This article describes electric meter bases of the Zinsco design made by GTE / Sylvania / Zinsco and by Kearney.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
This website discusses the electrical, fire, and shock hazards associated with Zinsco electrical components, circuit breakers, electrical panels, including certain Sylvania electrical panels and breakers which are in fact of the same product design and origin.
Above, courtesy of Judd Stiff, we include photographs of a Zinsco-Sylvania electric meter base. At the right of our left-most photo (above left) you can see the interior of the Zinsco main service disconnect switches.
At our closeup (above right) you can see that the electric meter connections have overheated and look burned.
Below is a close-up photograph of connections in a Kearney electrical meter base.
Contact Us with field reports and photos. We are pleased to credit and link-to contributors.
Current Kearney National concerns and related companies:
Kearney National, Inc., 565 Fifth Ave. (4th Floor), New York NY 10017-2143, Tel: 212-661-4600, website: x
Quoting: Kearney-National Inc. manufactures and distributes electrical power distribution products. Its manufactures electronic-parts and electronic switches. Kearney-National Inc. was incorporated in 1963 and is based in New York, New York. [4]
Kearney-National, Inc., 200 Park Ave, New York, NY 10166 Tel: 212-972-9590
National Metering Services in Kearney NJ, National Metering Services Corporate Offices and Certified Meter Testing Facility 163 Schuyler Avenue Box 491, Kearny, New Jersey 07032 Toll Free: 1-888-448-0009 Phone: 201-246-1115 Fax: 201-246-1831, quoting: Business Process Consultancy, Test and Measurement Instrumentation, Database Management, Leak Detection Sprays, Project Planning Consultancy available from National Metering Services based in Kearny, NJ. [6]
Millbank Residential Meter Sockets, Milbank Manufacturing Co. PO Box 419028 Kansas City, MO 64141-6028, Tel: 877-483-5314 [reader suggested that Millbank purchased Kearney): quoting: Milbank residential meter sockets can be installed on homes with light load current requirements of 100 amps, up to the demanding requirements of the largest homes requiring single 320 amp meter sockets or multiple meter sockets feeding multiple service panels.[7]
Patent litigation involving Kearney National gives an interesting insight into a small piece of the company's history. See Helen Wills Strong and Kearney-National, Inc., Plaintiffs-Appellants, v.General Electric Company, Defendant-Appellee., 434 F.2d 1042 (5th Cir. 1971) [3]
Below you will find questions and answers previously posted on this page at its page bottom reader comment box.
On 2020-07-04 by (mod) - Sylvania Zinsco Main Switch in 1977 Sylvania Meter Base MT12MBB
Sean
Unfortunately, yes, that's a Zinsco-Sylvania panel design. Notice those two vertical strips that connect to two deep slots in the circuit breaker?
That identifies this as a Zinsco design. Above I post a closer-view excerpted from your photo. There we show the key identifcation points to confirm the Zinsco breaker design.
On 2020-07-04 by SeanN - I don't think this is the bad Zinsco panel - is that right?
Thank you for all the information - I don't think this is a Zinsco panel, but would you be able to confirm?
Model# is MT12MBB and House was built in 1977 in San Mateo County, California, USA.
I'm looking to upgrade to 200A with solar system in future but trying to decide if I should replace it now if it's unsafe.
Please see attached - Thanks!
Sean
This Q&A were posted originally at IDENTIFY GTE SYLVANIA-ZINSCO PANELS
Sir, is Kearney electrical panels still in business, i need a repair part for a meter base, i can not get any info on the co. Thanks for any help, Don
Don, I did not find a source of Kearney meter base replacement parts, though there are plenty of similar part suppliers whom you can find online by searching for "replacement electric meter base".
You might want to give Millbank a call and discuss the model and type of meter base you need - reader below indicated that Millbank purchase Kearney (let us know what you're told)
Millbank Residential Meter Sockets, Milbank Manufacturing Co. PO Box 419028 Kansas City, MO 64141-6028, Tel: 877-483-5314, website: http://www.milbankmfg.com/
I also found three Kearney National concerns and provide their contact information in our references section below - see citations # [4][5][6] in case you want to give the current going concerns a call.
...
Continue reading at OK to USE ZINSCOS? or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see this
IDENTIFY ZINSCO SYLVANIA METER BASE at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.
Search the InspectApedia website
Note: appearance of your Comment below may be delayed: if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.
Only one image can be added per comment but you can post as many comments, and therefore images, as you like.