InspectAPedia®

Basic example of electricity (C) Carson Dunlop Associates Compare 120Volts to 240Volts - Is one More Energy Efficient?
Effect of 240V wiring on motor life

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.


Efficiency or energy savings of 240 Volt vs 120 Volt appliances & devices:

This article describes the difference between wiring an electrical motor, such as a well pump, to operate at 120 volts compared with 240 Volts and answers the common question of whether or not wiring an electrical device to operate at higher 240 Voltage level will save on the electrical bill by using less energy.

The short answer is no, and details are provided below. Sketch courtesy of Carson Dunlop Associates. Photographs and sketches illustrate voltage, electrical resistance, and other electrical wiring concepts.

We also provide a MASTER INDEX to this topic, or you can try the page top or bottom SEARCH BOX as a quick way to find information you need.

Does Wiring a Motor at 240V Save Electricity over Wiring it to Run at 120V?

240V pump relay switchAs we discuss at both AMPS VOLTS DETERMINATION and at VOLTAGE at the SEC the total current (Amps) that will flow through a wire (electrical conductor) is cut in half if the pressure (Volts) is doubled.

Twice the electrical power or energy can be delivered on a # 12 wire by doubling the voltage and holding the current unchanged, for example at 20 amps. Doubling both voltage and also doubling the amperage would deliver four times the power or energy. Thanks to reader Bob Hawley, for careful reading & editing of this point.

But doubling the power or energy does not mean that we cut our electrical bill in half. Why not? (Our photo at left shows a 240V pump control switch.)

As we introduced at Definition of Volts, Volt, formally, is defined as the potential difference across a conductor when a current of one ampere dissipates one watt of power.

This definition is not very helpful to consumers. Using a water-in-pipes analogy, volts is analogous to water "pressure" in the electrical system.

Having higher "pressure" in a pipe (or electrical conductor) means that conductor is capable of delivering more energy to the user. Later in this article we further explain electrical potential.

Mathematically the following simplified formula relates volts, watts, and amps in an electrical circuit

Volts = Watts / Amps. (Volts equals Watts divided by Amps).

Electrical Energy Usage Measured in Watts

The watts consumed (and therefore the size of your electric bill) for running a water pump or other electric motors will be almost exactly the same regardless of whether you are running the pump wired at 120 Volts or 240Volts.

Using an imperfect "water pressure" analogy, sending water through a pipe to move a water wheel, if we double the pressure (volts) at which we are supplying water energy to push the wheel, the number of gallons per minute (amps) we need to do the same work is cut in half.

Well pump data label (C) Daniel FriedmanSo if we keep our pipe and water wheel and all else the same, but send water through the pipe to push the wheel at 240 psi, we would need half as much water quantity (measured in gallons per minute or "amps") to turn the wheel at the same rate as if we were pushing on the wheel at 120 psi.

[Click to enlarge any image]

Electrical motor voltages are similar in this regard. If we have an electric motor that is designed to run at either 120V or 240V (not all of them are) then the label on the motor will tell us that at 120V (pressure or potential) the pump motor will draw about twice as much amperage (current) as at 240V.

Our label (photo at left) shows that this 1/2 horsepower jet pump electric motor can run at either 115V at 10.8 Amps of current draw, or at 230V at 5.4 Amps of current draw.

With this example, if our electric pump motor draws 10.8 Amps when running on a 120V circuit, you see from the motor label that it draws 5.4 Amps when in use on a 240CV circuit.

10.8 Amps = ?Watts / 120 or doing the algebra, 120 x 10.8 = 1296 Watts when our pump motor is running at full load and wired on a 120 Volt electrical circuit.

05.4 Amps = ? Watts / 240 or doing the algebra: 240 x 5.4 = 1296 Watts when our pump motor is running at full load wired on a (nominal) 240 Volt electrical circuit.

The electric meter at a building measures electricity usage in kilowatt hours (KWH). If you run a 1000W electric heater for one hour, you've just used 1 KWH of electricity. So the pump is costing essentially exactly the same to run at either voltage level.

So what advantages do we get from running an electric motor at 240V rather than 120V?

Pump pressure switch data (C) Daniel Friedman

Most electric motors will be a little easier to start turning at higher voltage. And for the same amperage draw, at 240V a smaller diameter circuit wire may be permitted - thus the circuit is a little less costly.

Finally, on a long circuit, the voltage drop due to resistance of the wire itself will be less at 240V than at 120V. However, separately, some experts point out that higher voltage circuits are potentially more dangerous.

In sum, the electric bill is about the same, but at 240V the pump has a little easier time starting, it may thus have a little longer life, and the wiring might be less costly.

The improvements in efficiency of use of electrical power is slightly better at higher voltages (less energy loss) but running a water pump will not be noticeably more or less costly between the two options.

See DEFINITIONS of ELECTRICAL TERMS for definitions of Amps, Volts, Watts, Ohms, etc.

Our photo at left shows the data tag inside of a pump pressure control switch and shows that the switch might be wired for either 120V or 240V if other site conditions and equipment specifications permit.

Reader comment: 220/240 50/60HZ Motors last longer

(Oct 29, 2015) RB Davis said:

The reason for using 220/240 50/60HZ is that Motors last longer. It's a well known fact it is more economical to use that rather that household current. Ask yourself why Industry does not use 120VAC motors in HD applications? And we all know HD products are better than household products. Certain facts come from hands on experience and general wisdom that age and experience provides, Not all things are "by the book" or apparent by simple math equations. - RB DAVIS - Electro-Mechanical Eng., formally with Struther-Dunn Relays.

Don't Rush to Re-Wire your Well Pump from 120V to Change it to 240V

Pump pressure control switch at 120V (C) Daniel FriedmanThe pump pressure control switch in our photo at left has contacts that permit it to be wired to operate at either 120V or 240V. But we don't know if the pump motor itself can run at either voltage. First make sure that the pump motor and control are labeled to indicate that either voltage level is permitted with the equipment you have installed.

Second we don't know that the pump motor, even if it can run at 240V, will not also require a heavier-duty pump control switch than this relay.

Second, there will be some additional costs when changing the voltage level at which an electric motor is going to be operated.

Even if the electrical wires can be left un-changed (when moving UP from 120V to 240V) the overcurrent protection (circuit breaker or fuses) will need to be changed to properly and safely protect the electrical circuit. In either case, if we exceed the current rating of an electrical wire, it will get hot, risking a fire. That's why we use fuse devices (or modern circuit breakers), to limit the current flow on electrical conductors to a safe level to avoid overheating and fires.

Some but possibly not all motor controls such as well pump control switches can be re-wired to operate at either voltage. But if not you'll need to replace the pump control switch.

The wall switch to turn off the well pump will need to be changed and rewired if you change the voltage serving the pump.

So when might we make these changes? Certainly when a new well pump is being installed or when other electrical work is being done on a building that would be the time to ask your licensed electrician about pump wiring and circuit voltage.

Reader Question: wiring for dual voltage so we can switch back and forth

(Aug 17, 2011) bill abrams said:

it would be nice to wire for dual voltage so I could run the pump from a 120v inverter during a power outage. Any one tried this?

Reply:

(Aug 17, 2011) (mod) said:

Bill the pumps I've worked with (which is not many) had to be opened and jumpers moved to select a power source (for pumps capable of 120/240V. There is no reason one could not wire up a pump to run either way provided that the switchover included an isolation switch to be sure that it's an "either-or" proposition.

Reader Question: why do we use 12V lights rather than 12V lights in a swimming pool?

(May 21, 2012) nick monte said:

swim pool inground lite - what is the reason for rating pool lights at 12 volts or 120 volts? 12 v is $168.00 vs @324.00. Is it energy cost?

Reply:

Nick, the wiring for 12V is usually smaller, easier to run, less costly; potentially the lower voltage can be less risky.

Reader Comment: 240V common use in Europe saves energy costs on voltage grop

(Aug 21, 2012) Bill said:

In Europe they use 240V to save energy cost on voltage drop. Makes sense, but in US we cannot do so, because our electrical outlets, cords, etc are around Jurassic era! When visiting Europe our kids cannot get zapped from 240V, because their (in civilized part of EU) outlets are 99% kid proof. You cannot push metal pins in the outlet, you need a real electrical plug to open those little safety guards.

Here in US, all you need is screw driver to kill your kid in an outlet. Home Depot sells those tamper proof outlets, but if I have them who says my neighbor does so I could send my kids over.

Another thing I've noticed, our plugs hang down revealing those metal pins going into the plug and all you need is to drop metal pin (ie. hangar) crossways on top to get a big boom. In Europe, by the time you'll see metal, it's already disconnected.

What a shame... Time for an upgrade my fellow citizens!

Be safe,
Bill

Reader comments on volts, watts, & current (amps)

5/4/2014 fred said:

110/115/120/220/230/240/1000000 volts.

Appliances use power- That's it. Power is all that matters.

If an appliance is rated say 1KW, 1000 Watts, then if used on a 120 volt supply it needs 1000/120 (amps). That is 8.33 amps.
Another appliance of 1000 watts fed from a 240 volt system would only need 1000/240 (amps) = 4.166.
A further appliance of 1000 watts fed from a 1000 volt supple would only draw 1000/1000 ( amps) = 1 amp.
The designers will work out what current is needed to give the 1000 watts of power the appliance needs knowing the voltage at the place where it will be used. In the UK it will be 230 v. Here it will most likely be 120 volts for a small appliance that only consumes 1KW.

Anything plugged into the typical 120 volt socket/receptacle here in the US will have a rating in watts. Its quite common to say something is a 6 amp vacuum cleaner or drill or whatever. You can say this because the voltage is fixed at 120 so quoting the current is a way to express power. But really the right way to quote something's power is in Watts or KWatts. K means 1000.

Amps times voltage IS Watts. So anytime the voltage goes up the current will go down for the SAME power.
2 amp at 200 volts is 400 Watts. But 20amps at only 20 volts is also 400 watts. The makers of appliances will work out what current is need to give the power required at 120 volts. They could make an identical appliance but working on 240 volts say and still 400 watts.

You could run something on 240 volts that is not a big load ( takes a lot of current), like a furnace. It does not mean that because you are using a 240 socket that it has to mean a lot of power ( Watts). You might have an electric clock connected to a 240 volt supply, as is common in the UK. It is power rated at only 2 Watts! So the current it uses is 2W/240V = 0.0083 amp ( 8.3 millamps) - not a lot.

Reply:

Thanks, Fred, your recap of amps, volts, watts, and Kwatts will surely help some readers. I'll copy the text into the article above. Use our CONTACT link to send me an email note if you want to be credited by name, contact info &c.

Details about amps, volts, watts and related terms are found at DEFINITIONS of ELECTRICAL TERMS

...


Continue reading at APPLIANCE EFFICIENCY RATINGS or select a topic from closely-related articles below, or see our complete INDEX to RELATED ARTICLES below.

Or see AMPS VOLTS DETERMINATION

Or see DEFINITIONS of ELECTRICAL TERMS

Or see ENERGY SAVINGS IN BUILDINGS - home

Suggested citation for this web page

EFFICIENCY of 120V vs 240V EQUIPMENT at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

INDEX to RELATED ARTICLES: ARTICLE INDEX to ELECTRICAL INSPECTION & TESTING

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia


...

Frequently Asked Questions (FAQs)

Click to Show or Hide FAQs

Ask a Question or Search InspectApedia

Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.

Search the InspectApedia website

HTML Comment Box is loading comments...

Technical Reviewers & References

Click to Show or Hide Citations & References

Publisher's Google+ Page by Daniel Friedman