InspectAPedia.com InspectAPedia®
Google
InspectAPedia
 

Free Encyclopedia of Building & Environmental Inspection, Testing, Diagnosis, Repair

Ask a Question or Search InspectAPedia

  • HOME
  • AIR CONDITIONING
  • ELECTRICAL
  • EXTERIORS
  • HEATING
  • HOME INSPECTION
  • INTERIORS
  • PLUMBING
  • ROOFING
  • SEPTIC SYSTEMS
  • STRUCTURE
  • WATER SUPPLY
  • ENERGY SAVINGS
  • ENVIRONMENT
  • INDOOR AIR IAQ
  • INSULATION
  • MOLD INSPECT TEST REMOVE
  • NOISE
  • ODORS
  • SOLAR ENERGY
  • VENTILATION
  • EXPERTS DIRECTORY
  • CONTACT US



Mobile viewMobile View
OIL STORAGE TANKS

ABANDONING OIL TANKS
ABOVE GROUND OIL TANK INSPECTIONS
AFUE DEFINITION, RATINGS
AGE of OIL TANK
ANODES & DIP TUBES on WATER HEATERS

BIOGAS PRODUCTION & USE
BOILERS, HEATING
BURIED OIL TANK ADVICE
BURIED OIL TANKS, FINDING

COMBUSTION PRODUCTS & IAQ

DEFINITION of Heating & Cooling Terms
DIAGNOSE & FIX HEATING PROBLEMS-BOILER
DIAGNOSE & FIX HEATING PROBLEMS-FURNACE
DIRECT VENTS / SIDE WALL VENTS
DIRECTORY of OIL TANK EXPERTS

FILTERS, OIL on HEATING EQUIPMENT
FIRE SAFETY CONTROLS
FLAME COLOR, BLUE vs YELLOW COMBUSTION
FLOATING UP OIL STORAGE or SEPTIC TANKS
FLOODED HEATING EQUIPMENT REPAIR
FLOODED WATER HEATER REPAIR
FUEL OIL TYPES & CHARACTERISTICS
FUEL UNIT, HEATING OIL PUMPS

GALVANIC SCALE & METAL CORROSION
GAUGES ON HEATING EQUIPMENT

HEAT LOSS in buildings
HEAT TAPES, Heat, Insulation prevent Freeze-Up
HEATING COST FUEL & BTU Cost Table
HEATING COST SAVINGS METHODS
HEATING OIL CLOUD WAX GEL POINT
HEATING OIL EXPOSURE HAZARDS, LIMITS
  Heating Oil Exposure Health Effects
  MSDS Sheet for HOME HEATING OIL
  Exposure Limits for Home Heating Oil
  MSDS Sheet for CRUDE OIL
  MSDS Sheets for OIL DISPERSANTS
HEATING OIL - OLD, USEABLE?
HEATING OIL PIPING TROUBLES
HEATING OIL SHELF LIFE
HEATING OIL SLUDGE
HEATING OIL TANKS
HEATING OIL USAGE RATE
HEATING SYSTEM INSPECT DIAGNOSE REPAIR
HEATING SYSTEM NOISES
HOME BUYERS GUIDE TO OIL TANKS
HOT WATER HEATERS

NO HEAT - BOILER
NO HEAT - FURNACE
NOISE CONTROL for HEATING SYSTEMS
NOISES COMING FROM WATER HEATER

ODORS & SMELLS DIAGNOSIS & CURE
ODORS FROM HEATING SYSTEMS
OIL BURNERS
OIL BURNER FUEL UNIT
OIL BURNER INSPECTION & REPAIR
OIL BURNER NOISE SMOKE ODORS
OIL BURNER NOZZLE & ELECTRODES
OIL BURNERS, RETENTION HEAD
OIL BURNER SOOT & PUFFBACKS
OIL FILTERS on HEATING EQUIPMENT
OIL FILTER MISSING
OIL FUEL TYPES & CHARACTERISTICS
OIL & GAS PIPING
OIL LINE CLOGGING FIX
OIL LINE QUICK STOP VALVES
OIL LINE SAFETY VALVES
OIL ODORS, LEAKY OIL TANK PIPING
OIL PUMP FUEL UNIT
OIL SPILL CLEANUP / PREVENTION
OIL TANKS
OIL TANK ABANDONING PROCEDURE
OIL TANK AGE
OIL TANK, BURIED, ADVICE
OIL TANK, BURIED, FINDING
OIL TANK FAILURE CAUSES
OIL TANK FAILURE RATES
OIL TANK FLOATING UP
OIL TANK GAUGES
OIL TANK INSPECTION, ABOVE GROUND
OIL TANK INSPECTION REPORTS
OIL TANK LEAKS & SMELLS
OIL TANK LEGAL ISSUES
OIL TANK LIFE
OIL TANK PIPING & PIPING DEFECTS
OIL TANK PRESSURE
OIL TANK REGULATIONS
OIL TANK REMOVAL COs
OIL TANK REMOVAL FINANCIAL AID
OIL TANK REPORT LANGUAGE
OIL TANK SAFETY
OIL TANK SLUDGE
OIL TANK STANDARDS
OIL TANK STANDARDS - Detailed List
OIL TANK SPILL CLEANUP / PREVENTION
OIL TANK SUPPORT
OIL TANK TESTING
OIL TANK TESTING COs
OIL TANK WATER CONTAMINATION
OIL TANK WATER REMOVAL

SOOT on OIL FIRED HEATING EQUIPMENT
STAIN DIAGNOSIS on BUILDING INTERIORS

WATER HEATERS

More Information

Photograph of  parts this leaking oil tank

MSDS for Oil Dispersants Exposure Effects, Exposure Limits, Health Hazards
InspectAPedia®  -      

  • Material Safety Data Sheets for Oil Dispersants
  • Gulf Oil Spil Oil Dispersant Selection, Choices, Availability
  • List of EPA-documented oil dispersants
  • MSDS data sheets for oil dispersants
  • Oil Dispersant Alternatives, Toxicity, Environmental Impacts

Crude oil dispersants: this document provides information on the contents of Crude Oil, Home Heating Oil, & other fuel oil material safety data sheets or Heating Oil MSDS.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers nor with topics or services discussed at this website.

See HEATING OIL EXPOSURE HAZARDS, LIMITS for information about possible health hazards from exposure to various forms of oil, crude oil, heavy oil, or home heating oil in liquid or gas (fumes) forms.

Readers should also see OIL TANK SAFETY where we describe the flammability and explosion hazards of fuel oil fumes and where we provide an extensive list of hazards and safety concerns for fuel oil. Also see OIL TANK LEAK ADVICE for our detailed advice on handling leaky oil tanks as well as links to oil tank leak regulations for U.S. states and Canadian provinces. Readers should also see BOILER NOISE SMOKE ODORS for a discussion of flue gas leaks, smells, and hazards from the combustion products of oil burning heating appliances.

© Copyright 2012 InspectAPedia.com, All Rights Reserved. Information Accuracy & Bias Pledge is at below-left. Use page top links to major topics or use links at the left of each page to navigate within topics and documents at this website. Green links show where you are in a document series or at this website.

Crude Oil Dispersant Material Data Safety Sheets - Dispersants Sprayed on Gulf or Injected into Gulf Oil Well Spill: Corexit, Dispersit, Others

Dispersants, used to break up oil spills both on the water surface and deep below the surface are intended to reduce the impact of crude oil spills on the ocean and its sealife.

In an unprecedented quantity of at least 700,000 gallons, Corexit® dispersants, produced by Nalco Energy Services, for example, were sprayed on the water surface or pumped below the surface in the 2010 oil leak catastrophe in the Gulf of Mexico.

According to the U.S. Centers for Disease Control,

Oil spill dispersants break an oil slick into small drops. For most people, brief contact with a small amount of oil spill dispersants will do no harm. However, longer contact can cause a rash and dry skin. Dispersants can also irritate your eyes. Breathing or swallowing dispersants can also cause health effects.

But dispersants themselves are toxic and though diluted by the water into which they are sprayed, may have long term effects on the environment. Although Corexit® product MSDSs include both 2-butoxyethanol and 38% 2-butoxyethanol, (both toxic chemicals) according to the New York Times ("Worry About Dispersant Rises as Men in Work Crew Complain of Health Problems", 28 May 2010), Nalco, the company that produces a series of Corexit dispersant products, has declined to disclose its proprietary chemical formula for these products that incude Corexit 9500, Corexit 9527, and Corexit 9580.

On 20 May 2010, also according to the Times, the U.S. EPA, citing the lack of knowledge of the chemical's impact, directed BP (British Petroleum) to use a less toxic dispersant spray on the Gulf oil spill. At that time the 700,000 gallon Corexit dispersant spray figure was also quoted, making this the largest use ever of chemical dispersants on an oil spill. This article quotes BP spokesman Toby Odone:

“Corexit was an E.P.A.-approved dispersant that had been widely used in the gulf and was available in the quantities we required”

According to a Nalco competitor, U.S. Polychemical who makes a competing dispersant Dispersit SPC 1000® that is water-based rather than oil-based,

"Corexit 9500 can cause central nervous system depression, nausea, and unconsciousness. It can cause liver, kidney damage, and red blood cell hemolysis with repeated or prolonged exposure through inhalation or ingestion according to the MSDS. The threat to human health via exposure is characterized a MODERATE".

BP stated that it continues to believe Corexit EC9500A is best alternative dispersant to use in the Gulf oil spill, indicating that

... this one doesn’t contain chemicals that degrade to nonylphenol (NP). Manufacturer indicates COREXIT reaches maximum biodegradation within 28 days of application. It doesn’t persist in the environment. These features make it a better choice for subsea application based on current information. COREXIT has fewer long-term effects than other dispersants.

According to the BP letter published below, five products on NCP product schedule met the EPA criteria in May 19th directive.

  1. Sea Brat #4 – contains a chemical that will degrade to a nonylphenol (NP) and has been identified as a potential endocrine disruptor and a persistent bioaccumulative toxin.
  2. Nokomis 3-F4
  3. Nokomis 3-AA
  4. Mare Clean 200
  5. Neos AB3000

The May 20 2010 Times article reports that Canadian oil spill expert Merv Fingas considers Corexit not much more toxic than other dispersants that have been in use for a long time. [OPINION: simply equating them to one another, such a comparison does not address the absolute actual toxicity of any or all of those products.]

A separate and important question remains about the actual effectiveness of dispersants in the Gulf oil spill where very large quantities of oil have been spilled a mile below the surface of the water. By the time that oil reaches the surface it has been emulsified (formed an emulsion mix with water) so that dispersants are not effective.

In addition to the MSDS links for Corexit products shown here, we have edited the Complete US EPA Table of Crude Oil Dispersants to add links to individual crude oil dispersant product MSDS in the original US EPA Dispersant list.

  • The MSDS Material Data Safety Sheet For Corexit 9500 crude oil dispersant is here.
  • The MSDS Material Safety Data Sheet for COREXIT® EC9527A crude oil dispersant is here - 2008 PDF document
  • The MSDS Material Data Safety Sheet For Corexit 9527 crude oil dispersant is here - older 1992 version in text format
  • The MSDS Material Data Safety Sheet For Corexit 9580 crude oil dispersant is here.
  • The MSDS Material Data Sheet For Dispersit SPC 1000® oil dispersant. U.S. Polychemical, provides general product description at their website. U.S. Polychemical was kind enough to provide us with the copy of the MSDS for Dispersit® linked-to here.

"May 19, 2010 Addendum 2 to Dispersant Monitoring and Assessment Directive ("Addendum 2")", to Rear Admiral Mary Landry, Commander, Eighth Cost Guard District, New Orleans LA, and Samuel Coleman, P.E., Director, Superfund Division, Dallas TX, from Douglas J. Suggles, B.P. - letter, PDF (U.S. EPA) discusses a comparison of available oil dispersants and the company's basis for choosing Corexit as the dispersant of choice in the circumstances of the Gulf Oil Spill. The letter makes plain that the need for a quick response combined with the availability of Corexit for that choice.

Dispersants Listed by the U.S. EPA with Links to MSDS for Oil Dispersants

Product
(1:10 Product-to-No. 2 Fuel Oil ratio)

Toxicity
(LC50 values in ppm)
Effectiveness (%)
Menidia
(96-hr)
Mysidopsis
(48-hr)
Prudhoe Bay
Crude Oil
South Louisiana
Crude Oil
Average of
Crude Oils
BIODISPERS 5.95 2.66 51.00 63.00 57.00
COREXIT® EC9500A 2.61 3.40 45.30 54.70 50.00
COREXIT® EC9527A 4.49 6.60 37.40 63.40 50.40
DISPERSIT SPC 1000™ 7.90 8.20 40.00 100.00 73.00
FINASOL OSR 52 5.40 2.37 32.50 71.60 52.10
JD-109 3.84 3.51 26.00 91.00 58.50
JD-2000™ [Also see Globemark Test Results] 3.59 2.19 60.40 77.80 69.10
MARE CLEAN 200 (possibly found at http://www.birkocorp.com/Products.html) 42.00 9.84 63.97 84.14 74.06
NEOS AB3000 57.00 25.00 19.70 89.80 54.80
NOKOMIS 3-AA [Data Sheet] 34.22 20.16 63.20 65.70 64.50
NOKOMIS 3-F4 [Data Sheet] 100 58.40 62.20 64.90 63.55
SAF-RON GOLD [EPA letter] 9.25 3.04 84.80 53.80 69.30
SEA BRAT #4 23.00 18.00 53.55 60.65 57.10
SEACARE ECOSPERSE 52 (see FINASOL® OSR 52) 5.40 2.37 32.50 71.60 52.10
SEACARE E.P.A. (see DISPERSIT SPC 1000™) 7.90 8.20 40.00 100.00 73.00
SF-GOLD DISPERSANT (see SAF-RON GOLD) 9.25 3.04 84.80 53.80 69.30
ZI-400 [aircraft cleaner] 8.35 1.77 50.10 89.80 69.90
ZI-400 OIL SPILL DISPERSANT (see ZI-400) 8.35 1.77 50.10 89.80 69.90

Other Dispersants and Oil Spill Remediation Products MSDS Sheets

  • Accepta 3549, oil spill dispersant for use at sea, on sand/pebble beaches, produced by Accepta, Ltd., U.K.
  • AgroRemed®, Sarva Bio Remed, LLC 11 N. Willow St., Trenton, NJ
  • Dispersant Solution, Sodium hexameaphosphate, OFI Testing Equipment, Inc., Houston TX
  • Dispersant Solution, 92-2285, A.B. Dick, Niles IL

 

MSDS Data for Corexit 9527

The MSDS for Corexit 9527, a dispersant developed by Nalco Energy Services in the 1980s, and widely used in the Gulf, includes 2-butoxyethanol and 38% 2-butoxyethanol. A question remains about whether the proprietary formula also includes ethylene oxide (a carcinogen), reported by valdezlink.com to have been in a 1989 version.

EXXON CHEMICAL AMERICAS DIV EX -- COREXIT 9527                                 
=======================================================
MSDS Safety Information 
=======================================================
FSC: 6850
MSDS Date: 06/14/1992
MSDS Num: BRYBG
LIIN: 00F030320
Product ID: COREXIT 9527
MFN: 01
Responsible Party
Cage: 72190
Name: EXXON CHEMICAL AMERICAS DIV EXXON CORP
Box: 3272
City: HOUSTON TX 77001
Info Phone Number: 713-870-6000
Emergency Phone Number: 713-870-6000
Review Ind: Y
Published: Y
=======================================================
Preparer Co. when other than Responsible Party Co. 
=======================================================
Cage: 72190
Name: EXXONMOBIL CHEMICAL CO, DIV OF EXXON MOBILCORP.
Address: 13501 KATY FWY
Box: 3272
City: HOUSTON TX 77253-3272
=======================================================
Contractor Summary 
=======================================================
Cage: 72190
Name: EXXONMOBIL CHEMICAL CO, DIV OF EXXON MOBILCORP.
Address: 13501 KATY FWY
Box: 3272
City: HOUSTON TX 77253-3272
Phone: 281-870-6000 / 800-726-2015
=======================================================
Ingredients 
=======================================================
Cas: 111-76-2
RTECS #: KJ8575000
Name: 2-BUTOXYETHANOL (ETHYLENEGLYCOL MONOBUTYL ETHER), BUTYL CELLOSOLVE, BUTYL
  GLYCOL, GLYCOL ETHER EB
% Wt: 38
Other REC Limits: 25 PPM (SKIN)
OSHA PEL: S, 50 PPM
ACGIH TLV: S, 25 PPM; 9293
=======================================================
Health Hazards Data 
=======================================================
Route Of Entry Inds - Inhalation: YES
Skin: YES
Ingestion: YES
Carcinogenicity Inds - NTP: NO
IARC: NO
OSHA: NO
Effects of Exposure: EYES: IRRITATING, MAY INJURE TISSUE IF NOT REMOVED
  PROMPTLY. SKIN: IRRITATING. ABSORPTION MAY CAUSE HEMOLYTIC ANEMIA &
  KIDNEY DAMAGE EVIDENCED BY PALENESS & RED COLORATION OF URINE.
  INHALATION: RESPIR ATORY TRACT IRRITATION. SYSTEMIC EFFECTS. INGESTION: LOW
  TOXICITY. INHALATION/SKIN OVEREXPOSURE: BLOOD/KIDNEY DAMAGE.
Explanation Of Carcinogenicity: NONE
First Aid: EYES: FLUSH W/PLENTY OF WATER FOR AT LEAST 15 MINS. SKIN: FLUSH
  W/PLENTY OF WATER. USE SOAP IF AVAILABLE. REMOVE CONTAMINATED CLOTHING,
  INCLUDING SHOES, AFTER FLUSHING HAS BEGUN. INHALATION: REMOVE TO  FRESH AIR.
  ADMINISTER ARTIFICIAL RESPIRATION IF BREATHING IS STOPPED. KEEP AT REST.
  INGESTION: INDUCE VOMITING. DON'T ATTEMPT TO GIVE ANYTHING BY MOUTH TO AN
  UNCONSCIOUS PERSON. OBTAIN MED ATTN.
=======================================================
Handling and Disposal
=======================================================
Spill Release Procedures: ELIMINATE IGNITION SOURCES. SMALL/LARGE SPILL:
  IMPLEMENT CLEANUP PROCECURES. FOR LARGE IF IN PUBLIC AREA, EVACUATE AREA.
  CONTAIN LIQUID W/SAND/EARTH. DON'T USE COMBUSTIBLES. RECOVER BY PUMPING
  (EXPLOS ION PROOF/HAND PUMP) OR W/A SUITABLE ABSORBENT.
Waste Disposal Methods: DISPOSE OF IN ACCORDANCE W/LOCAL, STATE, & FEDERAL
  REGULATIONS. PREVENT LIQUID FROM ENTERING SEWERS, WATERCOURSES OR LOW AREAS.
  COMPLETELY DRAIN, PROPERLY BUNG & PROMPTLY RETURN EMPTY DRUMS TO A DRUM 
  RECONDITIONER OR PROPERLY DISPOSED OF. NA 1993
Other Precautions: EMPTY CONTAINERS RETAIN RESIDUE & CAN BE DANGEROUS.
  DON'T PRESSURIZE/CUT/WELD/BRAZE/SOLDER/DRILL/GRIND/EXPOSE SUCH CONTAINERS TO
  HEAT/FLAME/SPARKS/ELECRICITY/OTHER IGNITION SOURCES; THEY MAY EXPLODE & 
  CAUSE INJURY OR DEATH.
=======================================================
Fire and Explosion Hazard Information 
=======================================================
Flash Point Method: TCC
Flash Point Text: 163F
Lower Limits: 1.1%
Upper Limits: 10.6%
Extinguishing Media: ALCOHOL TYPE FOAM, DRY CHEMICAL OR WATER SPRAY
Fire Fighting Procedures: USE WATER SPRAY TO COOL FIRE EXPOSED SURFACES &
  TO PROTECT PERSONNEL. ISOLATE FUEL SUPPLY FROM FIRE. AVOID SPRAYING WATER
  DIRECTLY INTO STORAGE CONTAINERS.
Unusual Fire/Explosion Hazard: COMBUSTIBLE LIQUID, CAN FORM COMBUSTIBLE
  MIXTURES AT TEMPS AT OR ABOVE THE FLASHPOINT.
=======================================================
Control Measures 
=======================================================
Respiratory Protection: IF THE TLV HAS BEEN EXCEEDED, USE A NIOSH/MSHA APPROVED
  RESPIRATOR.
Ventilation: LOCAL EXHAUST. STORE & HANDLE LABORATORY SAMPLES IN A LAB
  HOOD. PROVIDE MECHANICAL VENTILATION IN CONFINED AREAS.
Protective Gloves: CHEMICAL RESISTANT
Eye Protection: CHEMICAL SAFETY GOGGLES W/FACE SHIELD
Other Protective Equipment: CHEMICAL SUIT, RUBBER BOOTS, LONG SLEEVE CLOTHING.
=======================================================
Physical/Chemical Properties 
=======================================================
B.P. Text: 340F
M.P/F.P Text: -45F
Vapor Pres: 5
Spec Gravity: 1
Evaporation Rate & Reference: (N-BU AC = 1): 0.1
Solubility in Water: COMPLETE
Appearance and Odor: AMBER LIQUID W/GLYCOL ETHER ODOR.
=======================================================
Reactivity Data 
=======================================================
Stability Indicator: YES
Stability Condition To Avoid: HEAT, FLAME, SPARKS, STATIC ELECTRICITY OR OTHER
  SOURCES OF IGNITION.
Materials To Avoid: STRONG OXIDIZING AGENTS
Hazardous Decomposition Products: SMOKE FUMES, CO, CO2
Hazardous Polymerization Indicator: NO
=======================================================
Toxicological Information 
=======================================================
=======================================================
Ecological Information 
=======================================================
=======================================================
MSDS Transport Information 
=======================================================
=======================================================
Regulatory Information 
=======================================================
=======================================================
Other Information 
=======================================================
=======================================================
HAZCOM Label 
=======================================================
Product ID: COREXIT 9527
Cage: 72190
Company Name: EXXONMOBIL CHEMICAL CO, DIV OF EXXON MOBILCORP.
Street: 13501 KATY FWY
PO Box: 3272
City: HOUSTON TX
Zipcode: 77253-3272
Health Emergency Phone: 713-870-6000
Label Required IND: Y
Date Of Label Review: 09/30/1993
Status Code: C
Label Date: 09/30/1993
Origination Code: F
Chronic Hazard IND: Y
Eye Protection IND: YES
Skin Protection IND: YES
Signal Word: DANGER
Respiratory Protection IND: YES
Health Hazard: Severe
Contact Hazard: Severe
Fire Hazard: Moderate
Reactivity Hazard: Slight
Hazard And Precautions: EYES: IRRITATING, MAY INJURE TISSUE IF NOT REMOVED
  PROMPTLY. SKIN: IRRITATING. ABSORPTION MAY CAUSE HEMOLYTIC ANEMIA &
  KIDNEY DAMAGE EVIDENCED BY PALENESS & RED COLORATION OF URINE.
  INHALATION: RESPIR ATORY TRACT IRRITATION. SYSTEMIC EFFECTS. INGESTION: LOW
  TOXICITY. INHALATION/SKIN OVEREXPOSURE: BLOOD/KIDNEY DAMAGE. TARGET ORGANS:
  EYES, SKIN, KIDNEYS, RESPIRATORY TRACT, BLOOD.		    T ARGET
  ORGANS: EYES, SKIN, LIVER, KIDNEYS, RESPIRATORY & DIGESTIVE TRACTS,
  HEART.
=======================================================
Disclaimer (provided with this information by the compiling agencies): This
  information is formulated for use by elements of the Department of Defense.
  The United States of America in no manner whatsoever expressly or implied
  warrants, states, or intends said information to have any application, use or
  viability by or to any person or persons outside the Department of Defense
  nor any person or persons contracting with any instrumentality of the United
  States of America and disclaims all liability for such use. Any person
  utilizing this instruction who is not a military or civilian employee of the
  United States of America should seek competent professional advice to verify
  and assume responsibility for the suitability of this information to their
  particular situation regardless of similarity to a corresponding Department
  of Defense or other government situation.
 

Questions & Answers regarding this article

.

Ask a Question or Search InspectAPedia

HTML Comment Box is loading comments...

Recommend / Share this Article            

...

Technical Reviewers & References

  • InspectAPedia.com® - Daniel Friedman - Publisher & Editor.
  • InspectAPedia Bookstore lists recommended books, organized by topic & available for purchase. Most of our articles also include a list of recommended books for the specific article topic as well as other references, and information sources.
  • Critique, contributions wanted: Contact Us to suggest corrections or additions to articles at this website, and if you wish, to receive online listing and credit as a contributor. Particular thanks are due to the many experts and also consumers who read and critique technical articles at InspectAPedia.com.
  • Additional technical contributors & reference sources for this article are listed below.

Use links just below or at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website.

HEATING OIL EXPOSURE HAZARDS, LIMITS
  Heating Oil Exposure Health Effects
  MSDS Sheet for HOME HEATING OIL
  Exposure Limits for Home Heating Oil
  MSDS Sheet for CRUDE OIL
  MSDS Sheets for OIL DISPERSANTS

Also see CHIMNEY INSPECTION & REPAIR GUIDE for details of chimney inspection, diagnosis, and repair, including blocked chimney flues, chimney backdrafting, leaks, and odors from flues.

Separately we discuss CARBON MONOXIDE hazards in buildings. Readers concerned with LP gas or natural gas combustion flue gas products and hazards should also see Natural Gas Combustion Products and also LP & Natural Gas Safety Hazards.

  • "Toxicological profile for fuel oils", U.S. Department of Health and Human Services, Public Health Service, Agency for Toxic Substances and Disease Registry (ATSDR) Atlanta, GA 1995. - http://www.atsdr.cdc.gov/toxprofiles/tp75.html
  • Public Health Statement for Fuel Oils, ATSDR, (the full document original source can be found at http://www.atsdr.cdc.gov/toxprofiles/phs75.html). An excerpt from this document is just below. ATSDR,
    Division of Toxicology, 1600 Clifton Road NE, Mailstop F-32, Atlanta, GA 30333 888-422-8737.
  • Heating Oil Exposure Health Effects - The ATSDR section on health effects of exposure to heating oil see-ATSDR
  • No. 2 Home Heating Oil Chemical Properties - ATSDR data on the chemistry and composition of No. 2 home heating oil and of kerosene
  • Potential for Human Exposure to Heating Oil - ATSDR
  • Regulations and Advisories Pertaining to Fuel Oil - ATSDR data on how exposure limits for heating oil were derived, a table of international and national (U.S.) regulations governing fuel oil,
  • Home Heating Oil Spills, Fact Sheet, Connecticut Department of Public Health
  • "Home Heating Oil Spills", Wisconsin Department of Health, at http://dhs.wisconsin.gov/eh/Air/fs/Oilspill.htm
  • Occupational Exposures in Petroleum Refining; Crude Oil and Major Petroleum Fuels, IARC - World Health Organization, 1/21/1998. This monograph is available at http://monographs.iarc.fr/ENG/Monographs/vol45/volume45.pdf and it includes a chapter
    FUEL OILS (HEATING OILS) Residual (heavy) fuel oils (Group 2B) and Distillate (light) fuel oils (Group 3) that describes heating oil exposure data, concluding "Residual (heavy) fuel oils are possibly carcinogenic to humans (Group 2B)." To search the IARC monographs on various environmental concerns and carcinogens, use http://monographs.iarc.fr/ENG/Monographs/PDFs/index.php
  • "MSDS for No. 2 Fuel Oil - home heating oil", Hess Corporation, 1 Hess Plaza, Woodbridge, NJ 07095-0961 Original Source: www.hess.com/ehs/msds/0088No2FuelOil.pdf 07/01/2007
  • "MSDS for No. 4 Fuel Oil - home heating oil", Hess Corporation, 1 Hess Plaza, Woodbridge, NJ 07095-0961 Original Source: www.hess.com/ehs/msds/0088No2FuelOil.pdf 07/01/2007
  • Crude Oil MSDS from Martin Marietta Materials Corp., November 2007, Martin Marietta Materials, 2710 Wycliff Road, Raleigh, North Carolina 27607-3033 Effective Date: 8-07 (919) 781-4550, original source: http://www.martinmarietta.com/products/MSDS-CrudeOil.pdf
  • MSDS for Crude Oil, El Paso Corporation, and its subsidiaries Information: (713) 420-2600
    1001 Louisiana Street CHEMTREC: (800) 424-9300 Houston, Texas 77002, original source 4/230/10 http://www.elpaso.com/msds/A0017-Crude%20Oil.pdf
  • MSDS for Corexit 9527, - Web Search 06/13/2010 original source - http://www.valdezlink.com/inipol/pages/corexit9527_6-14-92.htm and http://www.valdezlink.com/corexit.htm
  • MRL - Minimum risk level: this is an estimate of the level of daily human exposure to a substance such that the exposure is probably not an appreciable risk for adverse effects (noncancer) over a specified exposure time period.
  • "Worry About Dispersant Rises as Men in Work Crew Complain of Health Problems", The New York Times, 28 May 2010, p. A15.
  • "Agency Orders Use of a Less Toxic Chemical in Gulf", Campbell Robertson, Elisabeth Rosenthal, The New York Times, May 20, 2010, http://www.nytimes.com/2010/05/21/science/earth/21disperse.html?scp=1&sq=corexit&st=cse
  • "May 19, 2010 Addendum 2 to Dispersant Monitoring and Assessment Directive ("Addendum 2")", to Rear Admiral Mary Landry, Commander, Eighth Cost Guard District, New Orleans LA, and Samuel Coleman, P.E., Director, Superfund Division, Dallas TX, from Douglas J. Suggles - letter - Web Search 06/13/2010, original source: U.S. EPA http://www.epa.gov/bpspill/dispersants/5-21bp-response.pdf
  • Nalco Energy Services, L.P. P.O. Box 87, Sugar Land, Texas 77487-0087, 281)263-7000, www.nalco.com
  • U.S. Centers for Disease Control and Prevention - US CDC, "What to Expect from the Oil Spill and How to Protect Your Health", web search 17 June 2010 - original source http://emergency.cdc.gov/gulfoilspill2010/what_to_expect.asp
  • U.S. EPA - environmental Protection Agency, List of Approved Oil Dispersants - Web Search 06/13/2010 - original source http://www.epa.gov/oem/content/ncp/tox_tables.htm
  • U.S. Polychemical of Spring Valley, N.Y., makes dispersant Dispersit SPC 1000 - Web Search 06/13/2010: Dispersant SPC 1000 specifications sheet - see http://www.uspoly.com/disspec.html - Quoting:

Polychem Dispersit SPC 1000 is an EPA reviewed, NCP listed water based dispersant to be used on oil discharges or oil spills in accordance with the procedures set forth by the U.S. Coast Guard and other governmental agencies. Polychem Dispersit SPC 1000 has been included in the NCP Product Schedule for use as a dispersant for oil spills.
Polychem Dispersit SPC 1000 is a unique aqueous composition with highly effective emulsifiers, dispersants and a water-soluble coupling solvent. Polychem Dispersit SPC 1000 contains no petroleum solvents. Independent testing (J L Ross Env. Ltd.) confirmed that Dispersit has significant effectiveness in fresh and brackish water. Dispersit is particularly well suited for application via a vessel based education system because it maintains effectiveness when diluted with water unlike petroleum based products.
Polychem Dispersit SPC 1000 has an overall effectiveness† of 73%, almost 50% better than the EPA requirement and the dominant product and has considerably less aquatic toxicity†† than the dominant petroleum based dispersant. Polychem Dispersit SPC 1000 contains no hazardous material and hence is user-friendly and environmentally safe.

U.S. Polychemical description of their product, Dispersit, includes an assessment of comparative health risks of water-based vesus oil-based oil dispersants: see http://www.uspoly.com/dispersit.html

  • "California Dispersant Plan and Federal On-Scene Coordinator (FOSC) Checklist for California Federal Offshore Waters", Fall 2008, - Web Search 06/13/2010, original source: nrm.dfg.ca.gov/FileHandler.ashx?DocumentID=15889
  • "National Oil and Hazardous Substances Pollution Contingency Plan (NCP) Product Schedule", U.S. EPA NCP Product Schedule Manager U.S. Environmental Protection Agency Office of Emergency Management (OEM) Regulation and Policy Development Division Ariel Rios Building 1200 Pennsylvania Avenue, NW (Room 6450EE, Mail Code 5104A) Washington, DC 20460 - Web Search 06/13/2010 - original source: http://www.epa.gov/oem/docs/oil/ncp/notebook.pdf. This document lists products suc as dispersants, surface washing agents, surface collecting agents, bioremediation agents, and miscellaneous oil spill control agents to be used for oil spills. Guidance and information include a lengthy list of products, their producers, contact information, and application information.

Books & Articles on Building & Environmental Inspection, Testing, Diagnosis, & Repair

  • Our recommended books about building & mechanical systems design, inspection, problem diagnosis, and repair, and about indoor environment and IAQ testing, diagnosis, and cleanup are at the InspectAPedia Bookstore. Also see our Book Reviews - InspectAPedia.
  • ...

Home About Us Accuracy Contact Us Content Use Policy Printing Tips Privacy Website Description © 2012 Copyright InspectAPedia.com