InspectAPedia®   -   Search InspectApedia

Photograph of  cooling system condensate leaks onto heat exchanger Air Conditioning / Heat Pump Condensate Drip Trays, Defects, Repairs

  • POST a QUESTION or COMMENT about air conditioner and heat pump condensate drip trays, overflow pans, and safety switches, controls, and drains

Condensate drip trays:

This air conditioning repair article discusses the inspection and repair of air conditioning condensate systems, including Air Conditioning Condensate Drip Trays, Defects, and Leaks.

Condensate overflow or drip tray leaks, piping, and float switches can shut down an air conditioner or heat pump.

These leaks can also damage the building, even causing costly mold contamination. A/C or heat pump condensate leak health and safety concerns are also reviewed.

This article is part of our series of diagnostic & repair articles for cooling system condensate piping, traps, drains, condensate pumps, and the detection and hazards of air conditioning system condensate leaks in buildings.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

Air Conditioning or Heat Pump Condensate Drip Tray or Condensate Overflow Pan Installation, Inspection, & Diagnosis

Photograph of  cooling system condensate leaks onto heat exchangerArticle Contents

Using an Auxiliary Condensate Drain Line from an Attic Cooling Coil Condensate Overflow Pan

As Carson Dunlop Associates ' sketch (left) illustrates, one method of insuring against building damage due to a clogged A/C condensate disposal line is the installation of a second, auxiliary drain line to empty the condensate overflow pan that should be installed beneath the indoor cooling unit

[Click to enlarge any image]

When an air conditioning unit is located in an attic where damage may result from air conditioning system condensate overflow from the primary condensate collection and drain equipment, an additional water-tight corrosion-resistant pan (an air conditioner condensate drip tray or "drip pan") should be installed below the air conditioning equipment to catch overflowing AC condensate should the primary AC condensate drain become clogged.

The sketch illustrates that the condensate drain from the auxiliary condensate tray is not only separated from the primary condensate drain, it is best routed to a different destination and one at which the discharge will be noticed, prompting a repair.

Also, a basement air conditioning system condensate pump can overflow and spill into the living area if the condensate pump fails or if the condensate pump drain line becomes kinked or clogged.

Missing air conditioner condensate overflow pans

Photograph of  cooling system condensate leaks onto heat exchanger

A missing air conditioning system condensate drip tray risks leaks into the attic ceiling, where air conditioner condensate can damage the building or cause a (hidden) mold problem, especially if condensate is leaking onto the upper, hidden (by insulation) attic side of drywall forming a ceiling of a room located below the equipment.

Both the drywall and the insulation itself may become mold reservoirs.

Improperly connected or joined air conditioner condensate drain lines and overflow pan drains

Photograph of a condensate tray drainAir conditioning drip pan drains: The air conditioner's condensate overflow pan or tray requires its own separate drain. In the left photo above, the overflow pan has its own drain line, but it joins with the main air conditioner condensate drain line almost immediately.

A blockage in the condensate drain is going to lead leaks out of the air handler into the overflow pan. but since the overflow pan itself shares the same drain the pan will overflow into the building ceiling, inviting a mold problem or other damage.

But this is the most common way we see these drains installed.

Most likely the installer is considering that the main risk of a blockage in the condensate drain system is going to be inside the air handler unit itself. We're not sure what data supports this view.

The float switch approach, discussed next, might be a safer approach.

 

Float switches on air conditioning condensate overflow pans

Photograph of a float switchA condensate leak or overflow into the drip tray can trip this switch, shutting down your air conditioner or heat pump system.

Float switches on condensate trays: Some air conditioning system air handler installations provide a float switch in the condensate overflow tray. This switch has a floating lever resting in the overflow pan.

The lever senses the presence of water and "floats up" until it shuts down the air conditioning system.

This may be inconvenient in hot weather, but the installer or owner have chosen to protect the building against a potentially costly mold or other leak-related problem by shutting down the air conditioner, forcing attention to the problem.

Remember that if the condensate float tray switch senses condensate in the tray (or is otherwise defective) it will shut the air conditioning system down - if your air conditioning system seems ok but won't turn on, this switch could be one of the items to check. Thanks to Lester Richter for this tip.

Watch out: if your air conditioner has suddenly shut off and won't start, don't forget to check the condensate overflow tray for water, and if this switch was used (instead of a second condensate drain pipe), see if the switch is keeping your air conditioner turned off.

If your condensate tray switch is a lever type (shown in our photo) try pushing the lever down to see if the A/C will turn back on. Other switches may have no moving parts: you'll need to remove the condensate and dry the switch.

Details are at CONDENSATE PAN SWITCH LOCKOUT

An air conditioner condensate pan or drip tray float switch installed, the cost will principally be the fee for an HVAC service call to install the switch in the pan (trivial) and wire it to the A/C controls (less than an hour). Figure $100. to $150 for a service call to install the switch if none is already present.

If there is an drain pan overflow shutoff switch already installed but needing replacement, it should be a simpler operation since it's just a swap-in part. The wiring to the HVAC system controls will already be in place.

The condensate pan or overflow pan safety switch itself, such as the Safe-T-Switch Model SS3 made by Rectorseal and sold as a drip pan overflow shut-off switch, retails from $30.00 to $50.00 U.S. [1]

Don't forget to find and fix the cause of condensate leakage into the overflow tray or you'll continue to have air conditioner operating problems.

See CONDENSATE PAN OVERFLOW SWITCH

Evidence of Leaks into an A/C Condensate Overflow Pan May Indicate Trouble

Photograph of  leaks into condensate tray

In this photograph of the interior of an air conditioner overflow drip pan or tray, the air conditioning system condensate overflow tray shows evidence of leaks.

Since normally condensate produced in the indoor air handler is carried from the air handler interior to a condensate drain, we don't expect to see condensate falling into the condensate overflow drip tray as a normal event.

If we see evidence of leaks into the condensate tray, the air conditioning system service technician should investigate the cause of this condition.

Readers who need to clean or unclog a blocked or leaky overflowing A/C or heat pump condensate drain should
see CONDENSATE DRAIN CLEAN & DE-CLOG.

Reader Question: My condensate drain seems clean but the overflow tray still is leaking

Leaking AC condensate tray Carson Dunlop AssociatesMy AC unit inside unit overflows into the crawling space. I have cleaned the drain pipe and the air handler coil but the unit still overflows out of the coil tray. What could be the cause(s) of this? - Angel J 6/16/11

Cleaned out the condensate drain pipe with shop vac, bleach, and weak mattress blower.

Only observed draining from the primary pipe during the day (85 - 100 degrees F) but noticed a little dripping from the overflow pipe at night (not continuous). Guessing up to a cup of water from overflow.

Primary condensate pipe still clogged? What kind of plastic tube would work as snake? - Mark 6/27/11

Reply:

Angel: Carson Dunlop Associates ' sketch (above left) illustrates what happens when a condensate tray leaks, risking costly damage to the equipment. Your question is why the condensate keeps flowing out of the tray when you are confident that the drain is not blocked.

When the air handler condensate system is leaking into the crawl space and you are sure that the condensate drain pipe is unclogged and properly pitched, I have to guess that there is a problem with the condensate collection pan inside the air handler such as:

- the drain in the pan itself is clogged with debris - you'll need to turn off and look inside the air handler

- the drain pan is corroded through and leaks - it will need patching or replacement;

- the drain pan or the whole air handler is not properly leveled - it may be sloped away from the condensate pan drain opening so that condensate collects in and runs over the edge of the pan in another direction.

Let us know what you find - it'll help other readers.

Mark:

There is an almost overwhelming number of products and methods sold for cleaning out A/C condensate lines, drains, and traps, and various tricks of the trade that fit to individual installations and situations.

I've used a small flexible bottle brush to clean A/C condensate traps; if the blockage is further along the line I've successfully used a small diameter flexible plastic tube bought at the local hardware store. - DF

 




ADVERTISEMENT





Reader Comments, Questions & Answers About The Article Above

Below you will find questions and answers previously posted on this page at its page bottom reader comment box.

Reader Q&A - also see RECOMMENDED ARTICLES & FAQs

Question: is a condensate tray required by California Code?

2020/05/07 Jeff Hedtke said:

Is an overflow pan underneath my AC condenser in the attic mandatory per the building code in CA?

My house was built five years ago without one, now a leak damaged my ceiling.

My AC contractor says a pan is mandatory per CA code, but I cannot find any applicable code

Moderator reply: not exactly, but something is required to address condensate leaks

Jeff
Above on this page we state:

When an air conditioning unit is located in an attic where damage may result from air conditioning system condensate overflow from the primary condensate collection and drain equipment, an additional water-tight corrosion-resistant pan (an air conditioner condensate drip tray or "drip pan") should be installed below the air conditioning equipment to catch overflowing AC condensate should the primary AC condensate drain become clogged.

However your local building or plumbing inspector might permit alternative measures such as a leak detection system that shuts down the AC system in the event of a leak.

You'll see in California's adoption of the mechanical code, that there are options permitted. Here is a direct quote from California's building code on condensate handling:

310.2 Condensate Control

Where an equipment or appliance is installed in a space where damage is capable of resulting from condensate overflow, other than damage to replaceable lay-in ceiling tiles, a drain line shall be provided and shall be drained in accordance with Section 310.1. An additional protection method for condensate overflow shall be provided in accordance with one of the following:

The additional pan or the additional drain line connection shall be provided with a drain pipe of not less than 3/4 of an inch (20 mm) nominal pipe size, discharging at a point that is readily observed.

Here is the entire section from the

California Mechanical Code on Condensate Handling


...

Continue reading at CONDENSATE HANDLING, HVAC or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.

Or see CONDENSATE DRIP TRAY FAQs for answers to questions posted originally at this article.

Or see these

HVAC Condensate Articles

Suggested citation for this web page

CONDENSATE DRIP TRAY DEFECTS at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.


Or see this

INDEX to RELATED ARTICLES: ARTICLE INDEX to AIR CONDITIONING & HEAT PUMPS

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Ask a Question or Search InspectApedia

Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.

Search the InspectApedia website

Note: appearance of your Comment below may be delayed: if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.

Only one image can be added per comment but you can post as many comments, and therefore images, as you like.
You will not receive a notification
when a response to your question has been posted.
Please bookmark this page to make it easy for you to check back for our response.
Our Comment Box is provided by Countable Web Productions countable.ca

Comment Form is loading comments...

Citations & References

In addition to any citations in the article above, a full list is available on request.



ADVERTISEMENT