to install a prefabricated pan made from 40-lb polystyrene foam coated with a reinforced cementitious coating that is ready to receive tile.
These range in size from 36x36 inches to 36x60 inches and come pre sloped with a built-in drain.
One unit, called Pro-Form (Bonsal American) is bonded to the subfloor with latex modified thinset, coated with a liquid waterproofing membrane, and is then ready to tile.
As long as the subfloor is sufficiently stiff to prevent flexing, these units should perform well with 4x4–inch tiles. Smaller tiles may exert too much of a point load for the underlying foam, while larger tiles can cause problems with the slope angle.
A less expensive option is to combine tiled walls with a one-piece fiberglass or acrylic shower pan (not to be tiled). These are the same materials used in one-piece shower or shower-tub units. A few companies also sell stand-alone solid-surface shower pans.
Like other plastic units, these must be properly supported underneath to prevent flexing and cracking. Some require setting in sand, wet mortar, or plaster. In general, acrylic units cost more than fiberglass but are stronger and less prone to flexing and cracking.
Built-in-place shower floors using a mortar bed and modern waterproofing shower pan membranes can provide many years of trouble-free service. For best performance use a heavy-duty sheet membrane, such as 40-mil Chloraloy (Noble Company), which is designed for use in shower pans and similar applications.
To guarantee that any trapped water will drain properly, the shower pan membrane is placed on a layer of latex-modified mortar sloped 1/4 inch per foot toward the drain.
Two-piece clamping-type drains are designed to seal to the membrane by compression between the upper and lower flanges (see Figure 6-41).
[Click any image or table to see an enlarged version with additional detail, commentary & source citation.]
A layer of sealant applied between the shower pan membrane and lower flange serves as backup waterproofing. Weep holes around the bottom of the drain, surrounded by pea gravel or pieces of broken tile, allow any water that accumulates to drain away (see Figure 6-42 below).
The shower pan membrane should run up all sides of the shower, at least 3 inches above the height of the finished curb.
Secure the membrane to the framing with galvanized staples or roofing nails along the top edge, being careful to make no holes in the membrane any lower than 2 inches above the finished curb.
At the inside wall corners, the extra membrane material is not cut, but pleated and folded over to lay flat against the framing. Avoid making wrinkles here or along the bottom of the pan.
At the curb, the membrane must be cut so it can fold over the top of the curb. Seal these corner cuts with either prefabricated “dam corners” or patches of membrane caulked in place with Nobleseal 150, a high-performance Kraton-based sealant.
-- Adapted with permission from Best Practices Guide to Residential Construction (Steve Bliss, J Wiley & Sons) .
...
Below you will find questions and answers previously posted on this page at its page bottom reader comment box.
On 2020-03-19 - by (mod) - don't confuse shower pan liners & membranes with peel-and-stick flashing membranes
Richard:
Thank you for the comment.
Indeed it's important to distinguish between peel-and-stick flashing membranes used on building exteriors and shower pan liners and membranes as they are different products with different requirements.
If you have an application that needs to hold standing water I'd recommend either using EPDM (rubber roofing) outdoors, or if protected by a finish surface, a shower pan liner rated for that use.
Indeed flashing membranes like those described at FLASHING MEMBRANES PEEL & STICK, aka "peel and stick membranes," are intended for use on buildings in areas that drain water away such as around windows and doors and as a sloped roof underlayment or valley liner.
Most of those products are not intended for use in showers as a shower pan liner and will fail in that location.
However there are a number of shower pan liners intended specifically for that use, typically 40 mil PVC membranes that are set in place, folded up at edges and corners, and where needed, adhered in place using a special PVC cement such as that provided by Oatey.
Examples of Shower Pan Liners and similar products that can tolerate standing water include:
BetterBath RV Shower pan liner membrane
Compo-Tite shower pan liner
Goof-Proof Waterproofing sheeting
Kohler K-8458 shower pan liner membrane
NobleSeal thinset TM shower pan liner
Oatey No. 41620 40 mil PVC shower pan membrane liner - shown below
Oatey "Perfect Brown" shower pan liner
Schluter Kerdi shower pan liner
Wal-Rich shower pan membrane
And there are paint-on waterproofing pan liner materials such as
Laticrete HydroBan waterproof membrane
Here is Oatey's PVC adhesive for shower pan liners
On 2020-03-19 by Richard McLauchlan
Shocked to discover many peal stick membranes (none torch on) are not designed warrantied to hold standing water! sill pan protection not
This Q&A were posted originally
at FLASHING MEMBRANES PEEL & STICK
...
Continue reading at CERAMIC TILE FLOOR & WALL or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see these
SHOWER PAN INSTALLATION & LINERS at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Search the InspectApedia website
Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.
In addition to any citations in the article above, a full list is available on request.