InspectAPedia®

Watts Series 9DM2, 9DM3 Dual Check Valve with atmospheric vent - Heating boiler backflow preventer valve installtaion position (C) InspectApedia adapted from Watts RP/IS-9D Backflow Preventer Valves for Heating Boilers
BBFP requirements, functions, installation, leaks, troubleshooting

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.


Heating boiler backflow preventer valves (BBFP): this article describes check valves installed on the water supply to heating boilers to prevent heating system water from re-entering the building potable water supply system and its piping.

Backflow preventers are installed on hot water (hydronic) or steam boilers on the boiler water feed line as required by both good plumbing practice and by building codes in many jurisdictions.

This article describes backflow preventers used on heating boilers including their function, location or placement, and their troubleshooting and repair of leaks or other problems.

We also provide a MASTER INDEX to this topic, or you can try the page top or bottom SEARCH BOX as a quick way to find information you need.



Green links show where you are. © Copyright 2017 InspectApedia.com, All Rights Reserved.

Heating Boiler Backflow Preventer Valves [BBPF] on Heating System Piping - A Different Check Valve

Automatic water feeder for hot water boilerHeating system backflow preventer valves protect public water mains as well as private building water piping from heating system water contaminants.

At a hot water heating system a heating system backflow preventer check valve is used to keep hot, high pressure water in the hydronic heating system from flowing backwards through a boiler water feed line into the building water supply - a sanitation concern.

[Click to enlarge any image]

Why do we need a Backflow Prevention Device on Heating Boilers?

Because a building potable water supply piping cold water line is used to deliver water to hydronic or steam heating boilers, we need to prevent heating system water from back-contaminating the building water supply piping. This back-contamination, or back-flow could occur, for example, if there were a loss of water pressure on the building supply-side of the heating boiler. In that condition, the boiler water, typically at 12-30 psi depending on boiler temperature, could be forced back into the building's potable water piping system, contaminating it with boiler chemicals or debris, even bacteria.

At our hot water heating boiler backflow preventer photo (above left) the automatic water feed valve (red arrow) includes a built-in backflow prevention device, while a separate, code-required backflow preventer valve is shown by the green arrow.

Our photo at below shows a similar backflow preventer valve (green arrow) installed at a steam heating boiler. Again you'll see that the valve is installed between the potable water supply piping and all other boiler controls and components. Click to see this close-up photo of this backflow preventer on a steam boiler.

Conbraco backflow preventer check valve installed at a steam boiler (C) Daniel Friedman

More generally connection of potable water piping to any device that could potentially send unsanitary water backwards into the potable water system is called a cross connection - a potential drinking water sanitation issue explained in detail at CROSS CONNECTIONS, PLUMBING.

So we install a backflow preventer - a special check valve - at the heating boiler.

Separately from the backflow preventer valve shown in the photos above, at both hot water (hydronic) heating boilers and steam heating systems a backflow preventer may also have been built into the automatic water feed valve itself - a separate control described in our article on WATER FEEDER VALVE, HYDRONIC BOILER in that article's section at BACKFLOW PREVENTER, HEATER WATER FEEDER.

Depending on local plumbing codes, a separate (from the water feeder valve) dedicated backflow preventer valve may also be installed "upstream" of the automatic water feeder - that is, between the heating system water feed valve and the incoming municipal water supply cold water piping (green arrow).

Backflow preventer (C) Daniel Friedman

A close up of the separate heating backflow preventer is shown in a second photograph at left.

These are two separate devices for heating system water backflow prevention, but often you will see both of them installed.


The blue arrow in our photograph shows the direction of water flow into the water feeder and onwards into the heating boiler.

In sum, backflow preventers found on heating systems are installed to prevent higher-pressure heating system water from being forced backwards (say through a water feeder valve) into the building potable water supply piping.

Details about automatic water feeders used on heating boilers or steam boilers are at WATER FEEDER Valves, Hydronic and WATER FEEDER VALVE, STEAM.

Backflow Preventer Valve Installation Position on Heating Systems

The backflow preventer valve such as the Watts 9D Dual Check valve can be installed either horizontally or vertically on the building water supply piping, but it should be positioned at the heating boiler before (on the supply side) the pressure regulator and as you will note in our photos below, it is also ahead of the expansion tank.

Conbraco backflow preventer on a residential heating boiler (C) Daniel Friedman

[Click to enlarge any image.]

Shown above and below: a Conbraco™ Series 40-400 continuous pressure backflow preventer installed at a residential heating boiler. The company's catalog describes this product as follows:

Cobraco backflow preventer (C) Daniel Friedman

The Conbraco Series 40-400 Continuous Pressure Backflow Preventer is designed to protect residential and commercial water supply lines from back-siphonage or back-pressure of non-potable (non-hazardous) substances. It has an intermediate atmospheric vent to insure protection from backflow conditions. It consists of two independently acting and spring-loaded check valves in a corrosion resistant material.

During normal flow operation, the vent valve is closed, and the two check valves are open allowing flow of water through the unit. Each check valve is designed to hold at least 1 psi in the direction of flow. When a back-siphonage condition occurs, both check valves close and the atmospheric vent opens to permit air to enter the intermediate zone. In the event of back-pressure and if the second check valve is prevented from closing tightly, leakage will be vented to the atmosphere through the vent port. - Conbraco™ cited below.

Reader Question: in what order should the backflow preventer be installed?

(Mar 17, 2013) DW said: I am in New York city where a check valve or back flow preventer (3/4 BBFP) [Boiler Back Flow Preventer] is required for domestic heating systems. I have a indirect hot water tank attached to a gas boiler. My question is - What order should the back flow preventer be installed in A or B. We have had no problems but neighbors with the same set up have had a lot of leaks from the check valve

A. city water>BBFP>expansion tank>hot water tank

or

B. city water>expansion tank>BBFP>hot water tank

Note: BBFP Dual Check Valves with Intermediate Atmospheric Vent prevent the reverse flow of hot or cold polluted water from entering into the potable water supply. It consists of a brass body with stainless steel internal parts, integral strainer, and two durable, tight-sealing, rubber check valves.

Designed for continuous pressure, non-health hazard applications in smaller supply lines, such as laboratory equipment, processing tanks, sterilizers, dairy equipment, and specifically for boiler feed lines. Minimum Working Pressure: 25psi (172kPa), Maximum Working Pressure: 175psi (12.06 bar)

Reply:

Above at DW's question we include photographs of Conbraco™ backflow preventer check valve installed at a residential heating boiler. You'll see that the back-flow preventer is installed on the building potable water supply piping ahead of the pressure reducer/regulator valve and ahead of the expansion tank. This is the proper location.

Watts Series 9DM2, 9DM3 Dual Check Valve with atmospheric vent - Heating boiler backflow preventer valve installtaion position (C) InspectApedia adapted from Watts RP/IS-9D

Thanks for the question DW, above I have included an adapted schematic provided by Watts corporation showing the installation position of the 9D Dual Check Valve with an atmospheric vent (above left) . The BBFP you cite probably refers to Watts BBFP, 3/4" CxC Backflow Preventer Watts 0063193 which is a similar device shown below.

Watts BBFP backflow preventer valve (C) Watts Corporation adapted by InspectAPedia

In the backflow preventer valve photo at left our blue arrow shows the direction of incoming water from the potable water supply and the small yellow arrow at the discharge port shows where water may be vented by the valve in normal operation.

Watts describes that BBFP backflow preventer as follows:

BBFP Dual Check Valves with Intermediate Atmospheric Vent prevent the reverse flow of hot or cold polluted water from entering into the potable water supply. It consists of a brass body with stainless steel internal parts, integral strainer, and two durable, tight-sealing, rubber check valves. Designed for continuous pressure, non-health hazard applications in smaller supply lines, such as laboratory equipment, processing tanks, sterilizers, dairy equipment, and specifically for boiler feed lines. Minimum Working Pressure: 25psi (172kPa), Maximum Working Pressure: 175psi (12.06 bar) - Watts

I'm doubtful that I have the whole picture of the building piping and requirements you describe but it seems to me that if you have a back flow preventer valve BETWEEN a heating appliance and its related expansion tank, you've defeated the purpose of the expansion tank - it's as if you eliminated it from the system. The result could be relief valve leaks etc.

The backflow preventer should be installed on the fresh water feed line before any pressure regulators.

Expansion tanks on the system will be on the building side of all of that equipment.

Strainers to Protect the Backflow Preventer Valve From Debris

In some plumbing jurisdictions such as in Australia and New Zealand, Watts' description of the proper installation of the company's double check valve assembly (required by building codes) includes the following advice for installation of a strainer to reduce the chances of debris entering the check valve assembly. Debris can cause the assembly check valve ports to stick open, leading to valve failure to protect against backflow for the Series 719, or debris may cause leaks at the atmospheric vent opening on the Series 9 check valves.

For Australia and New Zealand: Pipeline strainers should be installed between the upstream shutoff valve and the inlet of the backflow preventer. - Watts

To avoid debris-clogging or interference with the operation of a backflow preventer, the supply piping should be flushed of any debris, solder, flux, pipe chips etc. before the valve is installed. In addition, the valve's strainer should be cleaned "... every six months or as conditions require" - Watts.

References for heating boiler backflow preventer valve installation

Backflow Preventer Valve Troubleshooting: Leaks

Conbraco backflow preventer check valve installed at a steam boiler (C) Daniel Friedman

Reader Question: diagnosing leaks at the backflow preventer valve

Edward Martin said:

Could a defective automatic water feeder valve cause backflow preventer valve to leak at the Vent side of the "T"

Reply: causes of leaks at inline check valves

Edward,

Some discharge from a backflow preventer is normal, such as if water pressure on the supply side falls to atmospheric pressure. Water discharge is also expected at heating system start-up (when pressure increases) in a new valve installation, until the valve seat parts have sealed.

But otherwise, the following leaks at the backflow preventer valve vent are not normal and need attention:

Periodic discharge from the backflow preventer, showing up at its vent tube, can be caused by a water hammer problem in the building. Supply pressure fluctuations on the building supply side of the check valve can also cause leaks or discharge. To diagnose water hammer troubles see

WATER HAMMER NOISE DIAGNOSE & CURE

If the backflow preventer is dripping constantly there is probably dirt on its moving check valve parts (internally) - a condition that can be corrected by cleaning the valve or by replacing it.

Also check that your backflow preventer is properly installed and located - on the fresh water feed line but *before* the pressure regulator.

Backflow Preventer Check Valve Repair Kits

'Repair kits for backflow preventer valves can replace valve seats or parts that are responsible for leaks. Check with the valve manufacturer. For example Watts provides repair kits for their backflow prevention products - at www.watts.com . You will need to know the part number found on the label attached to your backflow preventer.

...


Continue reading at CHECK VALVES, HEATING SYSTEM or select a topic from closely-related articles below, or see our complete INDEX to RELATED ARTICLES below.

Or see ANTIFREEZE for BOILERS

Or see CHEMICAL TREATMENTS, BOILER

Or see CHECK VALVE FAQs

Or see Or see PROPYLENE GLYCOL DETECTION & POISONING SYMPTOMS

Suggested citation for this web page

BACKFLOW PREVENTER VALVE, HEATING SYS at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

INDEX to RELATED ARTICLES: ARTICLE INDEX to HEATING SYSTEMS

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia


...

Frequently Asked Questions (FAQs)

Click to Show or Hide FAQs

Ask a Question or Search InspectApedia

Use the "Click to Show or Hide FAQs" link just above to see recently-posted questions, comments, replies, try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.

Search the InspectApedia website

Comment Box is loading comments...

Technical Reviewers & References

Click to Show or Hide Citations & References

Publisher's Google+ Page by Daniel Friedman